2

* Setting internal parameters.

Next to the adjustment of the setpoint, some internal settings are possible like differential, sensor-
offset, setpoint range and the function cooling or heating.
By pushing the 

DOWN

 key more than 10 seconds, you enter the 'internal programming menu'. In the

left display the upper and lower segments are blinking. With the 

UP

 and 

DOWN

 keys the required

parameter can be selected (see table for the parameters).
If the required parameter is selected, the value can be read-out by pushing the 

SET

 key. Pushing the

UP

 or 

DOWN

 keys together with the 

SET

 key allows you to change the value of this parameter. If after

20 seconds no key is pushed, the 

ALFA 31 DP

 changes to its normal operation mode.

* Adjustment sensor.

The sensor can be adjusted by using the Sensor Offset (parameter 04). Indicates the 

ALFA 31 DP

e.g. 2°C too much, the Sensor Offset has to de decreased by 2°C.

* Error messages.

In the display of the 

ALFA 31 DP

 the following error messages can appear:

Er

 

- Sensor broken.  Solution:

- Check if the sensor is connected correctly.
- Check the sensor (1000

Ω at 25°C).

- Replace the sensor.

EE

 

- Settings are lost.  Solution:

- Reprogram the settings.

* Technical details.

Model

: ALFA 31 DP

Range

: -10/+40°C, readout at 0,1°C

Supply

: 230 Vac (optional 24Vac/dc or 12Vac/dc see sticker)

Relays

: SPDT 250V/16A(C-NO), 8A(C-NC) (cos phi=1)

Control

: by pushbuttons on the front.

Front

: Polycarbonate 

Sensor

: SM 811/2m (1000

Ω at 25°C)

Sizes

: 35 x 77 x 71,5mm (hwd)

Panel hole

: 28 x 70mm (hw)

- Provided with memory protection during power failure.
- Connection with screw terminals on the backside.
- Equipped with self test function and sensor failure detection.
- Special version are available upon request.