background image

4

* Parameters ALFA 75 RTDF.

Para-
meter

Description Parameter

Range

Default
Value

01
02
03
04
05
06
07
08

Switching differential
Minimum setpoint
Maximum setpoint
Read out above -10

/

C per 1

/

C

Offset Control-sensor
Read out Defrost-sensor
Offset Defrost-sensor
Defrost sensor present

0,1..15,0

/

C

-50..+50

/

C

-50..+50

/

C

0=No, 1=Yes
-15,0..+15,0

/

C

-
-15,0..+15,0

/

C

0=No, 1=Yes

0,5
-50
+50

0

0,0

-

0,0

0

10
11
12
13
14

Start-up delay Cooling 
Switch-off delay Cooling 
Parameter 10/11 in Sec. or Min.
Minimum on-time Cooling
Minimum off-time Cooling

0..99
0..99
0=Sec., 1=Min.
0..99 Minutes
0..99 Minutes

0
0
0
0
0

20
21
22
23
24

25
26
27

Switching differential Fan active
Switching differential Fan
Fan off as Compressor is off
Switch-off delay Fan
Defrost mode    0=only fan-relay, 
                1=only defrost-relay
Switch-on delay-temp. fan after defrost
Switch-on delay-time fan after defrost
Dripoff-time

0=No, 1=Yes
0..+50

/

C

0=No, 1=Yes
0..90 Minutes
0=Natural
1=Hotgas/Elec.
-50..+50

/

C

0..90 Minutes
0..90 Minutes

0

2,0

0
0
0

2,0

0
0

30
31
32
33
34
35

36
37

Defrost-interval-time
Maximum defrost-time
End of defrost temperature
Compressor on while defrosting
Defrosting on compressor-time
Temperature display locked during
 defrost cycle
Start with defrost after power-up
Defrost on-delay after power-up

1..99 Hours
0..99 Minutes
-50..+50

/

C

0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes

0=No, 1=Yes
0..99 Minutes

12
15

2,0

0
0
0

0
0

40

41
42
43
44
45
46
47

Alarm mode

Minimum alarm setpoint
Maximum alarm setpoint
Time-delay minimum alarm 
Time-delay maximum alarm
Control-delay after power failure
Compressor on at control-sensor failure
Compressor off at minimum alarm

0=None, 
1=Absolute
2=Relative
-50..+50

/

C

-50..+50

/

C

0..99 Minutes
0..99 Minutes
0..99 Minutes
0=No, 1=Yes
0=No, 1=Yes

1

-50
+50

0
0
0
0
1

50
51
52

Realtime hours
Realtime minutes
Time correction (at realtime clock)

0..23 Hours
0..59 Minutes
-99..+99 Sec./Yr

-
-
0

60
61
62
63
64
65
66
67
68
69
70
71
72

Real-time defrost active
Defrost-time 1 (Hours)
Defrost-time 1 (Minutes) steps 10 Min.
Defrost-time 2 (Hours)
Defrost-time 2 (Minutes) steps 10 Min.
Defrost-time 3 (Hours)
Defrost-time 3 (Minutes) steps 10 Min.
Defrost-time 4 (Hours)
Defrost-time 4 (Minutes) steps 10 Min.
Defrost-time 5 (Hours)
Defrost-time 5 (Minutes) steps 10 Min.
Defrost-time 6 (Hours)
Defrost-time 6 (Minutes) steps 10 Min.

0=No, 1=Yes
0..23/off Hours
0..50/off Min.
0..23/off Hours
0..50/off Min.
0..23/off Hours
0..50/off Min.
0..23/off Hours
0..50/off Min.
0..23/off Hours
0..50/off Min.
0..23/off Hours
0..50/off Min.

0

off
off
off
off
off
off
off
off
off
off
off
off

80
81
82
83
84

Night-shift (offset) of Setpoint
Start day (Hours)
Start day (Minutes) step 10 Min.
Start night (Hours)
Start night (Minutes) step 10 Min.

-10.0...10.0

/

C

0..23/off Hours
0..50/off Min.
0..23/off Hours
0..50/off Min.

0

off
off
off
off