Binary inputs
The TCU contains two galvanically isolated binary in-
puts, BIN 0 (connection 12) and BIN 1 (connection 13),
both inputs share a common ground (connector 11).
The switching device must be able to supply 12–28
VDC / 10 mA to the binary input. The connection prin-
ciple of binary inputs is shown in Fig. 9.
BINGND (11)
BIN0
(12)
BIN1
(13)
Fig. 9. Connection principle of binary inputs.
Table 1. BIN1 configured for process running status.
BIN0
BIN1
open
open
recipe 1 selected
Process Stopped
closed open
recipe 2 selected
Process Stopped
open
closed
recipe 1 selected
Process running
closed closed
recipe 2 selected
Process running
Table 2. BIN1 configured for recipe selection.
BIN0
BIN1
open
open
recipe 1 selected
closed open
recipe 2 selected
open
closed
recipe 3 selected
closed closed
recipe 4 selected
Installation & Owner's manual, OUL00489 V2.3 EN
16
Valmet Total Solids Transmitter