Vanguard PENINSULA VPN36 Installation And Operating Instructions Manual Download Page 6

6

55505

Figure 10

If a hearth extension is to be field constructed, it must be made of
noncombustible, inorganic material having an effective thermal
conductivity "K" of .84 BTU In/Ft 2 Hr. F or less at 1" thickness.

Thermal conductivity "K" of materials can be obtained from the
manufacturer.

The minimum required thickness for any material could be obtained
by the following formula:

K factor x 1" = Thickness required

.84

If the hearth extension is to be raised, a "Z" type metal safety strip
must be used, see Figure 7, page 5 and Figure 11.

OUTSIDE AIR KIT INSTALLATION

The installation of the outside air kit must be installed during the
rough framing of the firebox due to the nature of its location. Outside
combustion air can be accessed through an exterior wall or a vented
crawl space (see Figure 12).

WARNING: AIR INLET DUCTS MUST NOT TERMI-
NATE IN ATTIC SPACE.

Avoid installing outside air eyebrow in areas where inlet opening
may be blocked by snow, bushes or other obstacles. It should also be
located beyond the reach of small children.

The maximum height for the air inlet above platform of firebox is
within 3 feet below the termination flue gas outlet.

For further details on the installation of the outside air kit, please
refer to the instructions included with the kit. For operating instruc-
tions, please refer to your owner’s manual.

GAS LINE INSTALLATION

YOUR GAS SUPPLIER OR A QUALIFIED SERVICE PER-
SON SHOULD DO GAS LINE HOOKUP.

WARNING: BEFORE YOU PROCEED, MAKE SURE
YOUR GAS SUPPLY IS OFF!

A gas line may be installed for the purpose of installing a gas
appliance available through your local distributor. Use only 1/2"
black iron pipe and appropriate fittings. When installing a gas line,
a shut-off valve designed for installation outside the firebox is
recommended.

STEP 1: To install, remove the knockout indentation on the refrac-
tory (or firebrick) wall located approximately 2" above the refractory
hearth floor. The knockout indentation must be firmly tapped with
any solid object until it is released. Remove fragmented portion of
refractory (see Figure 13, page 7).

Figure 11

NONCOMBUSTIBLE

HEARTH EXTENSION

64 MIN.

20

MIN.

16

MIN.

65 MIN.

NONCOMBUSTIBLE

HEARTH EXTENSION

NONCOMBUSTIBLE

HEARTH EXTENSION

8" MAX

"Z" TYPE
EMBER PROTECTOR

EMBER PROTECTOR

FOR RAISED FIREPLACE SEE SECTION
ON FRAMING WITH A RAISED PLATFORM

1

/

2

" TYP

1

/

2

" TYP

"K" FACTOR

.84

SECURE TO
COLLARS WITH
DUCT TAPE OR
SCREWS

VENTED CRAWL
SPACE INSTALLATION

CHECK WITH LOCAL AREA CODES PRIOR TO
INSTALLING IN A VENTED CRAWL SPACE

AIR INLET
EYEBROW

AIR INLET
LOCATION
MUST ALLOW
FOR BUSHES
OR SNOW

Figure 12

Summary of Contents for PENINSULA VPN36

Page 1: ...should be located out of traffic and away from furniture and draperies Do not place clothing or other flammable materials on or near the appliance NEVER leave children unattended when a fire is burni...

Page 2: ...MNEY PIPE INSTALLATION PG 7 9 FINISHING YOUR CHIMNEY SYSTEM PG 9 10 TERMINATIONS PG 11 11 FINISHING YOUR FIREBOX PG 12 12 OPERATING GUIDELINES AND MAINTENANCE INSTRUCTIONS PG 13 13 REPLACEMENT ACCESSO...

Page 3: ...or approved by DESA INTERNATIONAL in this wood burning firebox PROPER INSTALLATION is the most important step in ensur ing a safe and continuous operation of this firebox Although grounding may not b...

Page 4: ...uld not be placed within 9 inches of the effective opening of this firebox The effective opening is considered the opening where actual heat output may occur Combustible material above and projecting...

Page 5: ...opening except on the end where projection is 16 in min to the front and 20 in to the sides see Figure 10 page 6 1 2 MIN OVERLAP 1 2 MIN METAL SAFETY STRIPS SUPPLIED 1 2 MIN TO COMBUSTIBLES 2 MIN CLEA...

Page 6: ...the outside air kit please refer to the instructions included with the kit For operating instruc tions please refer to your owner s manual GAS LINE INSTALLATION YOUR GAS SUPPLIER OR A QUALIFIED SERVI...

Page 7: ...ill install an unvented gas log set ONLY UNVENTED GAS LOGSETSWHICHHAVEBEENFOUNDTOCOMPLYWITHTHE STANDARDFORUNVENTEDROOMHEATERS ANS IAS AGA Z21 11 2 ARE TO BE INSTALLED IN THIS FIREPLACE NOTE An appropr...

Page 8: ...ramed opening into a living space above a firestop must be placed on the ceiling below Figure 16 Figure 16 When the pipe passes through a framed opening into an attic space above a firestop must be pl...

Page 9: ...e 20 and Rise and Offset Chart Figure 20 A B Maximum length of pipe between supports is 6 feet of angled run Amaximumoftwo6footangledrunsectionsperchimneysystem see Figure 21 Figure 21 FINISHING YOUR...

Page 10: ...50 feet measured from bottom of firebox to flue outlet end of pipe CHIMNEY MAINTENANCE Have your chimney system cleaned and inspected regularly to ensure safe and efficient operation Refer to your Own...

Page 11: ...le termina tion only Figure 27 shows an VRTL 10D round top termination Figure 27 CAUTION DO NOT SEAL OPENINGS ON THE ROOF TOP FLASHING FOLLOW THE INSTALLATION IN STRUCTIONS PROVIDED WITH THE TERMINATI...

Page 12: ...earances are adhered to refer to section on clearances and the firebox opening are not blocked or obstructed in any way see Figure 30 TOP SLOT UNDERNEATH FRAME ADJUSTMENT CLIP ADJUSTMENT CLIP SHORT PI...

Page 13: ...ting a fire this provides adequate outside combustionair Closethemechanismwhennotinusetopreventcold air from entering the room Periodically check your outside air intake vent hood for any possible obs...

Page 14: ...ANGLED RUN PIPE SUPPORT ASSEMBLY V12S 10DM OUTSIDE AIR KIT VAK4 900147 VENT HOOD EMBER PROTECTORS 5 VENT PLASTER COLLAR FRONT PANEL ASSEMBLY CABINET DOOR SET LEFT RIGHT VDGPN36 Cabinet Doors 2 sets an...

Reviews: