5
1.1.1
LFExx weights
The unit dry weight is the delivered unit with no
water in unit, the wet weight is the operational
weight when the unit is running.
1.2
Vent duct connections
1.2.1
General
The unit is designed to be mounted within a
ceiling void with either
The unit is designed to be mounted within a
ceiling void with either:
1 - a ducted inlet and discharge air for example
to ceiling grilles or,
2 - a Void inlet and ducted discharge for extract
ceilings void or,
3 - a Ducted inlet and void discharge for supply
air ceiling voids.
The duct connections onto the unit are designed
for 200 mm internal diameter flexible ducts. The
inlet and discharge for the unit can be on the
end, left side, or right side for both inlet and
discharge.
1.2.2
Ventilation duct connections
The unit is provided with two spigots one for
inlet the other for the discharge only one spigot
connection is required each end the other two
should be blanked off each end of unit, with
the four blanking plates provided with unit. The
spigot should be placed in one of three
positions as shown below the other two outlets
should be blanked off.
Duct work connections view from under side of
unit.
Discharge end
Inlet end
Note only one spigot is required each end the
other two ports must be blanked off with
blanking plates provided.
The spigot dimensions are
The unit can have free air return inlet or free
air discharge into void area if required in this
case the spigot need not be connected. If free
air return from void area is required a filter
screen can be provide part number FVKIT 179
Then the inlet port must have the Velcro strip
tapped around the hole as shown and the filter
fixed onto the Velcro so air is filtered before
entering the unit, note the other two inlets must
be blanked off.
1.2.3
Ventilation duty.
The unit design airflow is:
FAN SPEED
External pressure Air Volume
Pa
m
3
/s
Lo speed
0.
0.1
Lo speed
36
0.09
Hi speed
0
0.16
Hi speed
50
0.12
Note: maximum external resistance at hi speed
is 50 Pa which equals 36Pa external at Lo
speed.
Vapanet model
Dry Kg
Wet Kg
LFE05
34
38
Velcro tap
stuck around
inlet opening
Summary of Contents for VapaNet LFE Series