* Adjustment sensor.
The sensor can be adjusted by using the Sensor Offset (parameter 04). Indicates the
ALFA(NET) 19
e.g. 2% too much, the Sensor Offset has to de decreased with 2%.
* Error messages.
In the display of the
ALFA(NET) 19
the following error messages can appear:
EE
- Settings are lost. Solution:
- Reprogram the settings.
* Technical details.
Model
: ALFA(NET) 19 Humidify/dehumidify Hygrostat
Range
: 0/+100%RH, readout per 1%RH
Supply
: 230 Vac 50/60Hz
Relay
: SPDT 250V/16A(C-NO), 8A(C-NC) (cos phi=1)
Control
: by push buttons on the front.
Communication
: RS485-Network (2x twisted pair shielded, min. 0,75mm
2
)
Front
: Polycarbonate
Sensor
: 0-1Vdc (0-100%RH) from RH95-2, LC95-2 or RH970
Be aware!
Humidity sensors should be external supplied with 12Vdc
Sizes
: 90 x 53 x 58mm (hwd)
Panel hole
: 46 x 53mm (hw)
- Provided with memory protection during power failure.
- Connection with screw terminals on the back side.
- Special version on request available.