ALFA(NET) 51 PI -50/+50°C 

Doc.no.: 180142   version 1.1 

 

 

 

 

    

 

Pagina 3 van 8 

10

 

Error messages 

In the display of the ALFA(NET) 51 PI the following error messages can appear: 

 

Lo1 

- Minimum alarm. 

 

Solution E1: 

 

Hi1 

- Maximum alarm. 

 

- Check if the sensor is connected correctly. 

 

E1 

- Sensor-1 failure. 

 

- Check sensor (1000

Ω

/25°C). 

 

 

 

 

 

 

- Replace sensor. 

 

 

-L- 

- In case of sensor short-circuit the display alternates between error-code E.. 

 

 

  and -L-, as indication for a short-circuit sensor. 

 

-H- 

- In case of open-circuit sensor the display alternates between error-code E.. 

 

 

  and -H-, as indication for a open-circuit sensor. 

 

Reset Alarm.  When a error-messages appears it can be resetted by pushing the SET key.  

 

 

The function of this key depends on parameter P37. 

 

 

11

 

Technical data 

Type 

ALFA 51 PI -50/+50°C or 

ALFANET 51 PI -50/+50°C  

Range 

-50/+50°C   

readout per 0,1°C 

Supply 

100…240 Vac 50/60Hz    max. 10VA 

Display 

3-digit 7-segment  

LED display 

Sensor 

SM 811  2-Wire  

PTC 1000

Ω

/25°C 

Relays 

Ry1 = SPST (NO)  

250V/8A cosphi=1 or 250V/5A cosphi=0.4 

Ry2 = SPST (NO)  

250V/8A cosphi=1 or 250V/5A cosphi=0.4 

Ry3 = SPDT (NO/NC) 

250V/8A cosphi=1 or 250V/5A cosphi=0.4 

Relays have one common (C) 

Analogue output 

0-10Vdc PI-output  

Rload = min. 10KOhm  

Communication 

RS-485 Network  

Twisted-pair shielded 

only at ALFANET 

A, B, 0V  (Twist A and B) 

Connect according to newest norm ANSI/TIA/EIA-485-A-98 

Control 

By four push buttons on the front 

Front 

Polycarbonate 

Dimensions 

35 x 77 x 71,5 mm  

(H x W x D) 

Panel cut out 

28 x 70 mm  

(H x W) front mounting 

 

 

- Provided with memory protection during power failure. 

 

- Connection with screw terminals. 

 

- Equipped with senor failure detection. 

 

- Special versions are on request available. 

 

Summary of Contents for ALFA 51 PI

Page 1: ...out or set by an PC with the ALFANET program connected thru an ALFANET PC Interface 2 Installation On the connection diagram of the ALFA NET 51 PI is shown how the sensors analogue output power supply relays and optional network are to be connected After connecting the ALFA NET 51 PI to the power supply a self test function is started As this test is finished the measured temperature appears in th...

Page 2: ...DOWN keys after releasing the SET key Pressing the SET key again displays the maximum control value P43 in percentages which can now be adjusted with the UP and DOWN keys after releasing the SET key By pressing the SET key again the measured temperature is shown in the display again About 15 seconds after releasing the keys the measured temperature is shown in the display 7 Status of the relays By...

Page 3: ...chnical data Type ALFA 51 PI 50 50 C or ALFANET 51 PI 50 50 C Range 50 50 C readout per 0 1 C Supply 100 240 Vac 50 60Hz max 10VA Display 3 digit 7 segment LED display Sensor SM 811 2 Wire PTC 1000Ω 25 C Relays Ry1 SPST NO 250V 8A cosphi 1 or 250V 5A cosphi 0 4 Ry2 SPST NO 250V 8A cosphi 1 or 250V 5A cosphi 0 4 Ry3 SPDT NO NC 250V 8A cosphi 1 or 250V 5A cosphi 0 4 Relays have one common C Analogue...

Page 4: ...m P01 1 3 2 03 Function Relay 3 same as parm P01 1 3 3 04 Function PI output 1 Cool 2 Heat 3 Cool and Heat 1 3 1 05 Offset temperature sensor Calibration 15 15 0 C 0 0 06 Offset PI 15 15 0 C 0 0 07 P band setting 0 0 20 0 C 5 0 08 I time setting I action not active at P08 0 of P04 3 0 99 Minutes 0 off 10 Switch on stage two 0 Temp 1 Time 0 11 Switch on stage three 0 Temp 1 Time 0 12 Switch on dela...

Page 5: ...larm 0 1 0 36 Reset alarm relay after recovering alarm 0 No 1 Yes 0 37 Reset alarm relay after manual reset 0 No 1 Yes 0 40 Start up delay after power failure 0 99 Minutes 0 41 Forced relay function at sensor failure 0 None 1 Cool 2 Heat 0 2 0 42 43 45 Minimum control value Maximum control value Apply minimum and maximum control value 0 100 0 100 0 No 1 Yes 0 100 0 90 Network number only at ALFANE...

Page 6: ...ALFA NET 51 PI 50 50 C Doc no 180142 version 1 1 Pagina 6 van 8 13 Function diagram ...

Page 7: ...ALFA NET 51 PI 50 50 C Doc no 180142 version 1 1 Pagina 7 van 8 14 Connections ...

Page 8: ...Doc no 180142 version 1 1 Pagina 8 van 8 15 Dimensions 16 Address VDH Products B V Tel 31 0 50 30 28 900 Productieweg 1 Fax 31 0 50 30 28 980 9301 ZS Roden Email info vdhproducts nl The Netherlands Internet www vdhproducts nl ...

Reviews: