VDH ALFA 19 User Manual Download Page 3

3

* Setting internal parameters.

Next to the adjustment of the setpoint, some internal settings are possible like differential, sensor-
offset, set point range and the function humidify or dehumidify.
By pushing the 

DOWN

 key more than 10 seconds, you enter the 'internal programming menu'. In the

left display the upper and lower segment are blinking. Over the 

UP

 and 

DOWN

 keys the required

parameter can be selected (see table for the parameters).
If the required parameter is selected, the value can be read-out by pushing the 

SET

 key. Pushing the

UP

 or 

DOWN

 keys together with the 

SET

 key allows you to change the value of this parameter.

If after 20 seconds no key is pushed, the 

ALFA(NET) 19

 changes to it's normal operation mode.

* Parameters ALFA(NET) 19.

PARA-
METER

DESCRIPTION PARAMETER

RANGE

STANDARD
VALUE

01
02
03
04

Switching differential
Minimum set point
Maximum set point
Offset humidiy sensor

1..15 %RH
0..100 %RH
0..100 %RH
-15..+15 %RH

3
0

100

0

10

Startup delay after power failure

0..99 Minutes

0

15

16
17
18

19
20

Function hygrostat

Switch on delay relay   

1)

Switch off delay relay  

1)

Parameter 16/17 in sec. or min.

Minimum on-time relay
Minimum off-time relay

0 = Dehumidify
1 = Humidify
0..99
0..99
0 = Seconds
1 = Minutes
0..99 Minutes
0..99 Minutes

0

0
0
0

0
0

90
95
96
97
98
99

Network number
Software version
Production year
Production week
Serial number (x1000)
Serial number (units)

1..250
0..255
00..99
1..52
0..255
0..999

1

-
-
-
-
-

1) If delay is active, the led will flash

*

Address.