* Alarm function

When there is an error message or an alarm, an error code message appears in the display. The

ALFANET 95

 remembers this failure message, even if the problem has already been solved. The

failure message can be reset with the 

SET

 key. If, after pressing the 

SET

 key (=reset alarm) the alarm

is not yet solved, then the 

ALFANET 95

 shows the temperature and error code alternately, if the alarm

has been solved then the error code disappears and the temperature is shown again.

* Fan control settings

The 

ALFANET 95

 has various adjustment possibilities for  the Fan. Normally, the fan is always running

unless one of the parameters below is set at 1:

Parameter 20 = 1: Fan switch differential active.

The  fan  only  active  if  the  temperature  of  the  defrost  sensor  is  lower  than  the  control  sensor
temperature minus the temperature of the switch differential fan (P21)
 {Fan on if  T

defrost 

< (T

control 

- T

fandiff.

)}.

Parameter 25,26: Fan switching on delay after defrosting.

After defrosting and draining of the humidifier, to prevent the fan from running immediately and thus
blowing warm air into the cell, the following two conditions can be set, i.e.;
a. The fan is blocked until the defrost-sensor measures a temperature that is lower than the set

switching on temperature of  the fan (P25).

b. The fan is blocked until the switching on delay of  the fan (P26) is over, when the defrost- sensor

reaches  the  switching  on  temperature  (P25)  within  the  switching  on  delay,  then  the  fan  is
unblocked.

Parameter 22 = 1: Fan is off, when the compressor is off.

The fan is turned off if the compressor is off. This happens with a delay of parameter 23.

* Defrost control possibilities.

The automatic defrost is started on a real-time (P60) base and stops after the maximal defrost time
(P30), or earlier if the defrost sensor has reached the defrost end-temperature (P31). The 

ALFANET

95

 has a number of automatic defrost possibilities that can be set with the following parameters;

Parameter 24

Type of defrost:

The 

ALFANET 95

 has three possibilities for defrosting; 

P24 = 0

For defrost only the relay FAN is switched on (natural defrosting).

P24 = 1

For defrosting only the relay DEFR. is switched on (hot gas / electrical defrosting).

P24 = 2 

For  defrosting  both  the  DEFR.  and  the  FAN  relays  are switched on (hot
gas/elefan defrosting).

Parameter 60 = 1Defrosting on the  real-time clock

Here, the defrosting is started at set times (P61 to P71).