CONNECTING TO GAS
SUPPLY

 WARNING: A qualified service

person must connect heater to gas
supply. Follow all local codes.

The installer must supply an external regu-
lator. The external regulator will reduce
incoming gas pressure. You must reduce
incoming gas pressure to between 11 and 14
inches of water. If you do not reduce incom-
ing gas pressure, heater regulator damage
could occur. Install external regulator with
the vent pointing down as shown in Figure
12. Pointing the vent down protects it from
freezing rain or sleet.

 CAUTION: Never connect heater

directly to the propane/LP supply.
This heater requires an external
regulator (not supplied). Install the
external regulator between the
heater and propane/LP supply.

Figure 12 - External Regulator With Vent
Pointing Down

 CAUTION: Use only new,

black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe 3/8"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.

Propane/LP
Supply Tank

Vent
Pointing
Down

External
Regulator

INSTALLATION

Continued

Figure 13 - Gas Connection

*  A CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional CSA/AGA design-certified
equipment shutoff valve from your dealer. See Accessory, page 18.

Install sediment trap in supply line as shown
in Figure 13. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.

IMPORTANT:

  Hold pressure regulator

with wrench when connecting it to gas pip-
ing and/or fittings.

Installation must include a equipment shutoff
valve, ground joint union, and plugged 1/8"
NPT tap. Locate NPT tap within reach for
test gauge hook up. NPT tap must be up-
stream from heater (see Figure 13). An
appliance main gas valve (equipment shutoff
valve) shall be provided in an accessible
location for turning on or shutting off the
gas to the appliance.

IMPORTANT:

 Install an equipment shutoff

valve in an accessible location. The equip-
ment shutoff valve is for turning on or
shutting off the gas to the appliance.

 CAUTION: Use pipe joint seal-

ant that is resistant to liquid pe-
troleum (LP) gas.

Tee Joint

Reducer
Bushing to
1/8" NPT

1/8" NPT
Plug Tap

Test
Gauge
Connection *

Tee
Joint

Pipe
Nipple

Cap

Pressure
Regulator

3/8" NPT
Pipe Nipple

Heater
Cabinet

Ground Joint
Union

From External
Regulator
(11" W.C. to 14" W.C.
Pressure)

Equipment
Shutoff
Valve *

3" Minimum

Sediment
Trap

Continued

 WARNING: This appliance re-

quires a 3/8" NPT (National Pipe
Thread) inlet connection to the
pressure regulator.

Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.

Summary of Contents for VP10A

Page 1: ...y a qualified installer service agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxy gen from the room in which it is installed Provisionsforadequate combustion and...

Page 2: ...etween locked positions Poor combustion may result 6 This heater needs fresh outside air ven tilation to run properly This heater has an oxygen depletion sensor ODS pi lot light safety system The ODS...

Page 3: ...with care Follow all localcodes Intheabsenceoflocalcodes use the latest edition of National Fuel Gas Code ANS Z223 1 also known as NFPA 54 Available from American National Standards Institute Inc 143...

Page 4: ...s to breathe Fresh air must enter your home All fuel burning appliances need fresh air for proper com bustion and ventilation Exhaustfans fireplaces clothesdryers and fuel burning appliances draw air...

Page 5: ...ter __________________Btu Hr Gas water heater __________________Btu Hr Gas furnace __________________Btu Hr Vented gas heater __________________Btu Hr Gas fireplace logs __________________Btu Hr Other...

Page 6: ...cts WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appliances in both spaces Figure 2 Ventilation Air from In...

Page 7: ...re 4 Ifyoucan providegreaterclear ancesfromfloor ceiling andjoin ing wall WARNING Never install the heater in a bathroom VP10A only in a recreational vehicle where curtains furniture clothing or other...

Page 8: ...ued Figure 8 Tightening Anchors Thin or Thick Wall thick wall shown Solid Wall 1 16 Space Placing Heater On Mounting Screws 1 Locate two keyhole slots on back panel of heater see Figure 9 2 Place larg...

Page 9: ...menttrapinsupplylineasshown in Figure 13 Locate sediment trap where it is within reach for cleaning Locate sedi ment trap where trapped matter is not likely to freeze A sediment trap traps moisture an...

Page 10: ...ust be lighted by hand When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is he...

Page 11: ...0 seconds after lighting pilot After 10 seconds release control knob Note If pilot goes out repeat steps 3 through 7 OFF PILOT IGNITOR LOW HIGH TO SELECT HEATING LEVEL 1 Slightly press in control knob...

Page 12: ...ean Inspect these areas of heater before each use Have heaterinspectedyearlybyaquali fied service person Heater may need more frequent cleaning due to excessive lint from carpeting bedding material pe...

Page 13: ...itor cable if pinched by any metal or tubing Keep ignitor cable dry 5 Tighten nut holding piezo ignitor to heater cabinet Nut is located inside heater cabinet at top 6 Replace ignitor cable 7 Replace...

Page 14: ...Contact local propane LP gas company 3 Replace burner 4 Replace gas regulator 1 Replace burner 2 Contact local propane LP gas company 3 Turn control knob until it locks at de sired setting 1 Problem w...

Page 15: ...ing Gas Connections page 10 2 Replace control valve 1 Take apart gas tubing and remove for eign matter 2 Locate and correct all leaks see Check ing Gas Connections page 10 1 Refer to Air for Combustio...

Page 16: ...ex 8 x 1 4 9 7 099059 03 ODS Pilot Assembly 1 7 1 098514 01 Thermocouple 1 7 2 098594 01 Ignitor Electrode 1 8 099884 01 Burner Assembly 1 9 099056 01 Injector 1 10 099390 01 Tubing Valve to burner 1...

Page 17: ...ulator to valve 1 PARTS LIST This list contains replaceable parts used in your heater When ordering parts follow the instructions listed under Replacement Parts on page 18 of this manual ODS PILOT ILL...

Page 18: ...TechnicalServiceDe partment at 1 800 323 5190 for referral in formation When contacting your dealer or DESA In ternational have ready your name your address model and serial numbers of your heater how...

Page 19: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Page 20: ...y does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects...

Reviews: