Duct fitted
by the installer
Fresh air
Pressure drop
BEP
Pressure drop (Pa)
Air flow rate (m
3
/h)
resistance
Identification
For
heat recovery unit
ENY–P4
ENY–P3
ENY–P2
ENY–P1
BEP 40/9/T
BEP 35/6/T
BEP 25/3/M
BEP 25/2/M
Minimum air flow rate
Circular Flange Diameter
D
Amperes absorbed by the resistance
Power supply voltage
Rated power
m
3
/h
mm
A
V/Hz/Ph
kW
690
600
300
270
400
355
250
250
13,0
8,7
13,0
9,1
9,0
6,0
400V 50Hz 3Ph + Pe
3,0
230V 50Hz 1Ph + Pe
2,1
Code
ELECTRIC ANTIFREEZE COIL
BEP
(to be placed on the "External air"
intake duct)
Electric heating coil consisting of armored
elements inserted inside a galvanised she-
et metal duct section with circular flanges
and rubber gasket. The electric coil can
be used in premises with air temperature
between
-20° C and +40° C and is equipped
with double safety thermostat: one with au-
tomatic reset and one with manual reset.
The purpose of the pre-heating resistan-
ce is to prevent the heat exchanger from
freezing and is controlled from the control
board with PWM modulating logic in order
to maintain the exaust air temperature over
the freezing value. Protection class IP 43.
9022113
9022213
9022313
9022413
AIR