background image

6

 

MAINTENANCE

E

F

D

Location of the condensing 

water outlet seen  

from the side

Location of the 

condensing water outlet 

seen from the rear

CONDENSING WATER

In the heating season, the extract air humidity condenses 

to water. In new buildings, condensation runoff can form 

rapidly. Condensed water must be able to freely leave the 

unit. At some time before the heating season begins (e.g. 

during autumn maintenance), check that the condensing 

water outlets in the bottom pool are not clogged. To check 

this, pour some water into the pool. Clean as required. 

Water must at all times be kept out of the electrical system.
See the condensing water connections on page 15.

HEAT RECOVERY CELL

Check that the heat recovery cell (D) is clean roughly 

once a year when the filters are being replaced. Clean by 

washing as required. 

•  Pull the coarse filters including the frames out of the 

unit (A and C). Also remove the fine filter, if any (C).

•  Remove the sealing strip (E) above the heat recovery 

cell in the direction of the arrow. 

•  Once you have removed the sealing strip, pull the 

heat recovery cell out of the unit.

IMPORTANT! Handle the cell carefully! For example, do 

not lift the cells by the layers. The cell layers are very thin 

and easily damaged.

If the heat recovery cell is dirty, clean it by immersing it in 

water containing a small amount of a mild detergent. Rinse 

the heat recovery cell clean with a water spray. When all 

the water has drained from between the layers, push the 

cell recovery cell back in place. Lastly, push the sealing 

strip back in place.

Summary of Contents for TSK Multi 80 MC R

Page 1: ...Manual MANUAL Low energy ventilation unit with heat recovery Document D2585 Valid from 15 1 2018 Updated 29 1 2018 Model TSK Multi 50 MC TSK Multi 80 MC Types 3603 3602...

Page 2: ...upply and extract air ratio Adjusting the supply air temperature and summer winter function Vallox Simple Control control panel ordered separately 1 2 3 14 15 4 5 6 7 8 9 10 11 12 13 R model in the fi...

Page 3: ...post heating is turned off and the heat recovery cell is bypassed when the outdoor temperature is above 14 C The heat recovery will be turned on when the outdoor temperature falls below 12 C In the AU...

Page 4: ...r is turned clockwise the extract air flow is reduced The potentiometer for adjusting the supply and extract air flows Concealed installation of the fireplace switch optional MAINTENANCE REMINDER If a...

Page 5: ...on unit maintenance FILTERS When the maintenance reminder becomes activated check the cleanliness of the filters and replace them if required The Vallox ventilation unit has three air filters Class G4...

Page 6: ...OVERY CELL Check that the heat recovery cell D is clean roughly once a year when the filters are being replaced Clean by washing as required Pull the coarse filters including the frames out of the uni...

Page 7: ...ass duct filter stand package out of the unit and turn to the right 3 Disconnect the cable of the bypass damper motor 4 Tilt the supply air fan to the right and push the connectors out of the way 5 Tu...

Page 8: ...rotection class IP34 Post heating radiator Electric 900W Preheating radiator Additional heating radiator Fans Supply air Extract air 0 043 kW 0 32 A EC 0 043 kW 0 32 A EC Specific energy consumption S...

Page 9: ...sition V Air flow dm3 s Adjustment position V 3 4 5 6 7 8 9 10 11 4 3 4 5 6 7 8 9 10 11 4 Air flow dm3 s 8 1 13 8 18 8 25 1 31 3 38 7 43 9 50 4 54 6 13 7 19 1 26 2 32 1 37 9 45 50 3 56 9 62 8 Medium f...

Page 10: ...ting radiator Electric 900W Fans Supply air Extract air 0 071kW 0 5 A EC 0 071kW 0 5 A EC Specific energy consumption SEC in a cold climate in a temperate climate A B Operating efficiencies Annual eff...

Page 11: ...Adjustment position V Air flow dm3 s Adjustment position V 3 4 5 6 7 8 9 10 11 3 3 4 5 6 7 8 9 10 11 3 Air flow dm3 s 15 6 23 1 31 6 39 6 47 9 57 7 65 7 75 2 83 8 22 3 33 1 43 3 50 3 59 3 71 2 81 3 92...

Page 12: ...hood Cables BK black BN brown BU blue GN green GY grey WT white YE GN yellow green RD red 951155 951123 951153 951159 BU 1 BN 2 YEGN 9 951150 951152 BN 7 W T 8 GN 15 YE 16 RD 7 W T 8 BU 15 YE 16 BK 1...

Page 13: ...inal connector GND S GND S MC VENTILATION UNIT Four terminal connector MV VENTILATION UNIT GND AN I RM I RM O E I LED E O PROGRAMMING CONNECTORS OF THE MOTHERBOARD CONTACT DATA GUARD FUNCTION NORMAL S...

Page 14: ...RS 485 Common RH optional 946147 Nomak 2x2x0 5 0 5 0 10V LED G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A B C S DI2 G0 Vallox Procontrol 949034 S LED S B term CONFIG Control signal S Cooker hood or boost switch 11...

Page 15: ...ot cause any disturbance Such locations include storage premises and technical spaces Important The whole length of the outdoor air duct to the unit and exhaust air duct from the unit must be insulate...

Page 16: ...ulti 80 MC 942211 13 Side sealing strip of the heat recovery cell 3356300 Vallox TSK Multi 50 MC 13 Side sealing strip of the heat recovery cell 3352600 Vallox TSK Multi 80 MC NO Part Product number 1...

Reviews: