13
© Vallox Oy - All rights reserved
A
B
C
D
E
0
20
40
60
80
100
120
0
10
20
30
40
50
60
70
100 %
20 %
30 %
10 %
80 %
70 %
60 %
50 %
40 %
36
72
108
0
144
180
216
252
dm³/s
(l/s)
m³/h
Volume flow rate
Power (W)
Measurement points after the outlet collar. The fan curves indicate
the total pressure accounted for by duct losses.
FAN INPUT POWER
AIR FLOW MEASUREMENT POINTS
A Supply air
B Extract air
C Left side
D View from
above
E Right side
0
50
100
150
200
250
300
0
10
20
30
40
50
60
70
SFP 1,5
100 %
80 %
70 %
60 %
50 %
40 %
30 %
20 %
10 %
SFP 1,8
SFP 1,0
L
0
36
72
108
144
180
216
252
m³/h
(l/s)
dm³/s
AIR VOLUMES VALLOX TSK MULTI 50 MV, SUPPLY AIR (FINE+COARSE), EXTRACT AIR (COARSE)
Input power (total) (W)
Air flow (max) (dm3/s)
SFP =
SFP rate (Specific Fan Power)
recommended value <1.8 (kW m3/s)
PK and TK are examples of
pressure loss in the extract and
supply air ducts.
extract air
supply air
TECHNIC
AL SPECIFIC
ATIONS
TECHNICAL SPECIFICATIONS
AIR FLOWS AND SOUND VALUES
Pressure loss in ducts. Total pressure (Pa)
Volume flow rate
(dm
3
/s)
TECHNICAL SPECIFICATIONS
Product title
Vallox TSK Multi 50 MV R
Vallox TSK Multi 50 MV L
Product number
3520700
3520800
Air volumes
Supply air
Extract air
47 dm
3
/s, 100 Pa
56 dm
3
/s, 100 Pa
Fans
Supply air
Extract air
0,043 kW 0,32 A EC
0,043 kW 0,32 A EC
Post-heating
Electrical resistor, 900 W
Electrical connection
230 V, 50 Hz, 4,5 A power plug
Pre-heating
–
Enclosure protection class
IP 34
Additional heating
–
Heat recovery bypass
Automatic
Filters
Supply air
Extract air
ISO Coarse > 75 % + ISO ePM₁
ISO Coarse > 75 %
Specific energy consumption (SEC)
in a cold climate
in a temperate climate
A+
B
Operating efficiencies
Annual efficiency
Supply air efficiency
Specific Fan Power (SFP)
75 % A+
85 %
1.2 kW (25 dm
3
/s) B
Dimensions
(w x h x d)
900 x 236 x 547 mm
Weight
45 kg
Summary of Contents for TSK Multi Series
Page 22: ...CONFORMITY CERTIFICATES...
Page 23: ......