
www.desatech.com
105163-01C
11
iNSTaLLaTiON
Continued
Figure 11 shows the typical installation for the
gas line. When you have determined how the gas
line will run, locate one of the recessed knockouts
in the firebrick floor (see Figure 12). Firmly tap
the center of the knockout with a chisel until it is
released. Carefully chisel the rough edges of the
hole you have made to smooth edges. This hole
will line up with the hole in the metal floor.
CAUTION: Do not use exces-
sive force to remove the knock-
out. Too much force may damage
the firebrick concrete insert.
A manual shutoff valve, CSA certified and com
-
plying with the
National Fuel Gas code, ANS
Z223.1/NFPA 54
, must be included within (6') six
feet of the vent-free firebox gas supply system. It
may be convenient to install the gas shutoff outside
the vent-free firebox enclosure where it can be
accessed with a key through a wall as shown in
Figure 13. Depending on the type of installation,
some local codes may require you to install two
(2) manual shutoff valves independently accessible
from both rooms. Check your local codes for ap-
plicable installation requirements.
Figure 11 - Installing Gas Line and
Manual Shutoff Valve
Manual Shutoff Valve is
Located Under Firebox
Floor on Either Side
Gas Line Installed
Through Access Hole
on One Side of Firebox
Figure 12 - Location of Knockouts for
Gas Line
Extension
Key
Shut-Off Valve
Figure 13 - Typical Exterior Wall Gas
Shut-Off Installation
Remove Knockout
3/4" Thick Liner
Firebrick Floor
A 36" long 1/2" NPT SCHD 40 flexible gas connec
-
tor line complying with the
National Fuel Gas code
ANS Z223.1/NFPA 54
, may be run from the regula-
tor to the incoming 1/2" NPT black iron gas line.
You may also route the incoming 1/2" NPT black
iron gas line directly to the appliance regulator.
Remove the gas line cover plate from the vent-free
firebox’s outer surround and route the gas line into
the rear of the firebox (see Figure 11).
If a sediment trap is not incorporated as a part of
the gas utilization equipment, one shall be installed
as close to the inlet of the equipment as practical at
the time of installation, as per
ANS Z223.1/NFPA
54
. See Figure 14.
Figure 14 - Sediment Trap Installation
Incoming 1/"
Gas Line
Permitted by
Local Codes
Sediment Trap
(Not Supplied)