Pumped Manifold (PVST)  [1/3]

Fixed value control station for surface heating

with existing main pump

HEATING. COOLING. COMFORT.

e980313

Consumers 

with

presettable
flow rate

Temperature limiter

Factory setting 60 °C

Immersion sleeve with 

flow temperature sensor

with heat transfer paste

(Safety data sheet: www.variotherm.at)

Fixed value regulator

with remote sensor

Heat generator

e.g. gas, oil, solid 

fuel boiler, remote 

heating and buffer

Room

thermostat

PIANO H

Regulating valve

Setting the fixed value regulator

1

2

3

4

5

6

7

20 °C

28 °C

37 °C

45 °C

53 °C

62 °C

70 °C

•   The boiler flow temperature   must be at least 10 K higher than the set 

flow temperature of the surface heating   .

•   The temperature can be continuously adjusted between 20 and 70 °C.
   The scale of 1-7 on the handwheel gives the following target 

temperatures (guideline):

Boiler circuit

Surface heating circuit

2-14 heating circuits

230V AC, 50 Hz,

provided connection cable: 3 x 0,5 mm² (max. 3 A),

please note the electrical protection!

Boiler flow:

 3/4" female thread

Boiler return:

 3/4" female thread

Surface heating flow:

 3/4" Eurocone

Surface heating return:

 3/4" Eurocone

Check valve
Main pump
Caution!

  Observe the required capacity (pipe diameter).

 

 

Primary pressure required!

 The flow rate in the boiler circuit is adjusted using the regulating 

valve when the fixed-value regulator is fully opened (

)

Flushing ball valve

close when flushing

h = 385 mm / 405 mm with servomotor

Installation depth PVST:

125 mm