Minivap
Positioning the Minivap unit
DO's
DO
mount the unit indoors.
DO
mount the unit close to the steam nozzle
position.
DO
ensure adequate service access to the front of
the unit -min. 70Omm (2'3").
DO
remove the cylinder to gain access to the
mounting holes in the back of the steam section.
DO
use M6 projecting type wall bolts or equivalent
to mount the unit in position.
DON'Ts
DON'T
install the unit close to sources of strong
electromagnetic emissions e.g. variable speed lift
motor drives, KVA transformers, etc.
DON'T
mount unit in an unventilated enclosure.
DON'T
mount in a position requiring ladder access
to the unit.
DON'T
install the unit behind a false ceiling or other
situation where an unusual malfunction (e.g. water
leak) would cause damage.
DON'T
install the unit in an area which will be
hosed down.
DON'T
install the unit where the ambient air
temperature can exceed 35°C (95°F).
DON'T
mount the unit inside a cold-room or other
place where temperature and humidity conditions
can cause condensation on electrical components.
DON'T
mount the unit where the sound of a
contactor opening/closing and water flow in a pipe
would be unacceptable e.g. libraries, private
apartments, etc.
DON’T
place any object in front of an RDU (if used)
where humidity conditions can cause condensation.
DON’T
mount on a duct or plenum.