EN
DSBA3200 • Rév. 09/06/2020
29
TECHNICAL DATA
Type (1/4 turn electric actuator)
ER10
ER20
ER35
ER35
ER60
ER100
Housing type
Small housing (see p.19)
IP protection (EN60529)
IP66
(dusts, water spraying « flow <12.5 L/min »)
Corrosion resistance (outdoor and
indoor use)
Housing: PA6 25% GF and cover: PA6 UL94V0
Raw material : 304L Stainless Steel or Steel + Zn treatment
Temperature
-10°C to +55°C (BBPR GS2: -10°C to +40°C)
Hygrometry
maximum relative humidity 80 % for temperatures up to 31 °C decreasing linearly
to 50 % relative humidity at 40 °C
Pollution degree
Altitude
altitude up to 2 000 m
Extended environmental conditions
Outdoor use and in WET LOCATION
Sound level
61 dB
Weight
1 Kg
2.1 Kg
MECHANICAL DATA
Nominal
torque
10Nm 20Nm 35Nm 35Nm 60Nm 100Nm
1/4 turn travel time (standard ER)
11s
11s
25s
7s
12s
23s
1/4 turn travel time (slow ER)
41s
79s
119s
1/4 turn travel time (ER POSI)
25s
41s
79s
119s
Mounting actuator base (ISO5211)
Star 14
F03-F04-F05
Star 22
F05-F07
Swing angle
90° (others on request)
Mechanical end stops
90° +/- 5°
Manual override
Out axle
Direction of rotation
Anticlockwise to open
ELECTRICAL DATA
Voltage ±10%
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
15 V to 30 V AC 50/60 Hz and 12 V to 48 V DC
Frequency 50/60Hz
Power consumption
15W (0.08A) cos j = 0.75
45W (0.15A) cos j = 0.75
Overvoltage category
TRANSIENT OVERVOLTAGES up to the levels of OVERVOLTAGE CATEGORY ll
TEMPORARY OVERVOLTAGES occurring on the MAINS supply
Torque limiter
Electric
Duty cycle (CEI34)
50%
Limit switches maximal voltage
4 to 250V AC/DC
(Overvoltage category II)
Limit switches maximal current
1mA to 5A max
Electrical wiring
1 ISO M20 cable gland and 1 DIN43650 3P+T connector
Inrush current
Circuit breaker type D, nominal current according the number of actuators (max. 4 ac-
tuators) or use a inrush current limiter at the output of the circuit breaker.
large housing (see p.19)
Voltage ±10%
(BBPR GS2)
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
24 V to 30 V AC 50/60 Hz and 24 V to 48 V DC