8315 L&J Tankway Software Description
TankGate Interface
44
Installation and Operations Manual
4.11.2 Application
The GS2000 point provides an interface to GSI Model 2000 Tank Gauge Transmitters.
Tank gauges are connected directly to a TankGate. At startup, a WVSCAN point is
automatically created to manage the scanning task. The ID must match the unit address
of the GSI Model 2000.
The SpeedMode must match the configuration of the transmitter. The DataMode must
match the engineering units of the gauge. Conversion from Metric to English (or vice-
versa) can be performed be setting the LevelConvert and the TempConvert parameters
in the WVSCAN point associated with the GS2000 point.
The Level can be offset by entering a value for the LevelOffset parameter. The
LevelOffset is added to the Level after any conversion have be performed. Likewise, the
TempOffset may be used to offset the Temp value.
The FastScanMode parameter places the point in the Fast Scan list. Fast Scan points are
scanned more frequently than other points. The Interleave, FastScanMax, and
FastScanTime parameters of the WVSCAN point determine how fast scanning is
performed
Raw2
Raw data from gauge. Value reported as hexidecimal value.
Dynamic Parameters
Function
Summary of Contents for TankGate Interface 8315 Series
Page 2: ......
Page 14: ...Overview TankGate Interface 4 Installation and Operations Manual...
Page 30: ...8315 L J Tankway Interface Module TankGate Interface 20 Installation and Operations Manual...
Page 74: ...8315 L J Tankway Software Description TankGate Interface 64 Installation and Operations Manual...
Page 80: ...Installation TankGate Interface 70 Installation and Operations Manual...
Page 112: ...Troubleshooting TankGate Interface 102 Installation and Operations Manual...
Page 119: ...i 8300 NOTES...