Varmeteknikk AS
Phone +47 23 37 55 00 August 2020 V2
23
Power factors for regulator
Boiler type
Transformer
(5A)
Power
factor
Boiler type
Transformer
(5A)
Power
factor
MB 2035
100
8
MB 4035
100
14
MB 2045
200
16
MB 4045
100
14
MB 2060
200
16
MB 4060
100
14
MB 2075
200
16
MB 4075
200
28
MB 2090
300
24
MB 4090
200
28
MB 2105
300
24
MB 4105
200
28
MB 2120
400
32
MB 4120
200
28
MB 2140
400
32
MB 4140
200
28
MB 2150
400
32
MB 4150
300
42
Sensor resistance
Boiler sensor NTC22k
o
C
0
10
20
30
40
50
60
70
80
90
100
110
k
ꭥ
66,3
41,8
27,1
18
12,2
8,5
6
4,2
3,13
2,32
1,75
1,33
Outdoor sensor
o
C
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
ꭥ
1880
1443
1115
870
680
540
430
340
276
225
180
151
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz