Horizontal Termination Installations

•  The 530 heater may be installed using components from a variety of 

manufacturers listed on pages 36–37.

•  Allowable vent con

fi

 gurations and clearances for the 530 heater are listed in this 

manual and apply for all vent components listed on pages 36–37. For details of 
component installation, follow instructions packaged with each component.

•  The 530 heater is supplied with a smooth 4-by-6-5/8-inch co-axial collar 

intended to accept the Valor 551DVK Vent Termination with pipe attached. All 
other applications will require an 817VAK Vent Adapter to convert the collar to a 
twist-lock type collar. All other manufacturers’ components listed (including Valor 
551DVK) have designed their components to 

fi

 t this twist-lock type collar.

•  Do not mix components from different manufacturers.
•  Do not cut pipe lengths, except the 551DVK which may be cut to desired length. 

Use adjustable lengths otherwise.

Fix the Vent Unit or 817VAK to 
Appliance

•  Fit the vent unit or 817VAK over the 

inlet and outlet collars of the appliance, 
pushing on 

fi

 rmly. If using the 551DVK, 

ensure that the end of the pipe is cut 
cleanly and square. Rotate the pipe to 
ensure that the seam will pass through 
notch in the wall plates and that the drain 
hole is at the bottom.

•  Drill through the outer tube and the 

appliance collar with no. 6 screws. 

Make 

sure the drill does not penetrate the inner 
pipe

.

•  Secure the vent unit or 817VAK to the 

outer collar with two no. 6 thread-cutting 
screws supplied.

Through the wall details

•  If the wall has combustible material, 

appropriate insulation shielding or wall 
thimble must be used speci

fi

 c to the 

manufacturer of the venting. In any case, 
a minimum of 10 x 10 inches square 
or 10-inch diameter hole is required. If 
the wall is totally non-combustible (e.g. 
masonry block or concrete) mark for a 
7-inch circular hole. In both cases, the 
center of the hole should line up with the 
center line of the horizontal vent.

• See 

Horizontal Termination Locations

 

section for allowable vent terminal 
locations.

•  Avoid structural elements when locating 

the hole through the wall.

10” (254 mm)

10” (254 mm)

Align the 
vent center 
to the center 
of the frame

Important Installer Notice – Weather Sealing 
& Vapor Barriers

It is the installer’s responsibility to ensure that vent installations 
through exterior walls are caulked and weatherproofed in such a 
manner as to: 

•  Prevent rain water from entering the wall from the weather side 

by adequately caulking the outer vent plate to the exterior wall 
surface.

•  Prevent moisture inside the home from penetrating into the wall 

structure by ensuring the inside wall plate is adequately sealed to 
the inside vapor barrier.

•  Prevent rain water and moisture from entering the walls by 

sealing the joints between the outer vent tube and the inner and 
outer wall plates.

We recommend the use of a high quality polyurethane sealant.

551DVK Pipe or 
817VAK Vent Adapter

Summary of Contents for 530ILN

Page 1: ...r market permanently located manufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This ap pliance is not conve...

Page 2: ...ould you encounter an operational problem call your dealer immediately Do not try to repair the unit as you may cause an injury or damage the fireplace The information contained in this installation m...

Page 3: ...r Restrictors Installation 19 Gas Supply Installation 20 Aeration Setting Check 21 Ceramic Walls Installation logs and coals only 21 Ceramic Logs Installation 22 Ceramic Coals Installation 23 Ceramic...

Page 4: ...OBSTRUCT the flow of combustion and ventilation air Keep the front of the appliance CLEAR of all obstacles and materials for servicing and proper operation Due to the high temperature the appliance s...

Page 5: ...ling building or structure served by the side wall horizontal vented gas fueled equipment It shall be the responsibility of the property owner to secure the services of qualified licensed professional...

Page 6: ...facturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases but identifies special venting systems the following requirement...

Page 7: ...t Max Btu h 20 500 19 000 Input Min Btu h 6 500 12 500 Manifold pressure in w c 3 5 3 9 10 3 10 7 Min Supply pressure in w c 5 11 Max Supply pressure in w c 10 5 14 Front Trims Various fronts are avai...

Page 8: ...atings table on the previous page The supply connection is 3 8 inch NPT female located at the left side of the control valve The opening for the gas supply line is at the rear left corner of the appli...

Page 9: ...clearance to center line of meter regulator assembly located within 15 feet 4 6 m below the terminal 36 90 I Clearance to service regulator vent outlet 36 90 J Clearance to non mechanical air supply i...

Page 10: ...of grade or where accessible In Corner No Vertical Rise Maximum 1 x 45 elbow allowed Maximum 18 horizontal pipe length 835TG Terminal Guard is required with 551DVK if terminating within 7 0 of grade o...

Page 11: ...red with 551DVK if terminating within 7 0 of grade or where accessible 14 36 cm max combustible wall Approved side wall termination Approved through wall shield thimble 530 engine Use 835TG vent guard...

Page 12: ...the drill does not penetrate the inner pipe Secure the vent unit or 817VAK to the outer collar with two no 6 thread cutting screws supplied Through the wall details If the wall has combustible materi...

Page 13: ...depending on the particular installation 1 5 16 33 mm min clearance to combustible materials all round 40 12 2 m max Total offset 4 6 137 cm max Ceiling firestop Roof flashing Approved vertical termi...

Page 14: ...no combustible construction The appliance must not be connected to a chimney flue serving a separate solid fuel burning appliance Flashing 2 x 3 liners 24 1 2 3 min bend radius Co linear adapter 2 x...

Page 15: ...r 2 Place the appliance in its proper location 3 Drop a plumb from the ceiling to the center of the appliance vent opening Mark the position on the ceiling Drill a small hole at the marked position 4...

Page 16: ...horizontal run as shown on page 14 in this manual 5 Fit the termination kit and flashing if required to the exterior of the chimney 6 Secure the appliance to the floor or wall if necessary Vertical T...

Page 17: ...r inner vent collar and seal by unscrewing 8 screws 4 To make sure that the collars are axially aligned fit the adapter 817VAK over the outer vent collar 5 Position the inner collar and seal verticall...

Page 18: ...the adapter to the outer collar with two no 6 thread cutting screws supplied Co linear Conversion using Valor 556CLA Co linear Adapter Note Instructions may vary as 556CLA may be installed on Top or...

Page 19: ...on is optimal for each type of installation To fit the restrictors loosen the two center screws of the left and right inlet ports Place the restrictor assembly under the screw heads and tighten the ce...

Page 20: ...hut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5kPa The appliance must be isolated from the g...

Page 21: ...en side For ceramic walls installation for 530IR engine see Ceramic Rocks Installation section in this manual At this point you can install the 567FGP Top Grille if used logs or rock version only sold...

Page 22: ...he base log 6 4 5 1 2 3 Burner SIDE VIEW Back Brick Burner bracket Rest the base log behind the burner on its bracket flange BASE LOG Firebox supports 1a 5 Locate the left side log on the ceramic pin...

Page 23: ...Place the right front coal behind the metal lip at the front of the firebox Its left side should rest over the projection on the left front coal 1 2 4 5 3 1a Burner SIDE VIEW Back Brick Burner bracket...

Page 24: ...rille sold separately fit it now See instructions supplied with the grille 3 Place the rear panel on the rear support as indicated Hold in place and go to next step 4 Place the left and then the right...

Page 25: ...e 4 Identify the rocks L and R Those rocks don t have any peg or hole Install those rocks as indicated at the left and right of the rock pile positioning them so that the arrows underneath point to th...

Page 26: ...es to bed in the window seal Remote Control Initial Set up The receiver and the handset of the remote control system must be initially synchronized before the first use 1 Insert alkaline batteries in...

Page 27: ...ation may result in black carbon forming and dropping into the firebox Packing Contents 1 Wall Bracket A 2 Screws B 1 Screw C 2 Wall Anchor D 1 Spacer E detach before assembly 1 Wall Bracket F Switch...

Page 28: ...ing loaded bolts securing the bottom of the window 3 Carefully lift the window Keep the window and bolts in a safe place To refit the window 1 Place the window centrally against the engine unit restin...

Page 29: ...ne to two seasons depending on usage Removing batteries in the off season will extend battery life Manual On Off Switch In cases where you want to turn off your fireplace and cannot do it with the rem...

Page 30: ...tor turns automatically to maximum flame height 1 Make sure that the MAN knob on the valve is in ON position 2 Make sure that the switch on the valve is in the I position 3 Press and hold the OFF and...

Page 31: ...pressing either the or buttons Mode Sun Moon TEMP Daytime temperature setting Nighttime temperature setting TIMER Start time setting Stop time setting Flame Height The flame height can be adjusted in...

Page 32: ...efore you get up P1 start time and to turn off when you leave for the day P1 stop time Then you can set your fireplace to turn on again at the end of the day P2 start time and to turn off when you go...

Page 33: ...is no transmission from the handset to the receiver within a 6 hour period the appliance will go to Standby pilot mode Handset Receiver Match The remote control handset and receiver are programmed to...

Page 34: ...QJ QHDU WKH RRr If you smell gas STOP Follow B in the safety information above on this label If you don t smell gas go to the next step 3 AUTOMA7 1 7 21 J RFDWH WKH SLORW J LQVLGH RI UHER DW HIW DQG V...

Page 35: ...35 35 Wiring Diagram Optional Wall Switch Kit 1265WSK Connector Red Yellow GV60 Wiring Diagram...

Page 36: ...36 Vent Adapters Couplers Universal Adapter 3 Flex Coupler 2150 TM CFAA3 Co linear Flex Connector 46DVA ADF Co axial to Co linear Adapter 46DVA GCL TM 4CAA 556CLA Co linear to Co axial Adapter 46DVA G...

Page 37: ...B SV4B Flat Roof Flashing 46DVA FF TF 4F SV4F 559FSK Masonry Flashing TF 4MF Various Venting System Parts Wall Thimble 46DVA WT 4DT WT TM 4WT SV4RSM Storm Collar 46DVA SC 4DT SC TM SC SV4AC Decorative...

Page 38: ...on for air from other household equipment or appliances iii Damage due to chemicals dampness condensation or sulphur in the fuel supply lines which exceeds industry standards i This warranty does not...

Page 39: ...K913 40 Window support 320B399 41 Switch bracket 4001070 41a Switch with cable 4001036 41b Cable interruptor receiver 4001035 42 Valve to main burner pipe connector 220K891 42a Interruptor block 40010...

Page 40: ...40 40 1 2 4 5 6 7 8 9 10 11 12 13 14 19 20 21 22 23 24 25 26 27 28 29 30 31 33 32 34 35 36 38 39 40 41 42 43 44 43a 45 46 47 48 42a 41a 41b NG LPG Replacement Parts 44a 37...

Page 41: ...41 41 50 51 52 53 54 55 56 57 58 59 60 61 62 49 Replacement Parts 63 64 65 66 68 72 70 73 71 74 75 76 77 78 79 80 69 67 For 530IRN P only For 530ILN P and ICN P...

Page 42: ...G natural gas LPG propane Serial No Fuel Bed Logs Rocks Coals Front code description e g 550CAP Classic Arch Purchase date mm dd yyyy Home Owner Name Address City Province State Postal Code Zip Phone...

Page 43: ...Product Postage needed Were you given all documentation and manuals for your product YES NO Miles Industries Ltd 190 2255 Dollarton Highway North Vancouver BC V7H 3B1 Canada Fold here Online Warranty...

Reviews: