AC35

Horizontal mounting on the ceiling 

Threaded rods, wire suspension kits and ceiling brackets 

for ceiling mounting are available as accessories, see fig. 

7 and 8 and separate manuals.

 

Vertical mounting PL3JK

Units from 1,5 metres and  longer may be used vertically. 

For vertical mounting, all units must be supplemented 

with a vertical kit containing everything needed for a 

practical installation of floor standing units. 

The unit can be reversed and placed on either side of the 

door. Connections and PC Board PLS are positioned 

near floor level when the air curtain is placed to the left 

of the door and at the top when it is placed to the right 

(seen from the inside). 

The accompanying floor edging is attached to the floor 

with fasteners appropriate to the surface. 

Two units can be mounted directly on top of each other, 

the floor edging is then used as a joining bracket. 

The air curtain must be secured to wall or ceiling, use 

PL3JK (accessory). 

A design kit which gives a neater installation that 

conceals cables and pipes is available as accessory, see 

accessories pages.

See separate manual.

Electrical installation

The installation, which should be preceded by an om-

nipolar switch with a contact separation of at least 3 

mm, should only be wired by a competent electrician 

and in accordance with the latest edition of IEE wiring 

regulations. 

The control system is pre-installed in the air curtain with 

an integrated control card, (see fig. 2).  

PLS is supplied pre-programmed with quick-fit connec-

tions.  

Modular cables are connected to the control board. See 

manual for PLS.

 

Unit with water heating

Connected via the built-in PLS control board with  

2 m cord and plug.

 

Unit with electrical heating

The installation is made on the top of the unit (horizon-

tal) or on the reverse (vertical). 

Control supply is 230V~ and cable is routed from the 

built-in PLS control board.  

Power supply for heating (400V3N~) is connected to 

terminal block in the internal connection boxes. 2-metre 

and longer units require dual power supplies. The largest 

cable diameter for the terminal block is 16 mm². The 

cable glands used must meet the protection class require-

ments. In the distribution board it is to be indicated that 

”the air curtains can be supplied from more than one 

connection”.

 

See wiring diagrams.

Start-up (E)

Note! When using for the first time or when starting up 

after a long period of disuse, a small amount of smoke 

and a slight odour may occur temporarily, which is 

completely normal.

 

Type

Output 

[kW]

Voltage 

[V]

Minimum area 

2

 

[mm

2

]

AC35-10-E08

8

400V3N~ 

2,5

AC35-15-E12

12

400V3N~ 

4

AC35-20-E16

1

8 / 8

400V3N~ 

2,5 / 2,5

AC35-25-E20

1

8 / 12

400V3N~ 

2,5 / 4

1

 2 m and 2.5 m-units are connected with two power supplies, see p. 2. 2.5 meter units have elec-

tric batteries with two different effects, and the electric battery on the left, on a horizontal unit, 

seen from inside the room, has the highest effect.

2

 Dimensioning of external wiring shall comply with applicable regulations and local deviations 

may occur.

Summary of Contents for AC35

Page 1: ...AC35 Art nr 172786 01 GB Installation and maintenance instruction for air curtains IMPORTANT Read these instructions before the product is installed and used Save the instructions for future use 2 ...

Page 2: ...supplied with electrical heating or hot water heating AC35 is intended for en trances and smaller doors up to 3 5 metres in height Protection class for units with electrical heating IP20 Protection class for units with water heating IP21 Operation Air is drawn in at the top rear of the unit and blown out downwards outwards so that it shields the door ope ning and minimizes heat loss To achieve the...

Page 3: ...the air curtain with an integrated control card see fig 2 PLS is supplied pre programmed with quick fit connec tions Modular cables are connected to the control board See manual for PLS Unit with water heating Connected via the built in PLS control board with 2 m cord and plug Unit with electrical heating The installation is made on the top of the unit horizon tal or on the reverse vertical Contro...

Page 4: ... and subsequent water leakage during connection to water supply pipe work Adjustment of the air curtain and air flow The direction and speed of the air flow should be ad justed considering the load on the opening Pressure forces affect the air stream and make it bend inwards into the premises when the premises are heated and the outdoor air is cold The air stream should therefore be directed outwa...

Page 5: ...trical coil to cool 3 Determine the cause of overheating and rectify the fault 4 Connect the air curtain again All motors are equipped with an integral thermal safety cut out This will operate stopping the air curtain should the motor temperature rise too high The cut out will automatically reset when the motor temperature has returned to within the motor s operating limits Temperature control Tem...

Page 6: ... incoming water is heated enough If the fault cannot be rectified please contact a qualified service technician Residual current circuit breaker E When the installation is protected by means of a residual current circuit breaker which trips when the appliance is connected this may be due to moisture in the heating element When an appliance containing a heater element has not been used for a long p...

Page 7: ...L3525 8 M8 DN20 3 4 outside thread 160 A 43 205 92 364 40 PLS 2 m 2 5 m L1 528 275 40 23 L mm A mm AC35 10 1073 72 AC35 15 1583 72 AC35 20 2073 74 AC35 25 2583 71 L1 mm AC35 15 1589 AC35 20 2079 AC35 25 2589 AC35 10 35 15 4 M8 AC35 20 6 M8 AC35 25 8 M8 ...

Page 8: ...e front is blocked in open position with the front hatch hook Fig 2 Control card PLS is integrated in the air curtain at delivery Fig 1B When the front has been removed it is important to be sure it is firmly seated in the front locks again 100 Fig 3 Minimum distance ...

Page 9: ...9 AC35 A B A 160 L B 160 875 875 A B 160 770 745 745 Fig 5 M8 holes for mounting Fig 4 B A 3 4 Filling the water coil L mm AC35 10 750 AC35 15 1260 A B AC35 205 92 1 2 ...

Page 10: ...10 AC35 Fig 6 See separate manual for PA34WB AC35 PA34WB 20 mm 79 19 120 11 40 PA34WB AC35 W 15 2 pcs AC35 W 20 3 pcs AC35 W 30 4 pcs A B D E C F ...

Page 11: ...11 AC35 PL3JK PA34WS PA34CB PA34TR PA34CB Fig 7 PA34TR PA34CB See separate manual for PA34TR Fig 8 PA34WS PA34CB See separate manual for PA34WS ...

Page 12: ...12 AC35 Note The top of the air curtain must be secured in the wall or ceiling Fig 9 See separate manual for PL3JK PL3JK ...

Page 13: ... m PA34WS20 Wire suspension kit for 2 meter units Units 6 pcs AC35 20 Fig 8 PA34WS30 Wire suspension kit for 2 5 meter units Units 8 pcs AC35 25 Fig 8 PA34TR15 Threaded rods for 1 and 1 5 meter unit Units 4 pcs AC35 10 15 Fig 7 Threaded rods for ceiling moun ting Used with ceiling mounting brackets PA34CB Length 1 m PA34TR20 Threaded rods for 2 meter unit Units 6 pcs AC35 20 Fig 7 PA34TR30 Threade...

Page 14: ... unit PLSDC door switch and 2 modular cables with RJ12 quick connects 1 pc 3 m 1 pc 5 m IP30 PLSRTX External room temperature sensor 70x33x23 mm SIRECJ4 RJ11 coupler 4 4 Used to join together two RJ11 or RJ12 connec tors SIRECJ6 RJ12 coupler 6 6 SIRECC403 RJ11 modular cable 4 4 Length 3 m SIRECC405 Length 5 m SIRECC410 Length 10 m SIRECC415 Length 15 m SIRECC603 RJ12 modular cable 6 6 Length 3 m S...

Page 15: ...ctuator 230V Transformer 230V 200V 170V 145V 120V 100V N Black Black Grey Blue Blue White White C2 C1 ROOM Internal sensor Motor protection C C C Transformer 230V 200V 170V 145V 120V 100V N Yellow Orange Red Brown Black Green Blue N N 3515E C C C C 3525E 3520E 230V ...

Page 16: ...ansformer 230V 200V 170V 145V 120V 100V N Black Blue White White Supply 230V C2 C1 ROOM Internal sensor Motor protection Transformer 230V 200V 170V 145V 120V 100V N Yellow Orange Red Brown Black Green Blue 3510W C C C 3515W C C C C 3225W 3520W ...

Page 17: ...ent see manuals for PLS 230V 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY PLSB1 PLSB1 PLSRTX optional PLSUB1 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY PLSB1 PLSRTX optional PLSUB1 ...

Page 18: ...18 AC35 PLS Basic AC35 W C C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY 230V PLSB1 SD230 PLSRTX optional PLSUB1 ...

Page 19: ...t see manuals for PLS C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY C2 X5 C1 X4 ROOM X3 Pot Unit ID N L PE N L PE ACTUATOR SUPPLY 230V 230V 230V PLSB1 SD230 SD230 SD230 PLSB1 PLSB1 PLSUB1 PLSRTX optional ...

Page 20: ...tt 556138 3166 VAT no SE556138316601 Postal Cheque Service 48 51 08 5 Bank Transfer 926 0365 Fax Int 46 451 410 80 E mail veab veab com Phone Int 46 451 485 00 Website www veab com NB We reserve us from typographical errors and the right to make changes and improvements to the contents of this manual without prior notice AC35 20 ...

Reviews: