background image

20

20

Gas Supply Installation

•  It’s preferable to rough-in the gas line at this point before proceeding with the 

fi

 rebox installation.

•  The appliance is supplied for supply gas connection at the control valve. Supply line connection to the control 

valve of the appliance is 3/8 inch NPT (female).
Take care not to apply torque to the valve. An isolating valve may be 

fi

 tted within the appliance case. Be aware 

that the supply pipe should follow routing to clear the remote receiver or optional fan.

•  Use only new black iron or steel pipes or copper tubing if acceptable—check local codes. 

Note that in USA, 

copper tubing must be internally tinned for protection against sulfur compounds.

•  Unions in gas lines should be of ground joint type.
•  The gas supply line must be sized and installed to provide a supply of gas suf

fi

 cient to meet the maximum 

demand of the appliance without undue loss of pressure.

•  Sealant used must be resistant to the action of all gas constituents including LP gas. Sealant should be applied 

lightly to male threads to ensure excess sealant does not enter gas lines.

•  The supply line should include a manual shut-off valve and union to allow the appliance to be disconnected for 

servicing.

•  Pressure test the supply line for leaks.

•  The appliance and its individual shut-off valve must be disconnected from the gas supply piping system 

during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5kPa).

•  The appliance must be isolated from the gas supply piping system by closing its individual manual shut-

off valve during any pressure testing of the gas supply piping system at test pressures equal to or less 
than 1/2 psig (3.5kPa).

•  Failure to either disconnect or isolate the appliance during pressure testing may result in regulator or valve 

damage. Consult your dealer in this case.

•  The minimum supply pressure is given in 

Speci

fi

 cations 

section of this manual.

•  All piping and connections must be tested for leaks after 

installation or servicing. All leaks must be corrected 
immediately.

•  When testing for leaks:

•  Make sure that the appliance is turned off.
•  Open the manual shut-off valve.
•  Test for leaks by applying a liquid detergent or soap 

solution to all joints. Bubbles forming indicate a gas 
leak. 

Never use an open fl ame to check for leaks

.

•  Correct any leak detected immediately.

•  The pressure test tapping locations are shown in 

fi

 gure 

above. A built-in non-adjustable regulator controls the 
burner manifold pressure. The correct pressure range 
is shown in the table in the 

Speci

fi

 cations 

section of 

this manual. The pressure check should be made with the burner alight and at its highest setting. See 

Lighting 

Instructions

 section for full operating details.

Supply 
pressure
test tapping

Manifold 
pressure
test tapping

Summary of Contents for 530ILN

Page 1: ...r market permanently located manufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This ap pliance is not conve...

Page 2: ...ould you encounter an operational problem call your dealer immediately Do not try to repair the unit as you may cause an injury or damage the fireplace The information contained in this installation m...

Page 3: ...r Restrictors Installation 19 Gas Supply Installation 20 Aeration Setting Check 21 Ceramic Walls Installation logs and coals only 21 Ceramic Logs Installation 22 Ceramic Coals Installation 23 Ceramic...

Page 4: ...OBSTRUCT the flow of combustion and ventilation air Keep the front of the appliance CLEAR of all obstacles and materials for servicing and proper operation Due to the high temperature the appliance s...

Page 5: ...ling building or structure served by the side wall horizontal vented gas fueled equipment It shall be the responsibility of the property owner to secure the services of qualified licensed professional...

Page 6: ...facturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases but identifies special venting systems the following requirement...

Page 7: ...t Max Btu h 20 500 19 000 Input Min Btu h 6 500 12 500 Manifold pressure in w c 3 5 3 9 10 3 10 7 Min Supply pressure in w c 5 11 Max Supply pressure in w c 10 5 14 Front Trims Various fronts are avai...

Page 8: ...atings table on the previous page The supply connection is 3 8 inch NPT female located at the left side of the control valve The opening for the gas supply line is at the rear left corner of the appli...

Page 9: ...clearance to center line of meter regulator assembly located within 15 feet 4 6 m below the terminal 36 90 I Clearance to service regulator vent outlet 36 90 J Clearance to non mechanical air supply i...

Page 10: ...of grade or where accessible In Corner No Vertical Rise Maximum 1 x 45 elbow allowed Maximum 18 horizontal pipe length 835TG Terminal Guard is required with 551DVK if terminating within 7 0 of grade o...

Page 11: ...red with 551DVK if terminating within 7 0 of grade or where accessible 14 36 cm max combustible wall Approved side wall termination Approved through wall shield thimble 530 engine Use 835TG vent guard...

Page 12: ...the drill does not penetrate the inner pipe Secure the vent unit or 817VAK to the outer collar with two no 6 thread cutting screws supplied Through the wall details If the wall has combustible materi...

Page 13: ...depending on the particular installation 1 5 16 33 mm min clearance to combustible materials all round 40 12 2 m max Total offset 4 6 137 cm max Ceiling firestop Roof flashing Approved vertical termi...

Page 14: ...no combustible construction The appliance must not be connected to a chimney flue serving a separate solid fuel burning appliance Flashing 2 x 3 liners 24 1 2 3 min bend radius Co linear adapter 2 x...

Page 15: ...r 2 Place the appliance in its proper location 3 Drop a plumb from the ceiling to the center of the appliance vent opening Mark the position on the ceiling Drill a small hole at the marked position 4...

Page 16: ...horizontal run as shown on page 14 in this manual 5 Fit the termination kit and flashing if required to the exterior of the chimney 6 Secure the appliance to the floor or wall if necessary Vertical T...

Page 17: ...r inner vent collar and seal by unscrewing 8 screws 4 To make sure that the collars are axially aligned fit the adapter 817VAK over the outer vent collar 5 Position the inner collar and seal verticall...

Page 18: ...the adapter to the outer collar with two no 6 thread cutting screws supplied Co linear Conversion using Valor 556CLA Co linear Adapter Note Instructions may vary as 556CLA may be installed on Top or...

Page 19: ...on is optimal for each type of installation To fit the restrictors loosen the two center screws of the left and right inlet ports Place the restrictor assembly under the screw heads and tighten the ce...

Page 20: ...hut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5kPa The appliance must be isolated from the g...

Page 21: ...en side For ceramic walls installation for 530IR engine see Ceramic Rocks Installation section in this manual At this point you can install the 567FGP Top Grille if used logs or rock version only sold...

Page 22: ...he base log 6 4 5 1 2 3 Burner SIDE VIEW Back Brick Burner bracket Rest the base log behind the burner on its bracket flange BASE LOG Firebox supports 1a 5 Locate the left side log on the ceramic pin...

Page 23: ...Place the right front coal behind the metal lip at the front of the firebox Its left side should rest over the projection on the left front coal 1 2 4 5 3 1a Burner SIDE VIEW Back Brick Burner bracket...

Page 24: ...rille sold separately fit it now See instructions supplied with the grille 3 Place the rear panel on the rear support as indicated Hold in place and go to next step 4 Place the left and then the right...

Page 25: ...e 4 Identify the rocks L and R Those rocks don t have any peg or hole Install those rocks as indicated at the left and right of the rock pile positioning them so that the arrows underneath point to th...

Page 26: ...es to bed in the window seal Remote Control Initial Set up The receiver and the handset of the remote control system must be initially synchronized before the first use 1 Insert alkaline batteries in...

Page 27: ...ation may result in black carbon forming and dropping into the firebox Packing Contents 1 Wall Bracket A 2 Screws B 1 Screw C 2 Wall Anchor D 1 Spacer E detach before assembly 1 Wall Bracket F Switch...

Page 28: ...ing loaded bolts securing the bottom of the window 3 Carefully lift the window Keep the window and bolts in a safe place To refit the window 1 Place the window centrally against the engine unit restin...

Page 29: ...ne to two seasons depending on usage Removing batteries in the off season will extend battery life Manual On Off Switch In cases where you want to turn off your fireplace and cannot do it with the rem...

Page 30: ...tor turns automatically to maximum flame height 1 Make sure that the MAN knob on the valve is in ON position 2 Make sure that the switch on the valve is in the I position 3 Press and hold the OFF and...

Page 31: ...pressing either the or buttons Mode Sun Moon TEMP Daytime temperature setting Nighttime temperature setting TIMER Start time setting Stop time setting Flame Height The flame height can be adjusted in...

Page 32: ...efore you get up P1 start time and to turn off when you leave for the day P1 stop time Then you can set your fireplace to turn on again at the end of the day P2 start time and to turn off when you go...

Page 33: ...is no transmission from the handset to the receiver within a 6 hour period the appliance will go to Standby pilot mode Handset Receiver Match The remote control handset and receiver are programmed to...

Page 34: ...QJ QHDU WKH RRr If you smell gas STOP Follow B in the safety information above on this label If you don t smell gas go to the next step 3 AUTOMA7 1 7 21 J RFDWH WKH SLORW J LQVLGH RI UHER DW HIW DQG V...

Page 35: ...35 35 Wiring Diagram Optional Wall Switch Kit 1265WSK Connector Red Yellow GV60 Wiring Diagram...

Page 36: ...36 Vent Adapters Couplers Universal Adapter 3 Flex Coupler 2150 TM CFAA3 Co linear Flex Connector 46DVA ADF Co axial to Co linear Adapter 46DVA GCL TM 4CAA 556CLA Co linear to Co axial Adapter 46DVA G...

Page 37: ...B SV4B Flat Roof Flashing 46DVA FF TF 4F SV4F 559FSK Masonry Flashing TF 4MF Various Venting System Parts Wall Thimble 46DVA WT 4DT WT TM 4WT SV4RSM Storm Collar 46DVA SC 4DT SC TM SC SV4AC Decorative...

Page 38: ...on for air from other household equipment or appliances iii Damage due to chemicals dampness condensation or sulphur in the fuel supply lines which exceeds industry standards i This warranty does not...

Page 39: ...K913 40 Window support 320B399 41 Switch bracket 4001070 41a Switch with cable 4001036 41b Cable interruptor receiver 4001035 42 Valve to main burner pipe connector 220K891 42a Interruptor block 40010...

Page 40: ...40 40 1 2 4 5 6 7 8 9 10 11 12 13 14 19 20 21 22 23 24 25 26 27 28 29 30 31 33 32 34 35 36 38 39 40 41 42 43 44 43a 45 46 47 48 42a 41a 41b NG LPG Replacement Parts 44a 37...

Page 41: ...41 41 50 51 52 53 54 55 56 57 58 59 60 61 62 49 Replacement Parts 63 64 65 66 68 72 70 73 71 74 75 76 77 78 79 80 69 67 For 530IRN P only For 530ILN P and ICN P...

Page 42: ...G natural gas LPG propane Serial No Fuel Bed Logs Rocks Coals Front code description e g 550CAP Classic Arch Purchase date mm dd yyyy Home Owner Name Address City Province State Postal Code Zip Phone...

Page 43: ...Product Postage needed Were you given all documentation and manuals for your product YES NO Miles Industries Ltd 190 2255 Dollarton Highway North Vancouver BC V7H 3B1 Canada Fold here Online Warranty...

Reviews: