Valor PORTRAIT 922ECN Installation & Operating Instructions Manual Download Page 7

77

Location & Clearances

This appliance must not be connected to a chimney 

flue serving a separate solid-fuel burning appliance.

Note: The State of Massachusetts requires that any 

flue damper must be removed or permanently welded 

in the open position.

The appliance can be installed in the 

following constructions:

Solid-fuel (non-combustible) fireplaces 

As supplied, this appliance can be installed as an insert 

in an existing solid fuel type fireplace with a chimney 

and 4” dia. liner.
The fireplace must be built in accordance with the 

national, state, provincial, or territorial building code 

recognised by the authority having jurisdiction, or in 

the absence of such a code, in accordance with the 

National Building Code of Canada or the National Fire 

Protection Association code in the USA. The size of the 

fireplace recess must be sufficient to accommodate the 

appliance as shown in figure below.
If previously used for burning solid-fuel, the chimney 

must be swept before installation of the appliance. Both 

chimney and fireplace must be checked for soundness 

Min vent liner Ht 9’-0”
Min Ht before 90 deg elbows

is 9’-0”. Radiused offsets in 

liner are permitted

Ceiling

ceiling

See

mantel

table

A

36” min.

to combust.

mat’l

B

Min. 39-1/2”

Center line

Edge of

protruding

arch

4-3/4”

Mantel depth A

1” & 2”

3”-8”

Clearance from 

base of heater B

40”

42-1/2”

before installation of the appliance. The liner must be a 

type approved by the enforcing authority and installed 

in accordance with the manufacturer’s instructions.
The appliance must be installed on a floor, which is 

sufficiently flat and level to ensure stability. Some 

fireplace constructions have a well in the floor at the 

back that may need to be filled in.
Though not mandatory, we recommend that carpet, 

soft vinyl or other combustible floor coverings are kept 

at least 16” from the front of the appliance since these 

types of materials may be affected by the radiant heat 

output from this appliance. 
The minimum clearances from any combustible 

constructions at the front of the appliance are shown 

below.

The appliance must be connected to a vent that is a 

minimum of 9’-0” in height and must not have any 

90 degrees elbows within 9’-0” of the flue outlet of 

the unit (see fig. below). Radiused offsets in the 

flue liner of less than 90 degrees are permitted.

Summary of Contents for PORTRAIT 922ECN

Page 1: ...itable for installation in a bedroom or bed sitting room Manufactured by MILeS INDUSTRIeS LTD British Columbia Canada www valorfireplaces com Installation Operating Instructions Do not store or use ga...

Page 2: ...and comfort Your unit has been professionally installed by Dealer Name _______________________________________ Phone Number ______________________________________ Should you encounter an operational p...

Page 3: ...paration 8 Gas Supply Installation 10 Firebox Installation insert application only 11 Remote Control Installation 12 Ceramic Fuel Bed Installation 13 923ACF Adorn Cast Front Installation 15 Adorn Safe...

Page 4: ...ways BE KEPT CLEAN to provide for adequate combustion and ventilation air Always KEEP the appliance clear and free from combustible materials gasoline and other flammable vapors and liquids NEVER OBST...

Page 5: ...ight odor and could cause the flames to be the full height of the firebox or even slightly higher for the first few hours of operation It is also possible that these vapors could set off any smoke det...

Page 6: ...36 wide closure plate with black aluminum extrusion edge is available For installation instructions with Adorn cast front see Adorn cast front installation section in this manual For Windsor Arch cast...

Page 7: ...soundness Min vent liner Ht 9 0 Min Ht before 90 deg elbows is 9 0 Radiused offsets in liner are permitted Ceiling ceiling See mantel table A 36 min to combust mat l B Min 39 1 2 Center line Edge of...

Page 8: ...nd of the burner Push in the lighting knob and turn counter clockwise through the IGN position to PILOT A spark should flash across from the pilot electrode to the pilot burner shield Aeration Setting...

Page 9: ...the burner module Remove 2 screws and pull the burner module partially out of the firebox taking care not to pull on the wire leads going to vent switch With the module partly removed reach behind the...

Page 10: ...re test the supply line for leaks The appliance and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in...

Page 11: ...Insert a wall plug into each hole 5 Secure the collar on the vent connector unit to the 4 diameter chimney liner 6 Slide the firebox into the fireplace making sure that the vent connection unit is abo...

Page 12: ...tor on to the receiver circuit board The plug will only go on one way so please ensure that the wires are pointing up and slot in the board is in line with the tab on the wiring harness plug Connect w...

Page 13: ...on top of the base coal support as shown 2 Insert the right hand sidewall at an approximate 30 degree angle between the firebox side and the burner Swing the top of the sidewall to the vertical positi...

Page 14: ...box The side projection on this coal should be near the middle front of the firebox 3 Place the right front coal behind the metal lip at the front of the firebox Its left side should rest over the pro...

Page 15: ...p locates fully over the retaining brackets on the convection box see figure below 1 Locate the guard bottom wires over the ash lip 2 Hold the top springs down and swing the guard back 3 Release the s...

Page 16: ...cause the flames to appear more yellow or orange making the fuel effects glow less Too little aeration may result in black carbon forming and dropping into the firebox Check venting efficiency A chec...

Page 17: ...ing a soft bristle paintbrush after removing the safety guard We suggest that you remove the coals in the reverse order to that shown in fitting instructions Make sure that no particles are brushed in...

Page 18: ...2 Set the flame adjustment knob as far clockwise as possible 3 Turn the gas control knob clockwise to OFF NOTE The knob cannot be turned from PILOT to OFF unless it is pushed in partially Do not force...

Page 19: ...on for air from other household equipment or appliances iii Damage due to chemicals dampness condensation or sulphur in the fuel supply lines which exceeds industry standards i This warranty does not...

Page 20: ...720A200 30 Pilot pipe 030A226 31 Tubing nut 420K385 32 Pilot injector olive 720A196 33a Pilot injector NG 35 4002511 33b Pilot injector LPG 27 720A195 Code Description Part no 34 Flexible pipe assy 4...

Page 21: ...21 Replacement Parts 922 BODY 1 2 3 8 4 5 6 7 9a b 10 11 12 13 14 16a 16b 16c 17a b 18 19 20 38 37 36 23 22 21 15a b 24 25A B 26 27 28 29 41 32 42 31 40 39 34 35 47 52 50 51 49 48 44 45 46 30 33A B 4...

Page 22: ...22 22 Replacement Parts 53 54 57 56 58 55 59 60 61 62 63 64 72 71 70 69 68 67 66 65...

Page 23: ...del 922EC NG natural gas LPG propane Serial No Front Trim code description e g 549AFB Windsor Arch Purchase date mm dd yyyy Home Owner Name Address City Province State Postal Code Zip Phone Email Addr...

Page 24: ...Product Postage needed Were you given all documentation and manuals for your product YES NO Miles Industries Ltd 190 2255 Dollarton Highway North Vancouver BC V7H 3B1 Canada Fold here Online Warranty...

Reviews: