Vanderbilt IR261 Installation Manual Download Page 2

 

003908_f 

 

 

 

 

 

 

 
The  passive  infrared  motion  detector  IR261  is 
designed  for  indoor  surveillance  applications  for 
intruder  alarm  systems.  Ceiling  mounting  introduces 
the  possibility  of  overlooking  obstacles  in  the 
surveillance area. 
A pyroelectric dual sensor is placed at the focus of a 
multisegment  lens,  which  subdivides  the  coverage 
area into different detection zones. This arrangement 
provides 33 pairs of sensitive zones 

The  sensor  receives  infrared  energy  from  its 
environment,  which  is  used  by  the  detector  as 
reference.  As  long  as  this  reference  is  stable,  the 
alarm relay remains energised. When a person enters 
or  leaves  one  of  the  sensitive  zones,  the  detector 
registers  a  rapid  change  in  the  amount  of  infrared 
energy  received.  The  subsequent  electrical  signal 
from the sensor is processed for alarm triggering. 
Within  the  specified  environmental  conditions,  the 
detector  is  sensitive  to  intruders,  thereby  covering  a 
wide range of walking speeds. However, the detection 
capacity  decreases  when  there  is  only  a  slight 
difference between the background temperature and 
that of the intruder. 
Slow changes in the infrared energy level caused e.g. 
by  temperature  changes  of  walls  etc.,  are 
automatically compensated by the detector and 

do 

not cause alarm. 

Installation instructions 

 Mount the detector on  a stable ceiling  surface free 

from vibrations. 

 Several  detectors  may  be  installed  in  one  room. 

Overlapping  zone  patterns  do  not  create  any  false 
alarm problems. 

 Align  the  detectors  in  such  a  way  that  the  main 

direction in which an intruder is expected to move is 
at a right angle to the sensitive zones. 

 The  detector  will  not  react  to  movements  behind 

walls, large pieces of furniture, pillars, big plants or 
glass. 

 

Do  not  point  the  sensitive  zones  at  objects  that 
are  subject  to  rapid  temperature  changes,  e.g. 
heaters, heated surfaces, air conditioning outlets, 
windows. 

 Mounting height between 2m and 5m. 

 

Avoid  heights  greater  than  5m  because  of 
reduced detection sensitivity. 

Mounting 

1. 

Open the detector 

-  Slide the release lever to the direction of the arrow. 

The  sensor  part  can  now  be  detached  from  the 
detector base. 

2. 

Feed the cable through the opening in the detector 
base  or  through  the  break-out  cable  entry  on  the 
side 

3. 

Mount  the  detector  base  on  a  solid  surface  inside 
the room, using the enclosed screws. 

4. 

Connect the terminals 

. The terminal connections 

are  best  suited  for  solid  core  cables.  When  using 
multicore  cables,  one  or  more  of  the  following 
procedures must be carried out: 

-  The  bare  wire  must  be  doubled  over  before  it  is 

inserted into the clamp. 

-  A crimp must be attached to the cable ends for the 

insertion into the clamp. 

5. 

Pattern  setting  according  to  the  separate  chapter 
"Programming". 

6. 

Put the sensor unit into the detector base (mark the 
arrow) and push until the release lever clicks. 

7. 

Tighten the enclosed locking screw. 

Programming 

Alarm LED active / inactive 

 

Alarm LED (red) 

 

Switch 1 

LED active 
LED lights up in case of alarm, 

default 

 

LED not active:   
The LED becomes active when 
connecting the wire terminal 7 
(L/C) with - 12V. 

 

The LED can be switched to 
active / inactive mode by means 
of external switches. 

 

 

Alarm memory 

 

Alarm memory (yellow) 

 

Switch 2 

Active 
Auto reset, 

memory

As an alarm is activated, the 
yellow LED flashes for 3 
minutes and remains lit for 47 
minutes. Afterwards it is 
automatically reset and the 
memory is cleared. 

 

Not active 
Memory OFF, 

default 

 

 

Type of alarm contact 

 

Alarm contact 

Switch 3 

N/O: relay is normally open and 
closes when alarm is activated 

 

N/C: relay is normally closed 
and opens when alarm is 
activated, 

default 

 

 

Detection sensitivity 

 

Sensitivity 

Switches 4 & 

120% 

 

100%, 

default 

 

80% 

 

60% 

 

 

Alarm pulse counter 

 

Number of pulses after alarm 
activation (within 25 sec) 

Switches 6 & 

1 x

 

Alarm 

 

2 x

 

Alarm 

default 

 

3 x

 

Alarm 

Recommended 
for the 
prevention of 
false alarm 
caused by 
temperature 
fluctuation 

 

4 x

 

Alarm

 

 

 

Commissioning 

 

Check  that  switch  1  is  in  position  [ON],  see 
"Programming". 

1. 

Switch the power on. 

2. 

Wait  for  one  minute  until  the  detector  is  ready  for 
operation and the red alarm LED stops flashing. 

3. 

Walk  upright  through  the  surveillance  area  in  the 
direction  of  the  arrows,  at  approximately  one  step 
per second. 

-  Check  if  an  alarm  is  activated.  The  detector  must 

trigger an alarm, even when the furthest end of the 
coverage area is crossed. 

4. 

When  the  walk  test  is  finished,  ensure  that  the 
detector is in the correct operating mode again, i.e. 
check the position of the programming switches. 

Maintenance 

Repeat  the  walk  test  regularly  and  check  the  IR 
window  for  soiling  to  ensure  that  the  detector  is 
functional. 

Note: 

Each 

modification 

or 

manipulation 

to 

components  of  a  detector,  the  detector  looses  its 
intented function and the approval expires. 

Troubleshooting 

Detector does not respond 

-  Check supply voltage and polarity. 

No alarm indication on the detector 

-  Check programming switches. 

No alarm 

-  Check alarm relay. 
-  Check alarm line. 

Permanent or temporary alarm 

Switch  the  alarm  indication  on  the  detector  to  [ON], 
cover the detector window with a cardboard box and 
wait for 2 minutes. 
-  If the red LED lights up, the detector is defective. 
-  If the LED does not light up: 

-  Locate  sources  of  interference  in  the  coverage 

area and eliminate them. 

-  Check the sensitivity settings. 
-  Reposition the detector. 

Insufficient range 

-  Check the window for soiling. 
-  See  also  installation  instructions  and/or  range 

adjustments. 

Technical data 

Supply voltage (nom. 12V) ................. 10.5 to 30.0V

DC 

-. max ripple (0...100 Hz) .................................. 2.0Vpp 

Current consumption (quiescent, at 12V) .......... 25mA 
-.  ....................................................... +2mA at L/C use 

Alarm output ........................................ electronic relay 
-. relay contact (opens at alarm)... 24V(

AC/DC)

 / 250mA 

-. alarm holding time .................................... 2 seconds 

Alarm / walktest indication .................................... LED 

Tamper switch .................... closed with cover in place 
-. contact rating ............................. 30V(

AC/DC)

 / 250mA 

Evaluation mode................................. "HIGH" / "LOW" 

Sensitivity ........................................................ 4 levels 

Ambient conditions: 
-  operating temperature ........................ -15°C...+55°C 
-  storage temperature ........................... -15°C...+55°C 
-  humidity (EN60721)   .................................. <95% rH 

Details for ordering 

IR261 Passive infrared detector    VBPZ:5667770001 

EC Declaration of Conformity 

Hereby, Vanderbilt International (IRL) Ltd declares 
that this equipment type is in compliance with all 
relevant EU Directives for CE marking. From 
20/04/2016 it is in compliance with Directive 
2014/30/EU (Electromagnetic Compatibility 
Directive. 
The full text of the EU declaration of conformity is 
available at: 

http://pcd.vanderbiltindustries.com/doc/SPC

 

 

1

2

4

5

3

6

3

IR261 Instructions for use 

Summary of Contents for IR261

Page 1: ...003908_f Edition 02 2016 Supersedes 003908e en Passive infrared detector de Passiv infrarotmelder fr it es nl D tecteur infrarouge passif Rivelatore passivo a infrarossi Detector de infrarrojos pasiv...

Page 2: ...ed to active inactive mode by means of external switches Alarm memory Alarm memory yellow Switch 2 Active Auto reset memory As an alarm is activated the yellow LED flashes for 3 minutes and remains li...

Page 3: ...nd 3 Minuten und leuchtet danach f r 47 Minuten weiter Dann wird der Speicher automatisch zur ck gesetzt nicht aktiv Speicher AUS Standart Art des Alarmkontaktes Alarmkontakt Schalter 3 Relais ist im...

Page 4: ...2 Active Lors d une alarme la LED jaune s allume clignote pendant 3 minutes et reste ensuite allum e pendant 47 minutes Puis la m moire d alarme est automatiquement remise z ro Non active La m moire...

Page 5: ...47 minuti dopodich la memoria verr automaticamente riazzerata non attivo Memoria OFF default Tipo di contatto d allarme Contatto d allarme Interruttore 3 Il rel normalmente aperto e chiuso in caso di...

Page 6: ...arma amarillo Conmutador 2 activo Cuando se activa una alarma el LED amarillo parpadea durante 3 minutos y emite luz permanente durante 47 minuto Despu s la memoria es repuesta autom ticamente inactiv...

Page 7: ...t LED niet actief Door aansluiten van klem 7 L C met 12V wordt LED actief Met externe schakelaars kan zo de LED actief inactief geschakeld worden Alarmgeheugen Alarmgeheugen geel Schakelaar 2 Actief B...

Page 8: ...003908_f 8 Issued by Vanderbilt Clonshaugh Business and Technology Park Clonshaugh Dublin D17 KV84 Ireland www service vanderbiltindustries com...

Reviews: