background image

 
 

making sure that the keel cooler fits up flush with the hull, chamfering the hole if necessary. 

The 

rubber O-ring must then be installed and properly seated in the groove provided. Do not install 
the Keel Cooler without the rubber O-ring

. Adequate sealant of the correct type must be used, and a 

bead applied to the area between the O-ring and the shaft of the Keel Cooler is all that is normally 
required. The compressing of the rubber O-ring will serve to force sealant into any voids around the 
shaft as the fitting is tightened. Consult your local marine store if you are uncertain of which sealant to 
use. With the sintered “Ground Plate” models, a dab of sealant should also be applied to the fore and 
aft ends of the Keel Cooler where it meets the hull to secure its orientation. If installing the “Bare 
Bones” model, an adequate amount of sealer should be applied under the end fairing cap before the cap 
is secured to the hull with screws.  
 
When installing the thread-type Keel Cooler you will need someone to hold the Keel Cooler outside 
the boat while you tighten the nut inside. 

The mounting location should be carefully chosen. Select 

a location with a flat exterior surface, as a concave area will damage the sintering on the Keel 
Cooler when it is tightened. Also, avoid areas where lifting slings may be applied or where other 
damage may occur.  On the boat’s interior, the Keel Cooler should be installed in a location that 
is normally dry, and not where it is likely to be submerged or be subjected to frequent and/or 
heavy dousing. 

 
Consideration should be given to the fact that the Keel Cooler must be below the water-line, and the 
compressor unit must be mounted within 5' of the Keel Cooler location. On power boats it may be 
possible to mount the Keel Cooler in a vertical orientation on a section of the transom that is below the 
waterline when at rest. Keep the two tubes from the Keel Cooler separate from each other, and do not 
insulate them. 
 

It is extremely important to orientate the cylindrical Filter/Drier fitted to the Keel Cooler 
discharge tube in a vertical manner, with the arrow pointing downwards. Failure to do so will 
lead to poor system performance.   

 
Special constraints and working practices apply when installing the keel cooler on a vessel with a 
cored, metal, or carbon fiber hull. For these applications we suggest you consult a marine professional 
who is conversant in that particular field. 
 

4:2 

Grounding and cleaning

 

Provision is provided for a grounding/bonding wire to be attached. 

It is very important that the Keel 

Cooler is electrically connected

 

to a point that is at the same potential as the boat’s battery 

negative,

 

with no switch in the circuit between the Keel Cooler connection and the battery 

negative

. This connecting wire should be green in color and of 8 AWG or higher. 

 

If the Keel Cooler being installed is the type without zincs, it must be connected

 

to the vessel’s 

bonding system and also to a sacrificial zinc anode.

 This is an important safety precaution and does 

not alter the fact that a connection must be made between the Keel Cooler and a point that is at the 
same potential as the boat’s battery negative, whether the Keel Cooler has zincs or not. Bonding wire 
should be green in color and of 8 AWG or higher. 
 
If the installer is in any doubt as to how to make the grounding/bonding connections, a marine 
electrical technician should be consulted. 
 
The connections must be checked with a multi-meter after installation to ensure that Keel Cooler and 
the battery negative post are at the same potential. 
 
The sintered “Ground Plate” Keel Cooler should not be painted unless heavy and consistent fouling 
proves to be an issue. Clean occasionally with a brush, never with a metal scraper. All models of Keel 
Cooler must be inspected periodically for corrosion. 

Summary of Contents for Frigoboat Paris 35F

Page 1: ...ls Air Cooled Pumped Water Cooled Keel Cooled and Keel plus Air Cooled Systems using Secop formally Danfoss BD 35 or BD 50 compressors It is important to read this manual thoroughly before installing and operating a Frigoboat system Veco NA 301 352 6962 info veco na com Rev 39 02 2019 ...

Page 2: ...nit or an Air Add On air cooled condenser is installed together with a Keel Cooler ensure that the fan is operated only when the boat is out of the water and then switched off when the boat is launched Never defrost an evaporator using a hard or sharp object like an ice pick knife or screwdriver Never defrost using an appliance that generates high heat like a heat gun or hairdryer Natural defrosti...

Page 3: ...F Capri 35F Capri 50F Air cooled These units are designed to be mounted with compressor right way up on a horizontal surface in areas where they will not be susceptible to physical or water damage but accessible for service They require good ventilation preferably expelling the heated air to another location by attaching a flexible duct of not more than 6 in length to the duct ring on the unit A d...

Page 4: ...ill deliver 12v even if the system is connected to a 24v supply Full wiring instructions are included with the compressor If more than one W35 or W50 is sharing a single water pump they must be plumbed in a parallel configuration so that the pump output is split equally to each unit and each unit receives water direct from the pump The water discharges from each unit can then be combined into one ...

Page 5: ...tion of the transom that is below the waterline when at rest Keep the two tubes from the Keel Cooler separate from each other and do not insulate them It is extremely important to orientate the cylindrical Filter Drier fitted to the Keel Cooler discharge tube in a vertical manner with the arrow pointing downwards Failure to do so will lead to poor system performance Special constraints and working...

Page 6: ... control running at 2000 RPM All others must have either a manually adjustable compressor speed controller like a Speed Board or alternatively an automatic smart speed control such as the Merlin II Smart Speed Controller If your compressor unit comes with a Speed Board installed and you are installing a Merlin II the Speed Board must be removed from the Danfoss Secop controller 5 3 Fault Codes Pro...

Page 7: ... to the controller there may be a delay of up to 30 seconds before the compressor starts Note 2 If initial power is applied that is above the low voltage threshold but below the cut in voltage value see 5 3 1 digital displays will be lit but the compressor will not start and there will be no fault indication on the LED System will start when voltage is increased above the cut in value Note 3 The e...

Page 8: ...nels in the evaporator Never attempt to bend a plate downwards over a pipe as damage may result The area to be bent should be warmed with a hair dryer or heat gun to approximately 200 F before bending in order to prevent the paint from cracking There are sections of the evaporator that must not be bent and these are indicated on the Bending Sheet included with the evaporator If the Bending Sheet h...

Page 9: ...plastic plate on the evaporator so that it lays in the special grooves of the plastic plate Finish by tightening the clamping screw If using the Coastal MK3 digital thermostat the sensor mounts on the icebox wall not on the evaporator Full instructions are included with the Coastal MK3 thermostat 6 5 Mounting evaporators See also 6 1 Location H and B type evaporator plates can be mounted in any po...

Page 10: ...arefully coiled up and secured out of the way to avoid damage When securing the sensing tube make sure contact is made only with the evaporator at the point where it is attached under the plastic mounting plate and that it does not touch any part of the aluminum or copper tubing If necessary the tube can be protected with small bore plastic tubing either by sliding it on prior to attaching to the ...

Page 11: ...e top of the barrier 1 should be sufficient or 3 or more holes of the same size as the one behind the spillover fan All other holes gaps etc in the barrier must be completely sealed including drains 8 2 Electrical Connections The Spillover Kit with integral mechanical thermostat must be powered by an independent 12v supply This may be from a breaker on the electrical panel or via an in line 2 amp ...

Page 12: ...stalled until the very last moment when you are ready to connect the system together Once the dust caps have been removed it is imperative that the exposed components and surfaces be kept free of dust dirt construction debris etc After you have removed the plugs keep them in a safe place in case you need to remove or replace a component later Push the male and female fittings together and then car...

Page 13: ...ction Use either a breaker or fast blow fuse with 15 amp rating for a 12v supply or 7 5 amp for 24v 10 4 Connections Power Connect the power supply to the controller on the top two terminals using slip on connectors and wire size no greater than 10 AWG observing the correct polarity If wire of greater than 10 AWG is used for the power supply this must terminate remote from the controller and down ...

Page 14: ...e factory installed on the terminals marked F Black or Blue and Red If the wires are reversed the fan will not run The K50F and W50F models have a small oil cooler fan installed Full instructions are included with the W35F and W50F 10 7 Connections Pump The W35F and W50F model use a 12v pump that must be connected through a relay PN E251002 that is activated from the fan terminals on the controlle...

Page 15: ...roller or compressor to be faulty Controller can be removed by unscrewing the retaining screw or by levering the plastic case over the screw head 11 1 Compressor not running no start attempt Probable cause Action 1 Supply voltage too low Check voltage with a multi meter at the terminals on the controller This must be 11 7v or more for a 12v supply 24 2v at 24v for compressor to start Inspect power...

Page 16: ...lty or inadequate power supply Most likely Monitor the supply voltage at the power terminals on the controller before during and after start attempts to ensure that it does not fall below threshold levels If it does check power supply ground connections and components for integrity Check for correct wire sizing Charge batteries if necessary 2 Faulty fan or pump relay or unauthorized component inst...

Page 17: ...ing in others the system may be low on refrigerant or overcharged Call Veco NA for advice or go to www veco na com Technical Information 7 Drain left unplugged If your icebox is equipped with a drain in the bottom of the box this must be blocked off to prevent loss of cold air The drain should only be used if you revert to melting ice or after a major clean up 8 Tubing hole left unplugged The hole...

Page 18: ...ulation 11 5 Excessive frost build up Note This is the result of moist air being allowed to enter the box Problems are compounded when cold dense air leaks from the lower area of the box through an open drain or weak door seal and is replaced by warm humid air being drawn in elsewhere Probable cause Action 1 Drains and holes not plugged Make sure all drains and holes in the floor and walls of the ...

Page 19: ...ication Acts of God or service by personnel other than those pre authorized by the Company Damage failure or malfunction resulting from inadequate or faulty power supply to the system or improper faulty or unsafe vessel wiring Damage failure or malfunction due to foreign substances being injected into the system including but not limited to additional refrigerant oil conditioner flushing fluid Tha...

Reviews: