background image

5

Duct pieces 

Total

Equivalent number
length  x used      =

3- 1/ 4” x 10”
Rect.,
straight

1 Ft.           x (      )   =

Ft.    

8” Round,
straight

1 Ft.           x (      )   =

Ft.    

3- 1/ 4” x 10”
Rect. 90

0

elbow

15 Ft.         x (      )   =

Ft.    

3- 1/ 4” x 10”
Rect. 45

0

elbow

9 Ft.           x (      )   =

Ft.    

3- 1/ 4” x 10”
Rect. 90

0

flat elbow

24 Ft.         x (      )   =

Ft.    

3- 1/ 4” x 10”
Rect.
wall cap
with damper

30 Ft.         x (      )   =

Ft.    

3- 1/ 4” x 10”
Rect. to
6” round
transition

5 Ft.           x (      )   =

Ft.    

3- 1/ 4” x 10”
Rect. to
6” round
transition
90

0  

elbow

20 Ft.         x (      )   =

Ft.    

6” Round,
90

0  

elbow

15 Ft.         x (      )   =

Ft.    

6” Round,
45

0  

elbow

9 Ft.           x (      )   =

Ft.    

Ft.    

7” Round,
straight

1 Ft.           x (      )   =

Ft.    

Subtotal column 1  =

Duct pieces 

Total

Equivalent number
length  x used      =

6”- 8” Round
wall cap
with damper

30 Ft.         x (      )   =

Ft.    

Round

wall cap
with damper

30 Ft.         x (      )   =

Ft.    

7” or 8” 

Round,

90

0  

elbow

15 Ft.         x (      )   =

Ft.    

7” or 8” 

7” or 8” 

Round,

45

 

elbow

9 Ft.           x (      )   =

Ft.    

Ft.    

Ft.    

Ft.    

6”- 8” Round,
roof cap

30 Ft.         x (      )   =

Ft.    

7” or 8”

Round,

roof cap

30 Ft.         x (      )   =

Ft.    

Subtotal column 2  =

Subtotal column 1  =

Total ductwork      =

Maximum Duct  Length: 

For satisfactory air movement,

the total duct length of a 3 1/ 4” x 10” rectangular  6” or 7”
diameter round duct should not exceed 100 equivalent feet.

6” round to
3- 1/ 4” x 10”
rect. 
transition

1 Ft.           x (      )   =

Ft.    

6” round to
3- 1/ 4” x 10”
rect. 
transition
90

0  

elbow

16 Ft.         x (      )   =

Ft.    

7” round to
3 1/ 4” x 10”
rect. 
transition

8 Ft.           x (      )   =

Ft.    

7” round to
3- 1/ 4” x 10”
rect. 
transition
90

0  

elbow

23 Ft.         x (      )   =

Ft.    

Installation – 

Ducting Calculation Sheet

Summary of Contents for VCR-E30AG

Page 1: ...Use Care and Installation Guide Model number Serial Number PLATEAU VPL E30AS VPL E36AS SUMMIT VSU E30AS VSU E36AS CRESCENT VCR E30AG VCR E36AG AUG12 0401...

Page 2: ......

Page 3: ...od Specifications 8 10 Mounting the Hood VSU 11 Mounting the Hood VPL 12 Mounting the Hood VCR 13 Ductless Recirculating 14 FEATURES CONTROLS Mechanical Controls VSU 15 Electronic Controls VPL and VCR...

Page 4: ...of and amount of food being prepared WARNING TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP FIRE OBSERVE THE FOLLOWING a SMOTHER FLAMES with a close fitting lid cookie sheet or me...

Page 5: ...in conformance with National Electrical Code ANSI NFPA 70 latest edition or CSA standards C22 1 94 Canadian Electrical Code Part 1 and C22 2 No 0 M91 latest edition and all local codes and ordinances...

Page 6: ...cal codes Extension duct cover accessory Recirculating kit accessory HARDWARE PACKAGE CONTENTS 1 Suction Cup PARTS SUPPLIED MODELS VSU VPL VCR 1 Hood with internal blower 1 Duct cover wall bracket 1 D...

Page 7: ...ent number length x used 6 8 Round wall cap with damper 30 Ft x Ft Round wall cap with damper 30 Ft x Ft 7 or 8 Round 900 elbow 15 Ft x Ft 7 or 8 7 or 8 Round 450 elbow 9 Ft x Ft Ft Ft Ft 6 8 Round ro...

Page 8: ...and will loose its performance and efficiency If available also refer to range manufacturer s height clearance requirements and recommended hood mounting height above range Always check your local co...

Page 9: ...ng option Use single wall rigid Metal ductwork only Fasten all connections with sheet metal screws and tape all joints w certified Silver Tape or Duct Tape Some Ducting Options Installation Ducting Op...

Page 10: ...od Specifi cations 2 2 2 9 24 27 4 8 27 3 26 27 9 4 5 7 8 9 23 2 4 5 5 2 4 46 8 9 Standard Duct Cover Min ducted 27 1 2 Min recirc 32 Max ducted 42 1 2 V1C 00SU Extension Min ducted 46 1 2 Min recirc...

Page 11: ...PL Hood Specifi cation 4 8 9 7 21 4 9 46 41 8 27 2 4 27 21 6 9 33 2 27 6 6 27 29 8 27 Standard Duct Cover Min ducted 27 Min recirc 31 Max ducted 48 V1C 00PL Extension Min ducted 43 1 2 Min recirc 47 1...

Page 12: ...on VCR Hood Specifi cation 34 26 27 21 4 9 46 41 4 27 4 8 9 21 6 9 2 4 5 7 Standard Duct Cover Min ducted 23 Min recirc 27 Max ducted 42 V1C 00CR Extension Min ducted 41 1 2 Min recirc 45 1 2 Max duct...

Page 13: ...to wall below ceiling or soffit using 2 M4x1 screws 8 Install electrical 9 Install duct work and duct tape 10 Power up hood and check for leaks around duct tape 11 Place telescopic duct covers onto ho...

Page 14: ...rt fig A2 9 Center and attach duct cover mounting bracket to wall just below the ceiling or soffit using 2 M4 x 1 screws 10 Install electrical and duct work Seal duct work with aluminum duct tape 11 P...

Page 15: ...rt fig A2 9 Center and attach duct cover mounting bracket to wall just below the ceiling or soffit using 2 M4 x 1 screws 10 Install electrical and duct work Seal duct work with aluminum duct tape 11 P...

Page 16: ...ters and air diverter plate Hood Model Part No Filters Brackets in Pkg VSU models VRC 00SU 2 VPL models VRC 00PL 2 VCR models VRC 00CR 2 1 Purchase recirculating kit per the part number above 2 Secure...

Page 17: ...15 1 3 3 Features Controls Mechanical Controls VSU...

Page 18: ...Speed Selection 2 Delay Off Timer 4 Blower On Off Press to turn blower on and off If lights are on they will also switch off when this button is pressed Press to cycle through light levels Bright Dim...

Page 19: ...n cloth and with the grain Do not use any product containing chlorine bleach Do not use orange cleaners Metal Mesh Filters The metal mesh filters installed by the factory are intended to filter out re...

Page 20: ...urning bulb counter clockwise Note Bulb does not unscrew it turns 60 degrees stops and falls out If bulbs are difficult to turn due to prolonged use firmly attach a glass suction cup approximately the...

Page 21: ...he switch board or control board is defective 4 Change defective part The unit is vibrating 1 The motor is not secured in place 1 Tighten the motor in place 2 Damaged blower wheel 2 Replace the blower...

Page 22: ...Accessories Recirculating Kit VRC 00SU for VSU VRC 00PL for VPL VRC 00CR for VCR Replacement Charcoal Filter each V0F C002 Extension Duct Cover V1C 00SU for VSU V1C 00PL for VPL V1C 00CR for VCR Orde...

Page 23: ...you are also responsible for all labor costs associated with this warranty Limitations of Warranty OUR OBLIGATION TO REPAIR OR REPLACE AT OUR OPTION SHALL BE YOUR SOLE AND EXCLUSIVE REMEDY UNDER THIS...

Reviews: