VAMP Ltd
Ethernet adapter
User’s manual
VEA 3CGi
2.1.1.
Connection to 100-series relays
Figure 2.1.1-1 Connection to 100-series relay
Galvanically isolated.
Modbus and VAMPSET communication over TCP/IP.
Powered by VAMP relay via VX015 cable.
The REMOTE port of the 100-series has both REMOTE
and LOCAL port signals.
Cable VX015 is connected to both ports of VEA 3CGi.
2.1.2.
Connection to 200-series relays
Figure 2.1.2-1 Connection to 200-series relay
Galvanically isolated
Modbus and VAMPSET communication over TCP/IP.
Powered by VAMP relay via VX003 cable.
Serial cable 1 : RS-232 interface to LOCAL port
-
VAMPSET communication
-
Clock syncronization
Serial cable 2 : RS-232 interface to REMOTE port
-
Modbus TCP communication
VMVEAi.EN001
Vamp 24h support phone : +358 (0)20 753 3264