VENT TERMINAL LOCATIONS - MINIMUM DISTANCES
MINIMUM CLEARANCE
See figure 3
Ins
cms
A
Clearance above grade, verandah, porch, deck or canopy
12
30
B
Clearance to window or door that may be opened
12
30
C
Clearance to permanently closed window (recommended to prevent
condensation on window)
12
30
D
Vertical distance to ventilated soffit located above the terminal within a
horizontal distance 2 feet (60cm)
18
46
E
Clearance to unventilated soffit
12
30
F
Clearance to outside corner
12
30
G
Clearance to inside corner
12
30
H
Horizontal clearance to center-line of meter/regulator assembly located
below the terminal
36
90
I
Clearance to service regulator vent outlet
72
180
J
Clearance to non-mechanical air supply inlet to the building or the
combustion air inlet to any other appliance
12
30
K
Clearance to a mechanical air supply inlet
72
180
L
Clearance above paved sidewalk or a paved driveway located on public
property.
Note:
A vent must not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and
serves both dwellings.
84
210
M
Clearance under a verandah, porch, deck or balcony
12
30
Note:
Local codes and regulations may require different clearances.
Fig.3 Vent terminal locations