1. Switch on the warm airflow and check that temperature 

is correct and stable. 

2. From a distance of several inches, direct the airflow at 

the  guard  protecting  the  thermistor.  The  detector 
should alarm within 30 seconds. 

3. Upon  alarm  immediately  remove  the  heat  source  and     

check  that  the  red  LED  of  the  detector  is  illuminated. 
Reset the detector from the control panel. 

4.If  detector  fails  to  go  into  alarm  mode  within  30 

seconds  it  is  too  insensitive  and  needs  to  be  returned 
to the distributor for servicing. 

5. After  testing,  check  that  the  system  is  set  for  normal 

operation and notify the appropriate authorities that the 
testing operation is complete and the system is active 
again. 

NOT SUITABLE FOR INSTALLATION IN AREAS 
WHERE AIR VELOCITIES EXCEED 300 ft/min 

MAINTENANCE 

The  recommended  minimum  requirement  for  detector 
maintenance consists of an annual cleaning of dust from 
the  detector  head  by  using  a  vacuum  cleaner  cleaning 
program  should  be  agreed  to  the  individual  environment 
in conformance with NFPA-72A standard. 
 

CAUTION:  DO  NOT  ATTEMPT  TO  DISASSEMBLY  OF 
THE  FACTORY  SEALED  SMOKE  DETECTOR.  THIS 
ASSEMBLY  IS  SEALED  FOR  YOUR  PROTECTION  AND 
IS NOT INTENDED TO BE OPENED FOR SERVICING BY 
USERS.  OPENING  THE  DETECTOR  HEAD  WILL  VOID 
THE WARRANTY. 
 
REFERENCE TO THE TECHNICAL BULLETIN ISSUE NO. 
FDRTB20041225,REV.C 

 

SPECIFICATION 

Model 

2/4   

wire 

Ther

mal 

Voltage 

DC 

Standby 

Current 

(Max.) 

Alarm 

Current 

(Max.) 

Surge 

Current 

(Max.) 

Star-Up 

Time 

(Max.) 

Permissible 

Current 

(Max.) 

Frequency 

Alarm   

Sound level 

Alarm contact 

Base model 

FDR-16-HR 

57

°

12V 

320

μ

55mA 

 

60 Seconds 

80mA 

3-5 Seconds 

Form A/Auto Reset   

P/N774912 

FDR-26-S 

 

12V 

320

μ

35mA 

 

60 Seconds 

80mA 

3-5 Seconds 

Form A/Auto Reset   

P/N774912 

FDR-36-SHR 

57

°

12V 

320

μ

35mA 

 

60 Seconds 

80mA 

3-5 Seconds 

Form A/Auto Reset 

P/N774912 

 

Remarks: S

-smoke/ 

H

-heat/ 

R

-rise of heat 

 

LIMITED WARRANTY STATEMENT 

VAR-TEC  represents  that  this  product  is  free  from  defects  in  material  and  workmanship.  And  it  will  repair  or  replace  any 
product or part thereof which proves to be defective in workmanship or  material for a period of twelve (12) months from the 
date  of  purchase  but  not  to  exceed  eighteen  (18)  months  after  shipment  by  the  manufacturer.  For  a  full  description  of 
VAR-TEC

S  LIMITED  WARRANTY,  which,  among  other  things,  limits  the  duration  of  warranties  of  merchantability  and 

fitness  for  a  particular  purpose  and  excludes  liability  for  consequential  damages.  Please  read  the  entire  LIMITED 
WARRANTY  on  the  VAR-TEC  quotation.  Acceptance  of  order  and/or  original  invoice  which  will  become  part  of  your  sales 
agreement. Please contact VAR-TEC directly for a return merchandise authorization (RMA) number before returning goods 
to the company. Shipment must be prepaid and VAR-TEC will repair or replace your returned detector. 

 

 

 

                                                                                                                                                             

FDR-00008 

 

 

07-04-20

LUCOM GmbH    —   Flößaustr. 22a   —   90763 Fürth   —   Tel.:  +49 911/ 957 606 00   —   E-Mail: [email protected]   —   www.lucom.de

www

.lucom.de

Reviews: