DSBA3600 • Rév. 22/06/2020
27
EN
Positioning function
+
+
-
-
Setpoint
signal
Feedback
signal
4-20mA
0-10V
Learning mode - open position
Learning mode - storage
Learning mode - closed position
Led de validation (pos. 2)
Validation led (pos.1)
Learning mode
Put the power on
With the «
Next Mode
» and « Ok Mode » buttons, select the learning mode (the
APPR led
is on)
Press «
APPR Close
» button to drive the valve up to its closed position and keep both «
APPR Close
» and
«
APPR Mem
» buttons pressed during
2 seconds
.
The
APPR1 led
blinks and lights up. The closed position is correctly recorded
Press «
APPR Open
» button to drive the valve up to its open position and keep both «
APPR Open
» and
«
APPR Mem
» buttons pressed during
2 seconds
.
The
APPR2 led
blinks and lights up. The open position is correctly recorded
Both open and closed positions are recorded. Select positioning (POSI) mode and press «
OK Mode
» to con-
firm.
Setpoint signal
The actuator positions itself according to the setpoint signal. Two signal types are available, a 0-10V range voltage signal
or a 4-20mA range current signal. It’s possible to change this signal using the
A
X
MART
®
software without modifying the
electric wiring.
Feedback
According to its position, the actuator will provide a proportional voltage signal (0-10V) or a current signal (4-20mA).
It’s possible to modify the feedback signal using the
A
X
MART
®
software, but it requires changing the wiring.