23
Venting
Terminal
Cap
Flashing
2 x 3”
fl
ex
liners—see
Venting
Table for
length
allowed
Typical Vent Installation
See the
Approved Venting Components
list on page 39
of this manual.
Vent Location
The vent terminal must be located through the roof.
This direct vent appliance is designed to operate when
an undisturbed air
fl
ow hits the outside vent terminal
from any direction.
Check local codes for allowable vertical vent
termination.
Venting Table
Maximum
vertical height
40 ft (measured to bottom of termination)
Minimum
vertical height
10 ft (measured to bottom of termination)
Maximum
horizontal run
4 ft (measured center to center of pipe)
Maximum
offset angle
45
˚
(sweeping bend to allow for
obstructions)
Venting Notes
Where possible, avoid splicing
fl
ex pipes. If splices are
required, use a approved connector and seal joints with
RTV high temp sealant
.
Four feet horizontal is permissible to allow for routing
around masonry projections. Do not bend
fl
ex pipe over
a 45 degrees radius.
1. Co-linear venting may be converted to solid 4” x
6-5/8” co-axial venting at the top of the existing
solid-fuel burning chimney as necessary where
the existing chimney has deteriorated and
been removed. The conversion must be done
using approved components (see page 41) and
proper vent clearances to combustibles must be
maintained.
2. Three-inch liners may only be installed into solid-
fuel burning
fi
replaces and chimney systems (no
combustible construction).
3. The appliance must not be connected to a chimney
fl
ue serving a separate solid-fuel burning appliance.
Note
This appliance may also be vented using the following
optional methods (see installation instructions
packaged with optional kits):
• 720SWK—Co-linear sidewall kit
• 590FVK— 4-3/4” x 3” Co-axial Vent
Adapter with Flex Vent Kit for vertical venting in
existing solid-fuel burning chimneys.
3” Liners
3” min.
Bend
Radius
QUALIFIED
INSTALLER