INSTALLER’S GUIDE
Page 15
Figure 13. Fitting the foam seal
Figure 12. Flue restrictor
7.
The flue restrictor
This appliance is supplied with a flue restrictor for use
where the flue draught is excessive. The restrictor must
NOT be fitted where a precast flue or a flue liner is
used. For all other installations the restrictor should be
fitted. There may however, be certain exceptional
circumstances where fitting the restrictor causes the
fire to fail the spillage test. In such cases the restrictor
will have to be removed.
After removal conduct
the spillage check again.
The restrictor is supplied
loose and is fixed with
two screws. See figure
12.
8.
Fitting the Foam
seal
There is a length of self
adhesive foam seal
supplied with the fire.
This will need to be fitted
to the outer rear edges of
the side and top flanges
of the convection box.
Be careful not to stretch
the seal when measuring. Ensure that there is no gap between the foam seals where they
meet at the top flange (See figure 13).