Safety and Warning Information
Speci
fi
cations
This appliance is intended for installation
into existing
masonry or factory-built, solid-fuel burning
fi replaces only.
Approvals and Codes
This appliance is certi
fi
ed to ANSI Z21.88-2009 /
CSA 2.33-2009 American National Standard / CSA
Standard for
Vented Gas Fireplace Heaters
for use in
Canada and the USA and to CGA 2.17-91
High Altitude
Standard in Canada
. This appliance is for direct vent
installation terminating at the roof only.
Model RF24IDN
is for use with Natural Gas only.
Model RF24IDP
is for use with LPG only.
Conversion between fuels may only be done using the
approved conversion kits listed in the section
Options
.
This appliance complies with CSA P4.1-09
Testing
method for measuring annual
fi
replace ef
fi
ciencies
.
The installation must conform to local codes or, in the
absence of local codes with the
National Fuel Gas
Code, ANSI Z223.1
or the
Canadian Installation Code
CAN/CGA-B149
. Only quali
fi
ed licensed or trained
personnel should install this appliance.
This appliance, when installed , must be electrically
grounded in accordance with local codes, or in the
absence of local codes, with the
National Electrical
Code, ANSI/NFPA 70
or the
Canadian Electrical Code,
CSA C22.1
Ratings
*High Altitude Installations
Input ratings are shown in BTU per hour and are
certi
fi
ed without deration for elevations up to 4,500 feet
(1,370 m) above sea level.
For elevations above 4,500 feet (1,370 m) in USA,
installations must be in accordance with the current
ANSI Z223.1 and/or local codes having jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370 m).
Operating Your Fireplace for the First Time
When operating your new
fi
replace for the
fi
rst time,
some vapors may be released due to the burning of
curing compounds used in the manufacture of the
appliance. They may cause a slight odor and could
cause the
fl
ames to be the full height of the
fi
rebox, or
even slightly higher, for the
fi
rst few hours of operation.
It is also possible that these vapors could set off any
smoke detection alarms in the immediate vicinity.
These vapors are quite normal on new appliances. We
recommend opening a window to vent the room. After
a few hours use, the vapors will have disappeared and
the
fl
ames will be at their normal height.
Model
NG
LPG
Gas
Natural
Propane
Altitude (Ft.)*
0-4,500 feet*
Input Maximum (Btu/h)
24,000
24,000
Input Minimum (Btu/h)
10,500
10,500
Manifold Pressure (in w.c.)
3.95
9.5
Minimum Supply Pressure (in w.c.)
5.0
11.0
Maximum Supply Pressure (in w.c.)
10.5
14.0
Main Burner Injector Marking
82-580
92-260
Pilot Injector Marking
51
30