Valor HORIZON 534JN Installation Manual Download Page 43

43

 Commonwealth of Massachusetts

State of Massachusetts Carbon Monoxide 

Detector/Vent Terminal Signage 

Requirements

For all side wall horizontally vented gas fueled 

equipment installed in every dwelling, building or 

structure used in whole or in part for residential 

purposes, including those owned or operated by the 

Commonwealth and where the side wall exhaust 

vent termination is less than seven (7) feet above 

fi

 nished grade in the area of the venting, including 

but not limited to decks and porches, the following 

requirements shall be satis

fi

 ed: 

1. INSTALLATION OF CARBON MONOXIDE DETECTORS. 

At the time of installation of the side wall horizontal 

vented gas fueled equipment, the installing plumber 

or gas 

fi

 tter shall observe that a hard wired carbon 

monoxide detector with an alarm and battery back-up 

is installed on the 

fl

 oor level where the gas equipment 

is to be installed. In addition, the installing plumber 

or gas 

fi

 tter shall observe that a battery operated 

or hard wired carbon monoxide detector with an 

alarm is installed on each additional level of the 

dwelling, building or structure served by the side wall 

horizontal vented gas fueled equipment. It shall be 

the responsibility of the property owner to secure 

the services of quali

fi

 ed licensed professionals for the 

installation of hard wired carbon monoxide detectors.

a. In the event that the side wall horizontally vented 

gas fueled equipment is installed in a crawl space or an 

attic, the hard wired carbon monoxide detector with 

alarm and battery back-up may be installed on the next 

adjacent 

fl

 oor level.

b. In the event that the requirements of this subdivision 

can not be met at the time of completion of installation, 

the owner shall have a period of thirty (30) days 

to comply with the above requirements; provided, 

however, that during said thirty (30) day period, a 

battery operated carbon monoxide detector with an 

alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS. Each 

carbon monoxide detector as required in accordance 

with the above provisions shall comply with NFPA 720 

and be ANSI/UL 2034 listed and IAS certi

fi

 ed. 

3. SIGNAGE. A metal or plastic identi

fi

 cation plate 

shall be permanently mounted to the exterior of the 

building at a minimum height of eight (8) feet above 

grade directly in line with the exhaust vent terminal for 

the horizontally vented gas fueled heating appliance or 

equipment. The sign shall read, in print size no less than 

one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. 

KEEP CLEAR OF ALL OBSTRUCTIONS”.

4. INSPECTION. The state or local gas inspector of the 

side wall horizontally vented gas fueled equipment shall 

not approve the installation unless, upon inspection, 

the inspector observes carbon monoxide detectors and 

signage installed in accordance with the provisions of 

248 CMR 5.08(2)(a)1 through 4. 

(b) EXEMPTIONS: The following equipment is exempt 

from 248 CMR 5.08(2)(a)1 through 4: 

1. The equipment listed in Chapter 10 entitled 

“Equipment Not Required To Be Vented” in the most 

current edition of NFPA 54 as adopted by the Board; 

and 

2. Product Approved side wall horizontally vented gas 

fueled equipment installed in a room or structure 

separate from the dwelling, building or structure used 

in whole or in part for residential purposes. 

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT 

VENTING SYSTEM PROVIDED. When the manufacturer 

of Product Approved side wall horizontally vented 

gas equipment provides a venting system design or 

venting system components with the equipment, 

the instructions provided by the manufacturer for 

installation of the equipment and the venting system 

shall include:

1. Detailed instructions for the installation of the 

venting system design or the venting system 

components; and

Summary of Contents for HORIZON 534JN

Page 1: ...iately Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be...

Page 2: ...All rights reserved Designed and manufactured for Miles Industries Ltd Valor Fireplaces 190 2255 Dollarton Highway North Vancouver BC Canada V7H 3B1 T 604 984 3496 F 604 984 0246 valorfireplaces com T...

Page 3: ...s 24 Restrictors 25 Installation 26 Appliance into Framing 26 Gas Supply 27 Liner Panels 28 Fuel Beds 29 Traditional Logs 534LSK 29 Ceramic Rocks 534RSK 31 Driftwood 534DWK 33 Refit Check Window 35 B...

Page 4: ...educed when barrier screen is installed Solid wood flooring in front of the fireplace if al lowed may shrink during the heating season due to heat Some materials or items although safe may discolor sh...

Page 5: ...t be vented directly to the outside and must never be attached to a chimney serving a separate solid fuel burning ap pliance Each gas appliance must use a separate vent system Common vent systems are...

Page 6: ...000 24 000 Input Minimum Btu h 6 500 13 000 Manifold Pressure in w c 3 95 10 Minimum Supply Pressure in w c 5 11 Maximum Supply Pressure in w c 10 14 Main Burner Injector Marking 82 650 92 260 Pilot I...

Page 7: ...4004875 672MBF Matt Black Front 4004666 673 Edgemont Door Fronts di erent colors 4005065 Gas Conversion Kits 534PGK Conversion to propane gas 534NGK Conversion to natural gas Other Accessories GV60CKO...

Page 8: ...of the appliance X Stand offs 7 180 mm From finished wall front to top vent Stand offs 4 1 2 114 mm 1 1 2 38 mm 16 406 mm 7 7 8 199 mm Mantle depth A 1 25 mm 2 51 mm 3 76 mm 4 5 102 127 mm 6 152 mm 7...

Page 9: ...stible material such as plywood and so on Vinyl carpet and soft flooring require sheet metal extending the whole width and depth under the appliance This appliance does not require a hearth Combustibl...

Page 10: ...ms packed inside and around it Recycle packaging 3 Check that you have everything required for the in stallation using the Pack Content sheet Also check that you have Fuel bed packed separately Liner...

Page 11: ...aterial other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance Flush Wall Finish Forward 534 recessed WARNING SAFETY WAR...

Page 12: ...appliance is installed directly on carpeting tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth o...

Page 13: ...oints either here or here Below are some tips on how to best avoid any cracking Allow materials to dry thoroughly before finishing the wall Some materials such as cement board has the ability to absor...

Page 14: ...tute to foil tape Ensure all the pipe joints have a minimum of 1 1 4 inch overlap Wall Thickness The appliance vent is suitable for penetrating a combustible wall assembly up to 14 inches in thickness...

Page 15: ...ALL THIMBLE PIPE LENGTH PIPE LENGTH PIPE LENGTH 817VAK 817VAK PIPE LENGTH 90 ELBOW CEILING FIRESTOP ATTIC FIRESTOP ATTIC INSULATION SHIELD FLASHING STORM COLLAR VERTICAL TERMINATION Venting Typical Co...

Page 16: ...er Prevent rain water and moisture from entering the walls by sealing the joints between the outer vent tube and the inner and outer wall plates We recommend the use of a high quality polyurethane sea...

Page 17: ...tal clearance to center line of meter regulator assembly located within 15 feet 4 6bm below the terminal 36 90 I Clearance to service regulator vent outlet 36 90 J Clearance to non mechanical air supp...

Page 18: ...for top or rear outlet Max 24 before elbow Min 12 rise 45 elbow directly on flue collar is allowed with min 6 pipe between elbows 1 min all around vertical pipe 3 min above top of horizontal pipe 1 m...

Page 19: ...t 3 Any combination of rise and run can be used as long as they are within the allowable limits shown on the chart below 4 A maximum of 4 x 90 degrees elbows or equivalent 2 x 45 degrees 90 degrees ca...

Page 20: ...liance vent opening Mark the position on the ceiling Drill a small hole at the marked position Determine the position where the vent will pass through the roof If directly above the position where it...

Page 21: ...also be used as an alternate to the 556CLA Only for use when retrofitting a sollid fuel burning fireplace and chimney The appliance must not be connected to a chimney flue serving a separate solid fue...

Page 22: ...ng Components 46DVA GCL 46DVA CLAA Co linear Terminal Configurations 559CLT Co linear Termination Co axial Terminal Cap Co linear to Co axial Adapter Flashing with Alternate Co linear to Co axial Conv...

Page 23: ...crews 4 Locate the inner collar and seal inside the rear outlet opening Secure the inner collar with 8 screws 5 Fit the outer collar over inner collar Loosely fit the 12 screws Place the adapter 817VA...

Page 24: ...angles to the front face of the heater case is adjustable between 3 8 inch and 1 3 16 inch to allow for a range of wall finish material thickness e g tile etc NOTE When adding optional fronts and tri...

Page 25: ...e one shown at right are supplied with each 534 engine unit The restrictors cover part of the inlet air openings in the firebox rear wall behind the rear log support DO NOT install the restrictors in...

Page 26: ...ary adjust the position of the heater so that the distance from the front of the heater case to the angles is suitable for the thickness of the wall finish e g tile etc Top angle adjustment from back...

Page 27: ...n to the appliance Pressure test the supply line for leaks The appliance and its individual shut o valve must be disconnected from the gas supply piping system during any pressure testing of that syst...

Page 28: ...behind the flange of the firebox Pull the panel as forward as possible against the left edge of the firebox 3 Hold the right hand side panel at an angle and insert its bottom edge inside the firebox...

Page 29: ...e of the log sits against the front edge of the sheet metal support 2 Place the top left log on the pin of the rear log The bottom of the log rests against the left of the pilot shield and slightly ab...

Page 30: ...ight log onto the pin on the front right log Rest the narrow end in the notch into the rear log 7 Pour some ceramic loose coals on each side of the logs to hide the sheet metal work DO NOT put any coa...

Page 31: ...latform in the firebox rotat ing down to insert the front first behind the front support Lay the back of the ceramic plat form against the rear ceramic panel again being careful not to scrape the cera...

Page 32: ...Note that the ceramic base may need to be slightly adjusted side to side to allow stones to fit within the platform 5 Place the glass panel in its cavity formed by the front support and the ceramic p...

Page 33: ...y the base log and place it in the cavity of the ceramic platform The protruding parts of the log in the front should rest against the lip of the sheet metal log support behind the burner 2 Identify t...

Page 34: ...Identify the left side cross log which has one pin at one end Insert the pin in the hole at the front left of the platform and rests the top part of the log into the notch of the rear log as indicated...

Page 35: ...nditions Damages caused by incorrect window installation is not covered by the Valor warranty Installation Refit Check Window Refit and Check Window 1 Place window over the firebox 2 While holding it...

Page 36: ...1 5 V high quality alkaline batteries in the battery holder and one high quality alkaline 9 V battery in the remote handset The battery holder and cable are supplied with the appliance 3 Connect the c...

Page 37: ...reset button until you hear one short an done long beeps Release the button after the second beep 4 Within the next 20 seconds press the small flame button on the handset until you hear two short beep...

Page 38: ...depending of the fuel bed used the altitude and other considerations the flame picture may be improved by adjusting the aeration The need for adjustment should be determined ony by operating the appl...

Page 39: ...to the wall To install the holder to the wall find a convenient location and use the hardware provided with the kit See the diagram below for required hardward and configurations Note that the holder...

Page 40: ...RESET Button PANEL red yellow Receiver red Interruptor Block Thermal Safety Switch IGNITOR Connector Optional 1265WSK Wall Switch Kit Combination Control Valve Antenna Main Valve Knob MAN Knob PILOT T...

Page 41: ...106433 Co linear to Co axial Adapter 46DVA GK 46DVA CLTA TM 4CTA 4DCAT33 DV to B Vent Adapter DVA5BV7 Aluminum Flexible Liner 3 or 4 diameter NOTE 2 ply liner approved to CAN ULC S635 suitable for ven...

Page 42: ...stem Parts Wall Thimble 46DVA WT 4DT WT TM 4WT SV4RSM 4DWT 949064U Storm Collar 46DVA SC 4DT SC TM SC SV4AC 4DSC 94960608 Decorative Plate 46DVA DC 4DT CS TM 4TR TM 4TP SV4PF 4DFPB 94940612 Cathedral...

Page 43: ...the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed 2 APPROVED CARBON MONOXIDE DETECTORS Each car...

Page 44: ...facturer 1 The referenced special venting system instructions shall be included with the appliance or equipment installation instructions and 2 The special venting systems shall be Product Approved by...

Page 45: ...QHDU WKH RRr If you smell gas STOP Follow B in the safety information above on this label If you don t smell gas go to the next step 3 AUTOMA7 1 7 21 J RFDWH WKH SLORW J LQVLGH RI UHER DW HIW DQG VLG...

Page 46: ...h modes and settings OFF returns to set mode turns the burner and WKH SLORW R DUJH DPH EXWWRQ DPHV up sets hours temperature 6PDOO DPH EXWWRQ DPHV GRZQ DQG R VHWV PLQXWHV temperature Current temperatu...

Page 47: ...stment TEMP Daytime Temperature Mode When pilot is lit room temperature is measured and compared to set temperature Flame height automatically adjusts to reach Daytime Set Temperature TEMP Night time...

Page 48: ...must be set in the following order during a 24 hour cycle P1 P1 P2 and P2 Day Time temperature high program period Night Time temperature low program period Default Settings Program 1 P1 06 00 am P1...

Page 49: ...matically extinguishes the pilot This feature helps the consumer realize cost bene ts by automatically eliminating energy consumption during non heating months and limited use The programmed length of...

Page 50: ...Pipe valve to pilot 030A226 32 Olive nut for pilot pipe 220K913 33 Pilot shield 4002203 34 Pilot support bracket 330A904 35 Pilot seal 620B995 36 Access plate 4001680 37 Pipe valve to main burner 300...

Page 51: ...No 6 4001826 76 Rock Base 4001792 77 LH Twig 4001827 78 RH Twig 4001828 79 Front Support Platform 4001998AH 80 Ceramic Platform 4001997 81 Glass Panel 4001836 82 Driftwood Kit 534DWK 83 Rear Log 40058...

Page 52: ...are Parts NG LPG 21 23 28 29 30 31 32 24 25 26 27 22 18 42 43 5 16 17 41 4 40 3 14 20 2 13 19 58 59 60 1 6 6 7 7 9 8 10 11 12 34 33 39 38 35 36 37 57 56 44 45 46 47 48 55 53 54 Gaz naturel Gaz propane...

Reviews: