Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
Pg 4 of 21
d) Disabled (Amber)
: General Disabled Indicator, system in disabled
condition
e) System Fault (Amber)
: Indicate Programmable Micro Controller failure
f) Fire Sent (Red)
: Fire Signal to Alarm Remote Monitoring Station
activated (Optional)
g) Fire Line Trouble (Amber)
: Fire Signal Line open/short (Optional)
(
Note:
It shall not be suppressed during the Fire Alarm condition)
h) Fault line Trouble (Amber)
: Fault Signal Line open/short (Optional)
i) Sounder Fault (Amber) : Alarm sounder line open/short
(
Note :
It shall not be suppressed during Fire Alarm condition)
j) Earth Fault (Amber)
: Field input/output wires shorted to ground
k) Auxiliary Fault (Amber)
: Auxiliary supply / auxiliary supervised line open/short
l) Mains Failure (Amber)
: 230V AC Mains supply failure
m) Charger fault (Amber)
: Charger Fuse blown / charger voltage (low / high)
n) Battery Fault (Amber)
: Battery supply disconnected / battery fuse blown /
battery voltage (low / high)
o) Alarm Counter (3x7Seg.)
: Indicate that number of alarm (false) been activated
(for FALSE Alarm Management)
p) AVF Off (Amber)
: Indicate that AVF function been set off
q) Retard State (Amber)
: Indicate that system in Retard State
r) Confirmation State (Amber)
: Indicate that system in Confirmation State
Control Switches
a) Buzzer Silence (Black) (1)
: To silence fault buzzer (Audio & Visual)
b) Sounder Silence (Amber) (2)
: To silence alarm sounder (Audio & Visual)
c) System Reset (Brown) (3)
: To normalise the system
(
Note:
Silence alarm sounder before RESET)
d) Indicators Test (White) (4)
: To test the working condition of all LED
indicators and buzzer
e) Auxiliary Disable (Blue) (5)
: To disable auxiliary output control function
(Audio & Visual)
f) Sound Alarm (Red) (6)
: To raise alarm sounder manually for
emergency evacuation (Audio & Visual)