Clearing the Recipe
If you wish to empty the recipe, go to Recipe menu and
press 2 (Clear Recipe). The following display appears.
Clear recipe: 1
Press the Edit button and use the up and down arrow
buttons to select the desired recipe. Press the Save
button, after which the program asks you to confirm
your selection.
T h i s
a c t i o n
w i l l
c l e a r
r e c i p e
1
E N T E R = C l e a r
E S C = C a n c e l
Press Enter to clear the recipe.
Note: You cannot empty the recipe that is currently in
use.
Selecting the Recipe with Binary Inputs
The recipe can be selected using two digital control
lines connected to the TCU connector casing. In this
case, you can use up to four recipes. If only one binary
input is in use, you can use two recipes.
Select ‘Binary’ as the recipe selection method accord-
ing to the instructions in section Using Recipes.
S e l e c t :
B I N
1 . R E C 0 1 - - - 1 5 0 4 0 5
O N
2 . R E C 0 2 - - - 2 2 0 4 0 5
3 . - - - - - - - - 0 0 0 0 0 0
4 . - - - - - - - - 0 0 0 0 0 0
Connect e.g. the automation system’s digital control
lines to the connector casing binary inputs BIN0 and
BIN1. Connect the grounded line to BINGND. Select
the recipe with the digital control lines according to the
following table. The text ‘ON’ next to the recipe number
indicates which recipe is selected.
BIN0 BIN1 Recipe
0
0
1
1
0
2
0
1
3
1
1
4
Installation & Owner’s manual OUL00298 V2.3 EN
40
Valmet Mircowave Consistency Transmitter
Summary of Contents for Valmet MCA
Page 2: ......
Page 4: ...Installation Owner s manual OUL00298 V2 3 EN 4 Valmet Mircowave Consistency Transmitter...
Page 8: ...Notes Installation Owner s manual OUL00298 V2 3 EN 8 Valmet Mircowave Consistency Transmitter...
Page 24: ...Notes Installation Owner s manual OUL00298 V2 3 EN 24 Valmet Mircowave Consistency Transmitter...
Page 32: ...Notes Installation Owner s manual OUL00298 V2 3 EN 32 Valmet Mircowave Consistency Transmitter...
Page 34: ...Notes Installation Owner s manual OUL00298 V2 3 EN 34 Valmet Mircowave Consistency Transmitter...
Page 44: ...Notes Installation Owner s manual OUL00298 V2 3 EN 44 Valmet Mircowave Consistency Transmitter...
Page 58: ...Notes Installation Owner s manual OUL00298 V2 3 EN 58 Valmet Mircowave Consistency Transmitter...
Page 60: ......