Mounting

The Vallox TSK Multi 50/80 MC is normally installed on the 

ceiling using the four mounting hooks delivered with the unit. 

The weight of the unit (45 kg) must be taken into account when 
mounting the unit.

Wall structure

The wall structure must be observed in the mounting. 

Avoid mounting the unit on hollow, echoing intermediate 

walls and on bedroom walls, or take measures to prevent 

conduction of noise.

INSTALLATION SITE

Vallox TSK Multi 50/80 MC must be installed in a location 

where the temperature remains above +10 °C. When the 

unit is installed without a protective enclosure, the location 

must be chosen so that its noise does not cause any 

disturbance. Such locations include storage premises and 

technical spaces.

Important! The whole length of the outdoor air duct to the unit 

and exhaust air duct from the unit must be insulated using 

closed cell insulation.

CONDENSING WATER

The delivery includes a water seal and an elbow for connecting the pipe that leads the water condensed from the extract air to the 

floor drain (not directly into the sewer). The pipe must not rise after the water seal. See the accessory bag for further instructions 

on the installation of the water seal and the elbow.

DIMENSION TSK Multi 50  

mm

TSK Multi 80 

mm

A

431

519

B

91

91

C

16

16

D

548

626

E

530

600

F

236

293

G

935

1060

H

900

1026

F

Water seal

Water outlet 

(alternative)

54

Plug cord and cord 

for SC speed switch 

Space required 

for mounting

H

A

L

I

T

O

T

L

O

U

H

G

E

D

B

A

C

61

43

27

47

SPACE FOR 

MAINTENANCE

SPACE FOR 

MAINTENANCE

Summary of Contents for TSK Multi 80 MC R

Page 1: ...Manual MANUAL Low energy ventilation unit with heat recovery Document D2585 Valid from 15 1 2018 Updated 29 1 2018 Model TSK Multi 50 MC TSK Multi 80 MC Types 3603 3602...

Page 2: ...upply and extract air ratio Adjusting the supply air temperature and summer winter function Vallox Simple Control control panel ordered separately 1 2 3 14 15 4 5 6 7 8 9 10 11 12 13 R model in the fi...

Page 3: ...post heating is turned off and the heat recovery cell is bypassed when the outdoor temperature is above 14 C The heat recovery will be turned on when the outdoor temperature falls below 12 C In the AU...

Page 4: ...r is turned clockwise the extract air flow is reduced The potentiometer for adjusting the supply and extract air flows Concealed installation of the fireplace switch optional MAINTENANCE REMINDER If a...

Page 5: ...on unit maintenance FILTERS When the maintenance reminder becomes activated check the cleanliness of the filters and replace them if required The Vallox ventilation unit has three air filters Class G4...

Page 6: ...OVERY CELL Check that the heat recovery cell D is clean roughly once a year when the filters are being replaced Clean by washing as required Pull the coarse filters including the frames out of the uni...

Page 7: ...ass duct filter stand package out of the unit and turn to the right 3 Disconnect the cable of the bypass damper motor 4 Tilt the supply air fan to the right and push the connectors out of the way 5 Tu...

Page 8: ...rotection class IP34 Post heating radiator Electric 900W Preheating radiator Additional heating radiator Fans Supply air Extract air 0 043 kW 0 32 A EC 0 043 kW 0 32 A EC Specific energy consumption S...

Page 9: ...sition V Air flow dm3 s Adjustment position V 3 4 5 6 7 8 9 10 11 4 3 4 5 6 7 8 9 10 11 4 Air flow dm3 s 8 1 13 8 18 8 25 1 31 3 38 7 43 9 50 4 54 6 13 7 19 1 26 2 32 1 37 9 45 50 3 56 9 62 8 Medium f...

Page 10: ...ting radiator Electric 900W Fans Supply air Extract air 0 071kW 0 5 A EC 0 071kW 0 5 A EC Specific energy consumption SEC in a cold climate in a temperate climate A B Operating efficiencies Annual eff...

Page 11: ...Adjustment position V Air flow dm3 s Adjustment position V 3 4 5 6 7 8 9 10 11 3 3 4 5 6 7 8 9 10 11 3 Air flow dm3 s 15 6 23 1 31 6 39 6 47 9 57 7 65 7 75 2 83 8 22 3 33 1 43 3 50 3 59 3 71 2 81 3 92...

Page 12: ...hood Cables BK black BN brown BU blue GN green GY grey WT white YE GN yellow green RD red 951155 951123 951153 951159 BU 1 BN 2 YEGN 9 951150 951152 BN 7 W T 8 GN 15 YE 16 RD 7 W T 8 BU 15 YE 16 BK 1...

Page 13: ...inal connector GND S GND S MC VENTILATION UNIT Four terminal connector MV VENTILATION UNIT GND AN I RM I RM O E I LED E O PROGRAMMING CONNECTORS OF THE MOTHERBOARD CONTACT DATA GUARD FUNCTION NORMAL S...

Page 14: ...RS 485 Common RH optional 946147 Nomak 2x2x0 5 0 5 0 10V LED G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A B C S DI2 G0 Vallox Procontrol 949034 S LED S B term CONFIG Control signal S Cooker hood or boost switch 11...

Page 15: ...ot cause any disturbance Such locations include storage premises and technical spaces Important The whole length of the outdoor air duct to the unit and exhaust air duct from the unit must be insulate...

Page 16: ...ulti 80 MC 942211 13 Side sealing strip of the heat recovery cell 3356300 Vallox TSK Multi 50 MC 13 Side sealing strip of the heat recovery cell 3352600 Vallox TSK Multi 80 MC NO Part Product number 1...

Reviews: