Vanguard FBPS Owner'S Operation And Installation Manual Download Page 9

www.desatech.com

105163-01C

Figure 5 - Minimum Clearance -  

Front View 

42" Min.

0" to Wood Floor

8" Min.

4"

Min.

0" Min. Clearance to 
Upper Frame/Wallboard

Ceiling

Edge of
Brick Liner

4" Min. from the Perpendicular
Side Wall to the Edge of Facia

1/2" Min. Clearance
to Combustibles

43 

3

/

4

"

24"

36" Min. from 
Edge of Facial
to Facing Wall
on Open End
of Firebox

Figure 6 - Minimum Clearance - Top View

 CAUTION: Use only the clear-

ances specified in this manual or 

on the firebox rating plate.

Minimum clearances to combustibles are:

•  Sides of outer casing 

0" min.

•  Drywall to sides and top of 

0" min.

   front face

•  Ceiling to opening 

42' min.

•  Floor (see 

Minimum Wall

 

0" min.

 

and Ceiling Clearances

, note C, page 8)

•  Perpendicular walls  

4' min.

  Right and Left

•  Distance to Facing Walls 

36" min.

  on Sides and End of Firebox

iNSTaLLaTiON

Continued

Mantel Clearances for Built-In 
Installation

If placing custom mantel above built-in firebox, 

you must meet the minimum allowable clearance 

between mantel shelf and top of firebox opening 

shown in Figure 7. These are the minimum allowable 

mantel clearances for a safe installation. Use larger 

clearances wherever possible to minimize the heating 

of objects and materials placed on the mantel.

 CAUTION: Do not allow the 

vent-free gas log heater to touch 

or  extend  beyond  the  firebox 

screen. 

If your installation does not meet the above mini-

mum clearances in Figure 7, you must:

•  raise the mantel to an acceptable height,

OR

•  remove the mantel.

Supplied 
Firebox
Hoods Must 
Be Used at 
All Times

Wire-mesh

Screen

Firebox Top

Mantel Shelf

3"

6"

1

/

4

"

Combustible 
Material 1 

1

/

2

Max Thickness

Note:

 All vertical 

measurements are 

minimum distances 

from top of fireplace 

hood to bottom of 

mantel shelf. These 

minimum clearances 

replace any other 

recommended 

clearances supplied 

with your ANS Z21.11.2 

approved gas logs.

Wall board or facing material (above firebox) 
may be of combustible material, including
decorative mantel ornaments or other similar
projections off  of the facing material.

Top Frame
(Combustible Material)

12" 15" 18"

7" Min. 

Note:

 Fireplace shown as cross-section for clarity. 

Mantel material may not be less than 7" from top of
hood. Do not cover louver openings.

BUILT-IN OR INTERNAL WALL 
FIREBOx INSTALLATION

Built-in installation of this firebox involves installing 

firebox into a framed-in enclosure. This makes the 

front of firebox flush with wall. If installing a mantel 

above the firebox, you must follow the clearances 

shown in Figure 7. Follow the instructions below to 

install the firebox in this manner.

1.  Frame in rough opening. The firebox framing 

should be constructed of 2 x 4 lumber or heavier. 

Construct framing using dimensions shown in 

Figure 8 and 9, page 10. It is recommended that 

the framing be constructed first and the unit be 

placed in position. After sliding the unit into place, 

the flanges may be nailed to the framing before 

applying the wallboard to the exterior framing.

2.  If the vent-free firebox is to be installed directly 

on carpeting, tile (other than ceramic) or any 

combustible material other than wood flooring; 

the vent-free firebox must be installed upon a 

metal or wood panel extending the full width 

and depth of the vent-free firebox.

Figure 7 - Minimum Mantel Clearances 

for Built-In Installation

Summary of Contents for FBPS

Page 1: ...nce WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier WAR...

Page 2: ...ervice agency or the gas supplier WARNING For use only with decorative type unvented room heaters Do not build a wood fire This firebox has been tested and approved by I A S under their REQ 2 97 for use with any ANS Z21 11 2 approved gas logs This firebox may be installed in an aftermarket perma nently located manufactured mobile home where not prohibited by state or local codes Aftermarket Comple...

Page 3: ...d and brick liner in place Make sure these parts are in place and screens are closed beforerunningheaterinfirebox The supplied hoods may not be replaced with hoods which may be provided with a log heater Keep the appliance area clear and free from combustible ma terials gasoline and other flam mable vapors and liquids 1 This firebox shall not be installed in a bedroom or bathroom 2 Never install t...

Page 4: ... located directly above thebricklinerandundertheheat shield See Figure 20 page 15 Product Features Operation This firebox is designed for use with approved ANS Z21 11 2 decorative type unvented room heaters Physical size limitations apply Refer to minimum firebox requirements supplied with log heater The maximum size log this firebox will accept is width of 32 depth of 19 and a height of 17 Produc...

Page 5: ...ir Read the following instructions to insure proper fresh air for this and other fuel burning appliances in your home Today s homes are built more energy efficient than ever New materials increased insulation and new construction methods help reduce heat loss in homes Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in During heating months hom...

Page 6: ...ating only if there are doorless passageways or ventilation grills between them AIR FOR COMBUSTION AND VENTILATION Continued DETERMINING FRESH AIR FLOW FOR Firebox LOCATION Determining if You Have a Confined or Unconfined Space Use this work sheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater plus any adjoining rooms with doorless ...

Page 7: ... two perma nent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces see option 1 Figure 3 You can also remove door into adjoining room see op tion 2 Figure 3 Follow the National Fuel Gas Code ANS Z223 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts AIR FOR COMBUSTION AND VENTILATION Con...

Page 8: ...much moisture See Air for Combustion and Ventilation page 5 IMPORTANT Make sure the firebox is level If firebox is not level log set will not work properly Note Your Vanguard firebox is designed to be used in zero clearance installations Wall or fram ing material can be placed against any exterior surface on the rear sides or top of your firebox except where standoff spacers are integrally at tach...

Page 9: ...tel Shelf 3 6 9 1 4 Combustible Material 1 1 2 Max Thickness Note All vertical measurements are minimum distances from top of fireplace hood to bottom of mantel shelf These minimum clearances replace any other recommended clearances supplied with your ANS Z21 11 2 approved gas logs Wall board or facing material above firebox may be of combustible material including decorative mantel ornaments or o...

Page 10: ...s or wood screws through holes in nailing flange see Fig ure 10 Attach firebox to board base through holes in firebox bottom see Figure 10 IMPORTANT When finishing your firebox combustible materials such as wall board gypsum board sheet rock drywall plywood etc may be butted up next to the sides and top of the firebox Combustible materials should never overlap the firebox front facing more than 3 ...

Page 11: ...accessible from both rooms Check your local codes for ap plicable installation requirements Figure 11 Installing Gas Line and Manual Shutoff Valve Manual Shutoff Valve is Located Under Firebox Floor on Either Side Gas Line Installed Through Access Hole on One Side of Firebox Figure 12 Location of Knockouts for Gas Line Extension Key Shut Off Valve Figure 13 Typical Exterior Wall Gas Shut Off Insta...

Page 12: ...ting of the gas sup ply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Figure 15 Locating Electrical Connection and Gas Connection on Either Side of Fireplace Cover Plates Electrical Connection Access Hole Gas Connection Access Hole Hard wiring Firebox Model FBPS can be hard wired to the duplex outlet located inside the firebox bottom if desired This allows the blower acces...

Page 13: ...rts directed upwards along inner side wall of lower compartment The blower outlets must be installed flush to the outer cabinet for air to flow properly 5 Apply gentle force between hook and loop mounting strips to seat blower 6 Remove control knob and lock nut from blower speed control shaft 7 Place speed control shaft through 3 8 hole provided in right side of lower door panel removed in step 2 ...

Page 14: ...oth Sides 2 Screws Each End of Hood Corner Post Front Hood Typical Each Side 3 Screws Top Operating Guidelines and Maintenance Instructions When lit for the first time a vent free log heater will emit a slight odor for about an hour or two This is a normal occurrence which is due to the curing of the logs and the burn in of internal paints and lubricants used in the manufacturing process Keep cont...

Page 15: ...nd to stay away to avoid burnsorclothingignition Young children should be carefully supervised when they are in the same room as the appliance For lighting and operating this vent free firebox please refer to the vent free gas logs manufactur er s instruction manual Parts Not Under Warranty Contact authorized dealers of this product If they can t supply original replacement part s call DESA at 1 8...

Page 16: ...163 01C 16 Illustrated Parts Breakdown Model FBPS These items are used on both sides of fireplace 8 15 17 17 17 7 1 7 2 7 3 2 17 11 17 17 12 6 16 13 10 5 17 17 15 16 4 16 16 6 16 15 17 17 18 Typ Typ Typ 8 17 17 9 14 16 1 3 ...

Page 17: ...ng Flange 12 7 1 02013 Side Refractory Brick Liner 1 7 2 02014 Bottom Refractory Brick Liner 1 7 3 02036 Bottom Refractory Brick Liner 1 8 24007 Side Refractory Retainer 2 9 12125 Screen 4 10 26752 Extruded Louver 2 11 26733 Lower Door Panel 2 12 14200 Receptacle 1 13 21171 Access Hole Cover 3 14 12126 Screen 1 15 26771 Extruded Louver End 1 16 11164 Screw 10 x 1 2 zinc PH 24 17 11165 Screw 10 x 5...

Page 18: ...llation Polished Brass Hood GA6017 For Firebox End GA6054 For Firebox Side Replaces the standard black hood to provide a more formal appearance Note Each kit contains only one hood Two GA6054 kits are required to do both sides of firebox Polished brass louver GBL17 For Firebox End GBL41 For Firebox Side Replaces the standard black louver to provide a more formal appearance Note Each kit contains o...

Page 19: ...____________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _________________________________...

Page 20: ...iring a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIESAND LIMITS THE DURATION OFANYAND ALL IMPLIED WARRANTIES INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO FOUR 4 YEARS ON ALL COMPONENTS FROM...

Reviews: