background image

PRINTED IN THE U.S.A.

PAGE 9

MAINTENANCE & TROUBLESHOOTING

SECTION 9

9.5 TROUBLESHOOTING

The following check list should be used as a guideline for troubleshoot-
ing problems.

ARE THE TOWERS DEPRESSURIZING?

Check the purge valve for proper operation.  Check the purge
muffler. It might be clogged.  If clogged or damaged, replace it.
Use manual overide to check.  (This should cause
depressurization.)

IS THE  DEW POINT ACCEPTABLE?

• ARE THE INLET CONDITIONS WITHIN THE SPECIFICATIONS?

Reference Section 3.1 for the inlet conditions of the dryer.

Correct the inlet conditions if necessary.  Excessive inlet flow will
greatly reduce the performance of the dryer.

• WAS THE DESICCANT INSTALLED?

Make sure that the desiccant was installed.  Reference Section 9.3
for desiccant installation procedures.

• IS THE DESICCANT CONTAMINATED WITH LUBRICANTS?

Check the condition of the desiccant bed.  If the bed is
contaminated with lubricants, replace the desiccant following the
procedures in Section 9.3.

• IS THE DESICCANT CONTAMINATED WITH MOISTURE?

If the dryer was operated under excessive inlet conditions, the
desiccant bed may be saturated with liquid moisture. Check
upstream equipment such as aftercoolers.  Check the actual inlet
conditions, correct them and condition the bed following the
procedures in Section 5.3.

• ARE THE BYPASS VALVES OPEN OR LEAKING?

Check the valves (if installed).  Repair or replace if faulty.

IS THE POWER ON AND RUN SWITCH PRESSED?

Check the main power source and check that the Power LED is
lit.  Make sure that the dryer Run switch has been pressed and
that the Run LED is lit

IS THE SYSTEM PRESSURIZED?

The dryer is designed to operate at 60 to 150 psig.  Check the
upstream equipment and any isolation or bypass valves.

IS THE DRYER CYCLING?

• IS THE CONTROL SYSTEM WORKING?

Is there incoming power to the control box.

• IS THERE CONTROL AIR PRESSURE, 60 PSIG MINIMUM.

Make sure that the dryer inlet pressure is above 60 PSIG.  Check
the control air filter element and replace it with a new element.
Reference  Section 9.4 for element replacement instructions.

• IS THE INLET VALVE FAULTY?

Rebuild or replace the inlet valve as necessary.  Use manual
override to check.

• IS THE PURGE EXHAUST VALVE FAULTY?

Rebuild or replace the faulty purge exhaust valve.  Use manual
override to check.

• IS THE OUTLET VALVE FAULTY?

Check the outlet shuttle valve.

CAUTION

THE DRYER CONTROL CIRCUIT IS DUAL VOLTAGE RATED.
NEVER SET THE BOARD TO A VOLTAGE OTHER THAN THE
VOLTAGE RATING OF THE DRYER LISTED ON THE DRYER
DATA TAG.  SETTING THE BOARD INCORRECTLY WILL CAUSE
DAMAGE TO THE INLET AND PURGE VALVES AND POSSIBLE
PERSONAL INJURY OR FIRE.

9.6 WIRING DIAGRAMS

Summary of Contents for HLS-120

Page 1: ...PERSONAL INJURY DO NOT REMOVE REPAIR OR REPLACE ANY ITEM ON THIS DRYER WHILE IT IS UNDER PRESSURE NEVER OPERATE THIS DRYER ABOVE THE RATED OPERATING CONDITIONS OPERATION ABOVE SPECI FIED CONDITIONS WI...

Page 2: ...INJURY AND OR EQUIPMENT DAMAGE MAY RESULT MAKE SURE THAT ALL EQUIPMENT BEING USED TO LIFT THE DRYER IS CAPABLE OF LIFTING THE WEIGHT OF THE DRYER IF THE DRYER IS TO BE TRANSPORTED OVERHEAD MAKE SURE T...

Page 3: ...S 80 HLS 120 HLS 150 ELECTRICAL Nema 4 Electrical enclosure Standard 115V 115V 1PH 50 60Hz Optional 230V 230V 1PH 50 60Hz DESICCANT Material Activated Alumina 1 8 2 5 MM Bead type Quantity Per Tower L...

Page 4: ...to start up 4 3 REMOTE PURGE EXHAUST PIPING To reduce the noise during purging and tower depressurization this dryer was supplied with a muffler for installation on the purge exhaust valve If the soun...

Page 5: ...RSONAL INJURY AND DAMAGE TO THE DRYER WILL OCCUR IF THE DRYER IS CONNECTED TO A POWER SOURCE OTHER THAN THE VOLTAGE LISTED ON THE DATA TAG WHEN INSTALLING THE ELECTRICAL CONNECTIONS FOR THIS DRYER COM...

Page 6: ...d the purge air which was vented to atomosphere earlier in the cycle is now used to repressurize the regenerated tower FIGURE 6A PNEUMATIC SCHEMATIC 6 1 2 CHANGEOVER DEPRESSURIZATION STAGE Tower chang...

Page 7: ...ressurize both towers of the dryer until there is demand on the compressor The Hold LED will light if the dryer is wired as described and the compressor is not running IMPORTANT Operating this dryer o...

Page 8: ...ING THE DUST AND PROLONGED CONTACT WITH THE SKIN FIRST AID IN CASE OF EYE CONTACT IMMEDIATELY FLUSH EYES WITH PLENTY OF WATER FOR AT LEAST 15 MINUTES CONSULT A PHYSICIAN Take dryer off stream followin...

Page 9: ...ions correct them and condition the bed following the procedures in Section 5 3 ARE THE BYPASS VALVES OPEN OR LEAKING Check the valves if installed Repair or replace if faulty IS THE POWER ON AND RUN...

Page 10: ...ntrol Air Filter Element control air filter Desiccant Activated Alumina 1 8 dia 25 pail Control Box complete Circuit Board only Membrane Panel Pressure Switch HLS 55 115V PART NO 14 2073 26 6516 26 65...

Page 11: ...rol Air Filter Element control air filter Desiccant Activated Alumina 1 8 dia 25 pail Control Box complete Circuit Board only Membrane Panel Pressure Switch HLS 120 115V PART NO 14 2075 26 6515 26 651...

Page 12: ...FROM IMPROPER GROUNDING CAN CAUSE INJURY OR DEATH GROUND UNIT AND RELATED EQUIPMENT ACCORDING TO NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS WARNING WARNING READ THE OPERATOR S MANUAL BEFORE START...

Reviews: