VDH Alfanet 95 User Manual Download Page 5

Para-
meter

Description of Parameter

Range

Standard
value

5

80

Night shift (offset)

-10.0..+10.0

0,0

90
95
96
97
98
99

Network number
Software version
Production year
Production week
Series number (x1000)
Series number (units)

1..250
0..255
00..99
1..52
0..255
0..999

1

-
-
-
-
-

* Technical data.

Type

: ALFANET 95 Cool/Defrosting Thermostat

    CONTROL-UNIT:

Range

: -50,0/+50,0

C

Read-out

: 3-digit 7-segments display

Accuracy

: ± 0,5 % of  the range.

Status LEDs

: ALARM, COMPR., FAN, DEFR.1 and DEFR.2 (On display through 

C

 key)

Operation

: through pushbuttons on the front.

Front

: Polycarbonate IP65

Network

: RS485-network (2xtwisted-pair shielded) 

Dimensions

: 35 x 77 x 71,5mm (hwd)

Panel cutout

: 29 x 70mm (hw)

    I/O-UNIT:

Supply

: 230 Vac 50/60Hz (-5/+10%) Max. 3VA

Relays

: These two relays have one common;
   Ry-1 Alarm

SPDT (NO,NC) 250V/8A (cos 

=1)

   Ry-2 Cool SPST (NO) 

250V/8A (cos 

=1)

  These three relays have one common;
   Ry-3 Fan SPST (NO) 

250V/8A (cos 

=1)

   Ry-4 Defrost-1

SPST (NO) 250V/8A (cos 

=1)

   Ry-4 Defrost-2

SPST (NO) 250V/8A (cos 

=1)

Sensors

: 3x SM 811 (PTC 1000

/25

C).

Contact input

: 1x Day/Night switch (open = night shift active) or
  Door contact (cooling and fan off when door is open)

Dimensions

: 90x71x58mm (hwd) for  rail mounting

- Equipped with memory protection in case of power failure.
- Equipped with a self-testing function.
- Equipped with sensor failure detection.
- Connection through screw terminals on supply/relay module.
- Special models available on request.