background image

O&M-V5-FAP-AVF-LCD R0 
 

 

Operator’s Manual (Fire Alarm Panel c/w AVF & LCD) 

Pg 7 of 21

2.2.2 Resetting the System 

 

Before the system is reset, the cause of the alarm must be investigated and duly 
rectified.  In the case of a false alarm, make sure that there is no incident of fire before 
resetting the system. 

 

Note

 : It is not possible to reset the system before the alarm is silenced. 

 

a)  Re-instate the affected devices to normal 
b)  Press  

“System Reset”

 Switch 

(Green) (3)

  

c)  Upon resetting, the system should resume to normal operating condition, if there are 

no other events to cause another alarm and the original cause of the alarm being 
rectified. 

 

2.3 Fault Conditions 

 

A self diagnostic circuit are provided to check itself and indicates a wide range of 
possible faults. 
   
Under Fault Conditions: 
a)  The respective zone fault Amber LED lighted and/or 
b)  The respective system fault Amber LED lighted 
c)  General, amber 

“FAULT”

 LED lighted 

d)  Panel fault buzzer sound 
e)  LCD display shown as (Common Fault – non-latching) 

 
 
 
 
 
 

(07/04/06: 7

th

 April 2006, M000: “Main” panel address “000”, 10:06: 10:06AM) 

 

2.3.1 Silencing the Fault Buzzer 

If the fault cannot be rectified, it may be silenced by: 
a) Press 

“BUZZER SILENCE”

 Switch 

(Black) (1) 

b) Buzzer Silence Amber LED lighted 
c) Panel remains in fault state until fault rectified 

 

2.3.2 Resetting the System 

The cause of the fault should be investigated and rectified.  If it is due to a mains supply 
failure, the system will normalise when the mains supply resumes.  Some faults are 
internal to the system and are not covered in this manual. Once the fault(s) are rectified, 
the panel shall be normalised. 

FAULT

07/04/06         M000         10:06

Summary of Contents for V5

Page 1: ...V5 Operator s Manual Fire Alarm Panel AVF LCD...

Page 2: ...ult Condition 7 2 3 1 Silencing the Fault Buzzer 7 2 3 2 Resetting the System 7 2 4 Initiating Evacuate Alarm 8 2 4 1 Silencing Evacuate Alarm 8 2 5 Zone Auxiliary Disable 8 2 6 Indicators Test 8 2 7...

Page 3: ...l s are usually sited in the building fire command centre or any prominent location clearly visible from the main entrance Input devices are used to cause a change in panel status These devices may be...

Page 4: ...e Switch Blue To disable zone fire fault detection circuit Note Zone disable function only prior to an alarm activation 1 2 2 System Control Module Indicators a Power On Green System energised by Main...

Page 5: ...230V AC Mains supply failure m Charger fault Amber Charger Fuse blown charger voltage low high n Battery Fault Amber Battery supply disconnected battery fuse blown battery voltage low high o Alarm Co...

Page 6: ...access other level of function or password key as 1 c Up 2 White To move cursor up page up or password key as 2 d Down 3 Blue To move cursor down page down or password key as 3 e Enter Red To select...

Page 7: ...02 Main panel address 000 Zone 002 Fire at 14 49 2 49PM i For multiple fire events it shall be displayed by manual action Up Down key 2 2 1 Silencing the Alarm Bells Sounders It is a requirement under...

Page 8: ...and indicates a wide range of possible faults Under Fault Conditions a The respective zone fault Amber LED lighted and or b The respective system fault Amber LED lighted c General amber FAULT LED ligh...

Page 9: ...s To carry out zone auxiliary disablement a Press Disable for zone respectively or Auxiliary Disable Switch Blue 5 b Disabled amber LED lighted c General Disabled amber LED lighted d Zone s auxiliary...

Page 10: ...date and time LLM is integrated with non volatile memory EEPROM to store and record the activated alarm zone event up to 999 it will not be lost even the system total power failure The recorded zone a...

Page 11: ...E ARCHIVE To print the recorded alarm zone event a Connect the Printer b Press Menu c Select PRINT FIRE ARCHIVE by Up Down key and press Enter Print start from 017 TC017 17th event of Total Event Coun...

Page 12: ...et the Date select the Date by Up Down key and press Enter to save Day Month Year 4 DELETE To delete the recorded event key in the password and press press Enter Delete all recorded event Password and...

Page 13: ...t person shall also be responsible for keeping all the log records for all alarms activation genuine practice test or false faults service tests and routine preventive maintenance repair and alteratio...

Page 14: ...m the system reset b Check the battery condition and the voltage reading by the use of a multi meter c On completion of the above tests ensure that all switches are in the correct operating position d...

Page 15: ...panel is in a clean and operative condition i Visually inspect the condition of the components terminations and cables j Ensure that all faulty parts are satisfactorily replaced and recorded Enter in...

Page 16: ...tors are found to be coated with paint or any material likely to affect the operation of the detectors such material should be cleaned off or if necessary have the detector replaced Note In certain en...

Page 17: ...hort back of ZDM Zone line Line short circuit Zone line Line open circuit Zone Detector Missing Removed Zone Termination Loose Sub Alarm Panel Fault at Sub Panel Zone Fault If not May be Line Open EOL...

Page 18: ...iliary Fault Alm 2 O S FBM Alarm 2 output is used for Auxiliary Option as provided Refer to Sounder Fault for fault finding AC 230V Mains Failure AC Fuse Blown AC Switch OFF position Mains Failure Cha...

Page 19: ...ed Fault Line Trouble Alarm Monitoring Station 2 Red Short DIM Alarm Monitoring Transmitter Panel Faulty 1 Press Buzzer Silence Black 1 2 Check the possible causes and rectified 3 When fault is rectif...

Page 20: ...O M V5 FAP AVF LCD R0 Operator s Manual Fire Alarm Panel c w AVF LCD Pg 19 of 21 V5 Technical Specification and Installation Diagram...

Page 21: ...Max DC 24V 5Amp Wire 2 5mm2 Option for Voltage Contact selection provided 6 To MAP Output Wire 1 5mm2 For SAP Common Fire Fault signal to Main Alarm Panel MAP Zone 7 FIRE Output C NC NO Contact Max DC...

Page 22: ...ORS CALLPOINTS POLARISED SOUNDERS BELLS 6K8 OHM As Z1 Connection As ALM 1 Connection Auxiliary Output 1 Auxiliary Output 2 As per Jumper Setting 1 2 FC Free Contact Output Signal to Main Alarm Panel M...

Reviews: