OWNER’S MANUAL

 WARNING: Read all instruc-

tions completely and thoroughly
before attempting installation.
Failure to do so could result in
serious injury, property damage
or loss of life. Operation of im-
properly installed and maintained
venting system could result in
serious injury, property damage
or loss of life.

 WARNING: Seal all of the con-

nections with high temperature
silicone (600

°

F/316

°

 C) every time

a vent connection is made. Be-
fore joining elbows and pipes,
apply a bead of high temperature
silicone sealant (GE RTV 106/
Loctite RTV 81585) to the end of
the elbow or pipe. High tempera-
ture silicone must also be used to
re-seal any connections after
maintenance to venting system.

NOTICE: Failure to follow these
instructions will void the warranty.

INSTALLATION
PRECAUTIONS

Consult local building codes before beginning
the installation. The installer must make sure
to select the proper vent system for installa-
tion. Before installing vent kit, the installer
must read this fireplace manual and vent kit
instructions.

Only a qualified service person should in-
stall venting system. The installer must fol-
low these safety rules:

• Wear gloves and safety glasses for

protection

• Use extreme caution when using ladders

or when on roof tops

• Be aware of electrical wiring locations

in walls and ceilings

The following actions will void the war-
ranty on your venting system:

• Installation of any damaged venting

component

• Unauthorized modification of the vent-

ing system

VENTING
INSTALLATION

 WARNING: This gas fireplace

and vent assembly must be
vented directly to the outside.
The venting system must NEVER
be attached to a chimney serving
a separate solid fuel burning ap-
pliance. Each gas appliance must
use a separate vent system. Do
not use common vent systems.

 WARNING: Horizontal sec-

tions of this vent system require
a minimum clearance of 2" from
the top of the pipe and 1" mini-
mum to the sides and bottom.
Vertical sections of this system
require a minimum of 1" clear-
ance to combustible materials on
all sides of the pipe.

• Installation of any component part not

manufactured or approved by DESA
International

• Installation other than as instructed by

these instructions

INSTALLATION PLANNING

There are two basic types of direct-vent
installation:

• Horizontal Termination

• Vertical Termination

It is important to select the proper length of
vent pipe for the type of termination you
choose. It is also important to note the wall
thickness.

For Horizontal Termination:

 Select the

amount of vertical rise desired. The horizon-
tal run of venting must have 1/4" rise for
every 12" of run towards the termination.

NOTICE: Treatment of firestops
and construction of the chase may
vary from building type to build-
ing type. These instructions are
not substitutes for the require-
ments of local building codes. You
must follow all local building
codes.

Note:

 When installing in a chase, you should

insulate the chase as you would the outside
walls of your home. This is especially im-
portant in cold climates. Minimum clear-
ance between vent pipes and combustible
materials such as insulation is 1".

After framing the chase (see Framing and
Finishing
 on page 4) install the vent system
by following the installation instructions.

Installing Vent System in a Chase

A chase is a vertical box-like structure built
to enclose venting that runs along the out-
side of a building. A chase is not required for
such venting.

Continued

 WARNING: Never run the vent

downward as this may cause ex-
cessive temperatures which
could cause a fire.

You may use one or two 90

°

 elbows in this

vent configuration. See Horizontal Termina-
tion Configurations
 on pages 10 and 11.

For Vertical Termination:

 Measure the

distance from the fireplace flue outlet to the
ceiling. Add the ceiling thickness, the verti-
cal rise in an attic or second story, and allow
for sufficient vent height above the roofline.

You may use one or two 90

°

 elbows in this

vent configuration. See Vertical Termination
Configurations
 on pages 13 through 15.

Note:

 You may use two 45

°

 elbows in place

of a 90

°

 elbow. You must follow rise to run

ratios when using 45

°

 elbows.

For two-story applications, firestops are re-
quired at each floor level. If an offset is
needed in the attic, additional pipe and el-
bows will be required.

You may use a chase with a vent termination
with exposed pipe on the exterior of the
house. See Installing Vent System in a Chase,
below.

Your Vanguard direct-vent fireplace has
been tested for a minimum 3' rise with a
maximum 10" wall thickness. The maxi-
mum horizontal run is 20' with 8' vertical
rise (see Installation for Horizontal Termi-
nation
, page 8). The maximum vertical run
is 30' (see Installation for Vertical Termina-
tion
, page 12).

It is very important that the venting system
maintain its balance between the combus-
tion air intake and the flue gas exhaust.
Certain limitations apply to vent configura-
tions and must be strictly followed.

Summary of Contents for BHDV34N(A)

Page 1: ...efer to this manual for correct in stallation and operational procedures Forassistance or additional information consultaqualifiedinstaller service agency or the gas supplier This appliance may be ins...

Page 2: ...glass door must be properly seated and sealed If this unit is not properly installed by a qualified service person with glass door properly seated and sealed gas leakage can occur Carbon Monoxide Poi...

Page 3: ...ITOR This fireplace has a piezo ignitor This sys tem requires no matches batteries or other sources to light fireplace Figure 1 Vanguard Direct Vent Fireplace BHDV Series Glass Door Assembly Blower Ad...

Page 4: ...ure 3 34 1 2 34 3 4 20 Vertical Termination 19 Horizontal Termination CLEARANCES Minimum clearances to combustibles for the fireplace are as follows Back and sides 0 mm Perpendicular walls 6 152mm Flo...

Page 5: ...pe cifically approved for this fireplace Minimum clearance between vent pipes and combustible materials is 1 25 mm except where stated otherwise Combustible material may be flush with the top front of...

Page 6: ...de walk or a paved driveway located on public property 84 inches 2133mm minimum M clearance under veranda porch deck 12 inches 305mm minimum N clearance above a roof shall extend a minimum of 24 inche...

Page 7: ...proper length of vent pipe for the type of termination you choose It is also important to note the wall thickness For Horizontal Termination Select the amount of vertical rise desired The horizon tal...

Page 8: ...appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have four locking lugs indentations These lugs will slide straight i...

Page 9: ...dge of the vent cap Position the vent cap in the center of the 7 1 2 or 10 hole on the exterior wall with the arrow on the vent cap pointing up Insure proper clearance of 1 to combustibles is maintain...

Page 10: ...on for use with corner installation UP Horizontal Venting See information in Figures 17 and 18 for Vertical V and Horizontal H maxi mums and minimums The same amounts apply for flexible venting BGFVK...

Page 11: ...max 8 min 8 min 20 max 20 max 8 max 20 max Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max 20 max 20 max Figure 19 Horizontal Termi...

Page 12: ...ce to combus tibles when passing through ceilings walls roofs enclosures attic rafters etc Do not pack air spaces with insulation Also note maximum vertical rise of the venting system and any maximum...

Page 13: ...e Figure 23 Align the support box vertically and horizontally using a level Temporarily tack the support box in place through the inside walls and into the roof sheathing 4 Using tin snips cut the sup...

Page 14: ...d Venting Configuration With No Horizontal Run VENTING INSTALLATION Continued Venting with Two 90 Elbows Vertical V1 Horizontal H 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max Note Vertical V1 Ve...

Page 15: ...xial Pipe 6 pcs D1010 7 x 24 Galvanized Coaxial Pipe 6 pcs D1020 7 x 48 Galvanized Coaxial Pipe 6 pcs D1030 7 Adjustable 7 12 Galvanized Coaxial Pipe 6 pcs D1050 7 x 6 Galvanized Coaxial Pipe 6 pcs D2...

Page 16: ...un system scirculatingblowerwhile using heater This will help circu late the heat throughout the house In the event of a power outage you can use this heater as your primary heat source NOTICE A quali...

Page 17: ...the right side see Figure 33 Route power cord through both plastic bushing s and plug the power cord into a properly grounded 3 prong wall receptacle near the firebox b If your fireplace system insta...

Page 18: ...con nector if allowed by local codes not provided AnA G A design certifiedmanualshutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Pur chase the A G A design certifie...

Page 19: ...ne provided by installer from manual shutoff valve to fireplace Route flexible gas supply line through one of the access holes on side of fireplace 3 Attach flexible gas line from gas sup ply to contr...

Page 20: ...e Figure 37 2 Open propane supply tank valve for propane fireplace or main gas valve lo cated on or near gas meter for natural gas fireplace 3 Make sure control knob of fireplace is in the OFF positio...

Page 21: ...h as lamps direct sunlight fireplace or heat and air conditioning ducts 5 Gently remove the cover of the ther mostat from the base Grasp the sides of the cover firmly and pull to separate from the bas...

Page 22: ...ve battery cover on back of re mote control unit 2 Attach terminal wires to a 9 volt bat tery not included Place battery into the battery housing 3 Replace battery cover onto remote con trol unit Figu...

Page 23: ...4 Slide the left retainer bracket against the left side brick panel Loosely se cure the bracket screw This secures the left side brick panel 5 Install the right brick panel using the same method descr...

Page 24: ...s for fireplace model numbers WARNING Failure to position thepartsinaccordancewiththese diagrams or failure to use only parts specifically approved with this heater may result in property damage or pe...

Page 25: ...ort level between HI and LO The burners will turn on and off automatically to maintain the comfort level you select The ideal comfort setting will vary by household depending upon the amount of space...

Page 26: ...e left just inside the louver panel Both the GA3700 manual blower and the DA3610T thermostatically controlled blower have an ON setting and an OFF setting The blower will only run when the switch is i...

Page 27: ...pect the flames after installationtoensureproperinstallationand performance Figure 60 shows a typical flame pattern for BHDV34N A and BHDV34P A If burner flame pattern differs from that described turn...

Page 28: ...G Turn off fireplace and let cool before cleaning CAUTION Youmustkeepcon trol areas burners and circulat ing air passageways of fireplace clean Inspect these areas of fire place before each use Have f...

Page 29: ...n loose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut ho...

Page 30: ...warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local pro pane gas company 3 Clean burner see Cleaning and Maintenance page 28 or replace burner orifice 1...

Page 31: ...es at burner inlet blocked 3 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces unwanted odors Fireplace shuts off in use Gas odor even when control knob is in OFF position Gas odor during...

Page 32: ...n servicing controls Wiringerrorscancause improper and dangerous opera tion Verify proper operation af ter servicing Red Variable Fan Switch Fan Switch N O Black Black Green White On 110 115 V A C Blo...

Page 33: ...ssure 3 5 w c 10 0 w c Minimum Inlet Supply Pressure 4 5 w c 11 0 w c Thermal Efficiency 70 70 Dimension Inches mm HxWxD Fireplace 33 x 34 x 18 1 2 33 x 34 x 18 1 2 838 x 940 x 470mm 838 x 940 x 470mm...

Page 34: ...02W Series Off White Paint Shown with optional base and laminate hearth and mantel trim accessories Dimensions WxHxD 563 4 x483 4 x22 3 4 HARDWOOD HEARTH BASE G3000F Series Walnut Finished G3001U Seri...

Page 35: ...F STATUS ON LO HI TEMP RECEIVER AND HAND HELD REMOTE CONTROL KIT GHRC SERIES For all models Allows the heater to be turned on and off conveniently RECEIVER AND HAND HELD THERMOSTAT REMOTE CONTROL KIT...

Page 36: ...OPANE ILLUSTRATED PARTS BREAKDOWN BHDV34N A 1 2 3 4 6 6 36 5 5 6 5 11 Included in Hardware Pack 7 7 8 10 9 12 13 14 15 16 17 18 19 20 32 21 22 23 24 25 26 27 28 28 29 30 31 1 31 4 31 2 31 3 33 32 32 3...

Page 37: ...T Pilot Natural 1 19 104498 01 Thermocouple 1 20 104499 01 Thermopile 1 21 104500 01 Ignitor 1 22 104501 01 Ignitor Bracket 1 23 104502 01 Ignitor Screw 1 24 104503 01 Ignitor Wire 1 25 104504 01 Burn...

Page 38: ...ROPANE ILLUSTRATED PARTS BREAKDOWN BHDV34P A 1 2 3 4 6 6 36 5 5 6 5 11 Included in Hardware Pack 7 7 8 10 9 12 13 14 15 16 17 18 19 20 32 21 22 23 24 25 26 27 28 28 29 30 31 1 31 4 31 2 31 3 33 32 32...

Page 39: ...18 104497 02 SIT Pilot Propane LP 1 19 104498 01 Thermocouple 1 20 104499 01 Thermopile 1 21 104500 01 Ignitor 1 22 104501 01 Ignitor Bracket 1 23 104502 01 Ignitor Screw 1 24 104503 01 Ignitor Wire 1...

Page 40: ...ing a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED...

Reviews: