TLC3-FCR-T Engineering Manual

 

 

Doc: 70-00-0200, V3.1 Date: 20160411 

© Vector Controls GmbH, Switzerland 

Page 4 

Subject to alteration 

Display and Operation 

 

Operation mode 

 

Comfort (occupied) 

All control functions operating per set points. 

 

Economy (unoccupied): 

Set points shifted according to 

Parameters FC04.

 

Economy mode and setpoint shift may be disabled with UP06 

OFF 

Energy Hold Off 

Outputs are off, inputs monitored for alarm condition 

 

Heating 

Output activates if temperature lower than setpoint 

 

Cooling 

Output activates if temperature higher than setpoint 

 

Fan 

Fan is running, the vertical bars show active speed 1-3 

 

Manual mode 

Manual override of fan speed, fan only mode or override of time schedule active.  

 

Schedule 

Deluxe only: Time schedule is active 

Power Failure 

All the parameters and set points are memorized and do not need to be reentered. Depending on 

UP05

 the unit will 

remain switched off, switch on automatically or return to the operation mode it was in before the power failure. 

Deluxe version only

: Timer operation and daytime setting will be retained for 24h. The controller has to be connected 

to a power supply for at least 10 hours for the backup function to operate accordingly.  

Frost Protection 

The controller will enter frost protection mode if the room temperature drops below 5°C (41°F). All heating outputs will 

be fully opened. Frost protection mode will be left once the temperature reaches 10°C  (50°F). Frost protection display 

will remain until a button is pressed. Frost protection can be enabled/disabled using user parameter UP-09 

Toggle °C/°F display with one key press 

Setting UP03 = 4 allows changing °C/°F by pressing the right key for more than 2 seconds.  

Note: This setting disables access to clock settings and manual heat cool change.  

Error messages 

Following error condition may be shown: 

Err1:

 

Error temperature sensor. The temperature sensor may be damaged or not present. Verify wiring or setup.  

Err2:

 

 External input for heat / cool auto-change-over missing or damaged. Verify wiring or setup.  

FP:

 

Steady: Frost protection is active.  

Blinking: Frost protection activated in the past and is now inactive. Confirm with OPTION key.  

 

Up :  

Increase setpoint  
(Parameter setting: 
scroll menu options 
and parameters) 
 

Mode 

Display of operation 

mode 

 
 

Large Digits 

Display of input or parameter value. 

Indicators 

1 Remote 

temperature sensor 

Vertical Bar 

(fan speeds 1-3 or proportional 
output in 10% steps) 

Small Digits 

Display of setpoint, clock or 
parameter number. 
 

Right (OPTION)  

Press < 2 sec.: Select fan speed: 
Low, medium, high or auto 

Press > 2 sec.: According UP03: 
H/C change, Clock setting or °C/°F 
change(Parameter setting: ENTER 
to select menu option, accept 
parameter change) 
 

Left (POWER):  

Press < 2 sec.: Toggle Economy - 
Comfort mode or switch from OFF 
to ON 
Press > 2 sec.: Turn unit OFF. Text 
OFF displayed with current time 
(deluxe) temperature (standard) 
(Parameter setting: Return to 
previous level. ESC) 

Down :  

Decrease setpoint  
(Parameter setting: scroll menu 
options and parameters) 
 

Summary of Contents for 40-10 0114

Page 1: ...tems o radiator control chilled ceiling Simple individual room control for hotel rooms meeting rooms etc PWM or On Off Control of 2 spring return valves or 3 point on off or floating control of one 3...

Page 2: ...721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards...

Page 3: ...at the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the intercon...

Page 4: ...ft once the temperature reaches 10 C 50 F Frost protection display will remain until a button is pressed Frost protection can be enabled disabled using user parameter UP 09 Toggle C F display with one...

Page 5: ...ess UP DOWN to step through available options d1 7 d1 6 d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7...

Page 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be...

Page 7: ...ontrol of fan speeds ON OFF ON Enabled UP 03 Function of advanced mode long press right key 0 disabled 1 access to heat cool fan only change 2 access to clock settings and time programs 3 access to he...

Page 8: ...rence between switching on and switching off A small hysteresis will increase the number of switching cycles and thus the wear on fan and relays contacts 0 10 0 C 20 0 F 0 5 C 1 F FC 08 Mold Protectio...

Page 9: ...verridden by using the terminal Connecting the input to signal common returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy FC16 4...

Page 10: ...TLC3 FCR T Engineering Manual Doc 70 00 0200 V3 1 Date 20160411 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes...

Reviews: