Transformer Ration Analysis Software Manual
20
5.2 Retrieving Test Plans From ATRT-03 Memory
Select the “Retrieve Test Plan from TTR” menu option (Figure 8). The ATRT-03 will beep once to
indicate it has been accessed. The ATRT Test Plan Directory screen will display all the test plans
stored in the ATRT-03’s memory (Figure 15).
Click on the test plan to highlight the selection. More than one test plan can be selected by holding the
computer’s CTRL key when clicking a file. All the test plans can also be selected by clicking the
“Select All” button in the dialogue box.
Figure 15. ATRT-03 Test Plan Directory
Click the “OK” button to retrieve the selected test plans from the ATRT-03 memory now. The
program will retrieve the test plans from the ATRT-03 and store in the working directory. The Test
Plan Directory screen will disappear after the file transfer is completed.
The test plan file name uses the file name prefix and the test plan number listed in the directory.
For example, select test plan # 1 from the ATRT-03 memory, the file name shall be “PLAN1”.
The “Filename Prefix” box allows the user to type in text that will precede the test plan number. The
default file name prefix is “PLAN.” All the files selected will have the same prefix when uploaded to
the PC.