ROBUST - V
5
Safety instructions for all models
If the fan heater is incorrectly installed and/or used, it may give rise to danger.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capa-
bilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of
the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
Caution!
• Some parts of this product can become very hot and cause burns. Particular attention has to be given
where children and vulnerable people are present.
• Incorrect installation may cause personal injury.
• Do not use this fan heater in the immediate vicinity of a shower, bathtub or swimming pool.
• The fan heater must not be covered, since this may cause overheating and involve the risk of fire (see also Figure A).
• The fan heater must not be located immediately below or in front of a power socket.
• The plug/CEE connector must be readily accessible.
• Place the fan heater so that any combustible material in the vicinity will not be ignited.
• When work is done on the fan heater or when electrical work is done, the power supply to the fan heater must al-
ways be isolated.
• Work on the heater, such as removing the cover, etc., may be done only by authorized personnel.
• If the power supply cable of the fan heater is damaged, it may be changed only by authorized personnel.
• When the cover is being fitted, tighten the screws 2 ½ turns after the screw gasket has been nipped, in order to
maintain the IP classification of the fan heater.
A
GB
Important!
When using heater as a portable,
the brackets on the heater should
be swung out of the way and the
bracket holder removed as per
instructions on page 7.
Technical data Robust V
Type
Robust
Total
output
(W)
Heat
output
(W)
Motor
output
(W)
Adjustment
range
(kW)
Voltage
Current
(A)
Air
volume
(m³/h)
Temperature-
rise
(°C)
Weight
(kg)
V3R
3065
3000
65
0-2-3
230V~ 50/60Hz
9.1/13.5
400
21
11
V3
3065
3000
65
0-1.5-3
400V3~ 50/60Hz
4.2/4.8
400
21
12
V3,6
3665
3600
65
0-1.8-3.6
440V3~ 50/60Hz
4.6/5.2
400
25
12
V5N
5065
5000
65
0-2.5-5
230V3~ 50/60Hz
10.7/12.4
700
20
12
V5
5065
5000
65
0-2.5-5
400V3~ 50/60Hz
6.7/7.7
700
20
12
V6
6065
6000
65
0-3-6
440V3~ 50/60Hz
7.3/8.3
700
24
12
V6T
6060
6000
60
0-3-6
500V3~ 50/60Hz
6.35/7.38
700
24
14