Vanguard VP10A Owner'S Operation And Installation Manual Download Page 6

PROPANE/LP GAS HEATERS

6

®

 VP5D AND VP10A

104273

AIR FOR
COMBUSTION AND
VENTILATION

Continued

Or 

Remove 

Door into 
Adjoining 

Room, 

Option 3

Ventilation Grills 

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into Adjoining

Room, 

Option 1

VENTILATION AIR

Ventilation Air From Inside
Building

This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must pro-
vide two permanent openings: one within
12" of the ceiling and one within 12" of the
floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2). You can also
remove door into adjoining room (see op-
tion 3, Figure 2). Follow the National Fuel
Gas Code NFPA 54/ANS Z223.1, Section
5.3, Air for Combustion and Ventilation
 for
required size of ventilation grills or ducts.

 WARNING: Rework work-

sheet, adding the space of the
adjoining unconfined space. The
combined spaces must have
enough fresh air to supply all
appliances in both spaces.

Figure 2 - Ventilation Air from Inside Building

Figure 3 - Ventilation Air from Outdoors

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation
grills or ducts. You must provide two per-
manent openings: one within 12" of the
ceiling and one within 12" of the floor.
Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces
include attics and crawl spaces. Follow the
National Fuel Gas Code NFPA 54/ANS
Z223.1, Section 5.3, Air for Combustion and
Ventilation
 for required size of ventilation
grills or ducts.

IMPORTANT: 

Do not provide openings for

inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.

Outlet
Air

Ventilated
Attic 

Outlet
Air

Inlet
Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Summary of Contents for VP10A

Page 1: ...y a qualified installer service agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxy gen from the room in which it is installed Provisionsforadequate combustion and...

Page 2: ...etween locked positions Poor combustion may result 6 This heater needs fresh outside air ven tilation to run properly This heater has an oxygen depletion sensor ODS pi lot light safety system The ODS...

Page 3: ...with care Follow all localcodes Intheabsenceoflocalcodes use the latest edition of National Fuel Gas Code ANS Z223 1 also known as NFPA 54 Available from American National Standards Institute Inc 143...

Page 4: ...s to breathe Fresh air must enter your home All fuel burning appliances need fresh air for proper com bustion and ventilation Exhaustfans fireplaces clothesdryers and fuel burning appliances draw air...

Page 5: ...ter __________________Btu Hr Gas water heater __________________Btu Hr Gas furnace __________________Btu Hr Vented gas heater __________________Btu Hr Gas fireplace logs __________________Btu Hr Other...

Page 6: ...cts WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appliances in both spaces Figure 2 Ventilation Air from In...

Page 7: ...re 4 Ifyoucan providegreaterclear ancesfromfloor ceiling andjoin ing wall WARNING Never install the heater in a bathroom VP10A only in a recreational vehicle where curtains furniture clothing or other...

Page 8: ...ued Figure 8 Tightening Anchors Thin or Thick Wall thick wall shown Solid Wall 1 16 Space Placing Heater On Mounting Screws 1 Locate two keyhole slots on back panel of heater see Figure 9 2 Place larg...

Page 9: ...menttrapinsupplylineasshown in Figure 13 Locate sediment trap where it is within reach for cleaning Locate sedi ment trap where trapped matter is not likely to freeze A sediment trap traps moisture an...

Page 10: ...ust be lighted by hand When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is he...

Page 11: ...0 seconds after lighting pilot After 10 seconds release control knob Note If pilot goes out repeat steps 3 through 7 OFF PILOT IGNITOR LOW HIGH TO SELECT HEATING LEVEL 1 Slightly press in control knob...

Page 12: ...ean Inspect these areas of heater before each use Have heaterinspectedyearlybyaquali fied service person Heater may need more frequent cleaning due to excessive lint from carpeting bedding material pe...

Page 13: ...itor cable if pinched by any metal or tubing Keep ignitor cable dry 5 Tighten nut holding piezo ignitor to heater cabinet Nut is located inside heater cabinet at top 6 Replace ignitor cable 7 Replace...

Page 14: ...Contact local propane LP gas company 3 Replace burner 4 Replace gas regulator 1 Replace burner 2 Contact local propane LP gas company 3 Turn control knob until it locks at de sired setting 1 Problem w...

Page 15: ...ing Gas Connections page 10 2 Replace control valve 1 Take apart gas tubing and remove for eign matter 2 Locate and correct all leaks see Check ing Gas Connections page 10 1 Refer to Air for Combustio...

Page 16: ...ex 8 x 1 4 9 7 099059 03 ODS Pilot Assembly 1 7 1 098514 01 Thermocouple 1 7 2 098594 01 Ignitor Electrode 1 8 099884 01 Burner Assembly 1 9 099056 01 Injector 1 10 099390 01 Tubing Valve to burner 1...

Page 17: ...ulator to valve 1 PARTS LIST This list contains replaceable parts used in your heater When ordering parts follow the instructions listed under Replacement Parts on page 18 of this manual ODS PILOT ILL...

Page 18: ...TechnicalServiceDe partment at 1 800 323 5190 for referral in formation When contacting your dealer or DESA In ternational have ready your name your address model and serial numbers of your heater how...

Page 19: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Page 20: ...y does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects...

Reviews: