Operation and maintenance

After installation, check with the installation engineer that the 
system is in perfect condition. Ask the installer to demonstrate the 
control and functions so that you know how the system should work 
and be maintained.

1.  Check that the heating system has been filled with water and 

vented.

2. Turn the main switch to position 1.

3. Set the desired temperature on the thermostat.
4.  The immersion heater now heats until the temperature matches 

the set temperature.

Check regularly that there is water in the system. 
After venting, the pressure must be checked and water may need to 
be added.
To maintain the safety function, the heating system's safety valves 
must be operated regularly.
The immersion heater must be switched off before the system is 
drained of water.

When it is extremely cold, no part of the heating system must be 

switched off. Call an installer if any part is suspected of freezing.

Operation

The temperature is controlled by a thermostat with approx. 10°C 

connection difference.

Overheating protection

The overheating protection is triggered when the temperature 

exceeds approx. 100°C. It can be reset at the front of the automatic 
control cabinet once the temperature has dropped to approx. 80°C. 

There must be fairly high pressure in order to reset the protection.

Fault

Possible cause of fault

Action

Operation indication 

light is out. No heat.

Main switch off.

Turn the main switch to position 1.

The immersion heater has no 
power.

Check the fuses.

The overheating protection 
has been triggered.

If the overheating protection has been triggered, the operation of the system's 
circulation pumps and valves must be checked. It can be reset by pressing 

the button to the overheating protection when the temperature is lower than 
80oC.

Group fuses for im-

mersion heater trig-

gered.

Immersion heater faulty.

Turn off the main switch. Check the insulation of the immersion heater. If any 

of the electric elements is faulty, replace the immersion heater.

Troubleshooting

Värmebaronen AB

Arkelstorpsvägen 88

291 94 Kristianstad

+46 44 22 63 20

www.varmebaronen.se

www.varmebaronen.com

[email protected]

Work on the system which requires tools, must only be carried out by authorised installers.

 

Ensure the boiler de-energised before  starting work!