User manual
Document no. : 032189
Version : V1.5
MC 785 CHILLER-2
Customer: Heinen & Hopman
Page: 8 of 16
4.1
Parameter table.
No.
Description
Range
Unit
Default
Sensor settings
P 01
P 02
Offset inlet temperature sensor-1
Offset outlet temperature sensor-2
-10.0...+10.0
-10.0...+10.0
O
C
O
C
0.0
0.0
P 10
P 11
P 12
P 13
Value HP2 pressure sensor-1 at 4mA
Value HP2 pressure sensor-1 at 20mA
Offset HP2 pressure sensor-1
Delay factor pressure sensor-1
-10.0...30.0
-10.0...30.0
-10.0...+10.0
0...100
bar
bar
bar
%
0.0
25.0
0.0
10
P 14
P 15
P 16
P 17
Value OIL2 pressure sensor-2 at 4mA
Value OIL2 pressure sensor-2 at20mA
Offset OIL2 pressure sensor-2
Delay factor pressure sensor-2
-10.0...30.0
-10.0...30.0
-10.0...+10.0
0...100
bar
bar
bar
%
0.0
10.0
0.0
50
P 18
P 19
P 20
P 21
Value LP2 pressure sensor-3 at 4mA
Value LP2 pressure sensor-3 at 20mA
Offset LP2 pressure sensor-3
Delay factor pressure sensor-3
-10.0...30.0
-10.0...30.0
-10.0...+10.0
0...100
bar
bar
bar
%
0.0
10.0
0.0
50
P 22
P 23
P 24
P 25
Value HP1 pressure sensor-4 at 4mA
Value HP1 pressure sensor-4 at 20mA
Offset HP1 pressure sensor-4
Delay factor pressure sensor-4
-10.0...30.0
-10.0...30.0
-10.0...+10.0
0...100
bar
bar
bar
%
0.0
25.0
0.0
10
P 26
P 27
P 28
P 29
Value OIL1 pressure sensor-5 at 4mA
Value OIL1 pressure sensor-5 at20mA
Offset OIL1 pressure sensor-5
Delay factor pressure sensor-5
-10.0...30.0
-10.0...30.0
-10.0...+10.0
0...100
bar
bar
bar
%
0.0
10.0
0.0
50
P 30
P 31
P 32
P 33
Value LP1 pressure sensor-6 at 4mA
Value LP1 pressure sensor-6 at 20mA
Offset LP1 pressure sensor-6
Delay factor pressure sensor-6
-10.0...30.0
-10.0...30.0
-10.0...+10.0
0...100
bar
bar
bar
%
0.0
10.0
0.0
50
P 40
P 41
P 42
P 43
P 44
Number extra LMS exchanger sensors
Offset LMS exchanger sensor1
Offset LMS exchanger sensor2
Offset LMS exchanger sensor3
Offset LMS exchanger sensor4
0..4
-10.0...10.0
-10.0...10.0
-10.0...10.0
-10.0...10.0
O
C
O
C
O
C
O
C
2
0.0
0.0
0.0
0.0
Heating
P100
P101
P102
Offset first heater
Differentiation first heater
Delay first heater
-10.0...+10.0
0.1...10.0
0...999
O
C
O
C
Sec.
0.0
1.0
60
P103
P104
P105
Offset second heater
Differentiation second heater
Delay second heater
-10.0...+10.0
0.1...10.0
0...999
O
C
O
C
Sec.
-1.0
1.0
120
P106
P107
P108
Offset third heater
Differentiation third heater
Delay third heater
-10.0...+10.0
0.1...10.0
0...999
O
C
O
C
Sec.
-2.0
1.0
180
P109
P110
P111
Offset fourth heater
Differentiation fourth heater
Delay fourth heater
-10.0...+10.0
0.1...10.0
0...999
O
C
O
C
Sec.
-3.0
1.0
240