Maintenance and Troubleshooting
Tank Gauge Transmitter
30
Installation and Operations Manual
4.6
Model 1200 Error Messages
The following error messages can be encountered while using the Model 1200.
4.7
Host Communication Loopback Tests
Communications between a host computer and several field devices, such as the ATT,
usually occurs on a single set of wires. Each device is individually addressable by the
host computer.
The ATT contains special circuitry that reduces the chance of one ATT shorting the host
communication lines. The circuitry allows the ATT to disconnect itself from the
communication line and perform a loop-back test.
The test is performed automatically on power-up. It is also performed periodically if
communication is no longer detected from the host computer.
If the ATT fails its local loop-back test, it will generate a 'Bad Comm Board' status and
disconnect itself from the host communication lines. It will remain disconnected until it
can pass its internal loop-back test.
Error Message
Description
INVALID ANSWER
The operator was expected to enter either a 'Y' for yes
or an 'N' for no and something different was entered.
INVALID FLOAT
The operator entered an invalid floating point number. The
proper format for floating point entry is
[spaces][sign]number['.'][number]['E'][sign][number]
where the fields surrounded by brackets([]) are optional.
Leading spaces are permitted, however spaces within the
number are not allowed. A maximum number of 15 characters
is allowed. The exponent (value after 'E') cannot be larger than
30 nor less than -30.
INVALID INPUT
The operator was given a choice of two different
characters to enter and something else was entered.
INVALID NUMBER
The operator entered an invalid number.
NEGATIVE NUMBER
The operator entered a negative number when asked for
a positive float number.
NOT ALTERABLE
The operator attempted to alter a Command,
Informational, or Menu Item using the F3 (alter) key.
NOT IN ALTER MODE
The operator attempted to alter a Configuration Item
using the F3 (alter) key while in the Display Mode.
TOO MANY CHARACTERS
The operator attempted to enter more than the allowed
number of characters.
NUMBER TOO LARGE
The operator entered a number that is beyond the limits
of a particular Configuration Item.
Summary of Contents for Network Adapter 4000
Page 2: ......
Page 6: ...Advanced Technology Transmitter iv Installation and Operations Manual...
Page 46: ...Specifications Tank Gauge Transmitter 36 Installation and Operations Manual...
Page 48: ...Ordering Information Tank Gauge Transmitter 38 Installation and Operations Manual...
Page 54: ...Theory of Operation Tank Gauge Transmitter 44 Installation and Operations Manual...
Page 72: ...Modbus Implementation Tank Gauge Transmitter 62 Installation and Operations Manual...
Page 78: ...Tank Gauge Transmitter 68 Installation and Operations Manual...
Page 79: ...69 4000 NOTES...