background image

VALLOX DIGIT SE / VKL

VALLOX DIGIT SE VKL part list

Voltage values for each fan speed:

0

0.20...1.25 VDC

1

1.75...2.25 VDC

2

2.75...3.25 VDC

3

3.75...4.25 VDC

4

4.75...5.25 VDC

5

5.75...6.25

VDC

6

6.75...7.25 VDC

7

7.75...8.25 VDC

8

8.75...10.00 VDC

Current values for each fan speed:

0

0.5...2.5 mA

1

3.5...4.5 mA

2

5.5...6.5

 mA

3

7.5...8.5 mA

4

9.5...10.5 mA

5

11.5...12.5 mA

6

13.5...14.5 mA

7

15.5..16.5 mA

8

17.5...20.0 mA

Voltage and current signal values (selection in the motherboard)

Control of operation

Power supply to the unit can be controlled with a contactor in the distribution
panel if needed, e.g. with a timer programme. After starting, the unit first
operates at basic fan speed. After that power is adjusted based either on the
measurement data from air quality sensors and/or on manual control at the
control panel.

Fan speed adjustment

Manual control

Fan speed of the ventilation unit is controlled in 8 steps at control panel 

H

.

Week clock control

Fan speed of the ventilation unit is controlled in 8 steps using the week clock

in control panel 

H

. The week clock can be used to programme the desired fan

power option and the setpoint for supply air temperature for each day of the

week and each hour in the day.

Carbon dioxide and humidity control

The fan capacity of the ventilation unit is controlled in multiple steps
depending on loads, and based on the measurement results of the air quality
sensors (CO

2

 and %RH sensors) located in the ventilation zone. The aim is to

keep carbon dioxide and/or humidity content below the threshold set at
control panel 

H

. You may also choose automatic search for thehumidity

content threshold on the control panel 

H

. One or more modes of control may

be used simultaneously - the mode demanding boosting is the dominant one.
Fan speed varies depending on load between the basic and maximum fan
speeds. The basic and maximum fan speeds can be set at the desired level at
the control panel 

H

.

Control through voltage or current signal

The fan power of the ventilation unit is controlled in 8 steps with a voltage
signal of 0...10 VDC, or with a current signal of 0...20 mA. However, fan
power cannot be raised above the set maximum fan speed. Voltage or
current signal control is used to control basic fan speed. Because of this, fan
speed can only be raised when necessary, but not lowered by the manual,
CO

2

 and %RH controls.

15

DESCRIPTION OF OPERATION DIGIT SE VKL, water radiator

Supply air temperature

Supply air temperature can be controlled using either constant temperature
adjustment or cascade adjustment.

Supply air constant temperature control

The control unit directs the operation of the control valve 

SV

 on the basis ofthe

measuring data on the temperature sensor 

TE2

. The aim is to keepsupply air

temperature at the temperature value set on the control panel H

(+10...+30

°

C).

Supply air cascade control

The control unit directs the operation of the control valve 

SV

 on the basis ofthe

measuring data on the extract air sensor 

TE4

. The aim is to keepextract air

temperature at the temperature value set on the control panel 

H

 (+10...+30

°

C).

Heat recovery bypass

When post-heating has been switched on, heat recovery is enabled all

thetime. Automatic heat recovery bypass is active whenever post-heating

hasbeen switched off and outdoor temperature exceeds the preset

threshold(range 0…+25

°

C). In this case, the control unit directs the operation

ofthe damper motor 

FG

 on the basis of measuring results given by theoutdoor

sensor 

TE3

 and the extract air temperature sensor 

TE4

. The aim isto get as cool

supply air to the ventilation zone as possible. The indicationof a freezing risk

appears in the display of the control panel. Heatrecovery is, however, on

whenever outdoor temperature is below the limitset, or whenever outdoor air is

warmer than extract air.

Heat recovery anti-freezing

Active when outdoor temperature is below 0

°

C. The control/adjustment center

of the unit directs the operation of the preheater 

LP1

 on the basis of the

measurement data supplied by the temperature sensors 

TE1

 and 

TE3

. The aim is

to prevent the risk of freezing and the stopping of the supply air fan 

TF

. If the

capacity of the preheater 

LP1

 is not sufficient, or if there is no preheater, the

control center intermittently stops the 

TF

 supply air fan on the basis of the

measuring data on the temperature sensors 

TE1

 and 

TE3

, thereby preventing

the heat recovery cell from freezing. As soon as the risk of frosting passes,

the fan restarts automatically. The threshold temperature for defrosting (-

6…+15

°

C) and the difference area (+1…+10

°

C) can be set on the control

panel 

H

. When the fan 

TF

 stops, power supply to the 

LP1

 radiator stops and

the actuator valve 

V1

 of the 

LP2

 post-heating radiator starts to open or

remains open.

Antifreeze protection of the water radiator

Based on the measurement data in outdoor temperature sensor 

TE3

 (outdoor

air <0

°

C) and supply air temperature sensor 

TE2

 (supply air <7

°

C) the

control centre of the unit stops fans 

TF

 and 

PF

. Moreover, valve V1 remains

open and self-actuated dampers 

SP

 of the fans close. This decreases the

freezing risk in the water circulating heating unit 

LP2

. A freezing alert

appears in the display of the control panel. The fans restart automatically as

soon as the risk of freezing passes (supply air > 10 

°

C).

Alarms

The pressure difference switches 

PDS1

 and 

PDS2

 monitor the pressure

difference between the supply and extract air sides. If the pressure difference

rises too high because of dirty filters or clogged ducts, an alarm will be

issued. This is indicated by a symbol ( ) in the main display of the control

panel. If the unit is not equipped with pressure difference switches, the

symbol ( ) appearing in the main display of the control panel reminds of the

need of servicing the unit. The reminder interval can be set between 1...15

months. The factory setting is 4 months. This function is always active. The

fault signal relay in the unit gives potential-free alarm indications on the

following fault conditions:
•  when the defrost function of the water-circulated radiator is on, the points

of the relay close and open at a 10-second interval.

• alarm of high carbon dioxide content (>5000 ppm ) switches the relay at

1-second intervals.

•  in other fault situations, such as a sensor fault ( ) and a filter guard alarm,

the points of the relay close.

Booster or fireplace switch function

The booster or fireplace switch function of the ventilation unit is controlled

either at control panel 

H

 and/or separate switch 

S

, which can be connected

to the connection box of the unit. The mode of operation of the switch is

selected at control panel 

H

. The booster switch function raises fan speed to

the set maximum fan speed for 45 minutes. The fireplace switch stops the

extract air fan for 15 minutes and produces overpressure in the ventilation

zone.

LON remote monitoring control can be implemented with the VALLOX LON converter.

SP

Damper 2 pcs 

Air flow operated 

Standard

Summary of Contents for DIGIT SE L

Page 1: ...e control panel Timing of fan speeds and post heating control at the control panel Week clock control at the control panel Ability to control from several places max 3 control panels LON remote monito...

Page 2: ...ting radiator electricity 1000W or water Heat recovery cell Outdoor air filter EU7 Outdoor and extract air prefilter EU3 Summer winter damper Duct connections duct inside 160mm extension joints 1 2 3...

Page 3: ...IR FLOW Sound power level from the ventilation unit to extract air ducts by octave band Lw dB ADJUSTMENT POSITION AIR FLOW Medium frequency of the octave band Hz ADJUSTMENT POSITION AIR FLOWS supply e...

Page 4: ...off When the indicator is lit the unit is on Carbon dioxide adjustment With this button you set carbon dioxide adjustment on and off When the indicator is lit the adjustment is on Humidity adjustment...

Page 5: ...T TERMINAL BLOCK HUMIDITY SENSORS When mounting two or more humidity sensors connect them to the terminal block of the connection box by connec ting the first humidity sensor to RH1 in place of the re...

Page 6: ...ide DIGIT SE 130 E VALLOX SILENCER UNIT EXTRACT AIR SUPPLY AIR 10 m2 sound absorption ROOM SOUND LEVEL MEASUREMENT Expected sound levels db A in a room with a VALLOX silencer 10 m2 sound absorption Ex...

Page 7: ...PRESSURE Pa 65 69 72 74 76 78 78 51 59 61 64 66 68 69 33 39 44 47 50 52 54 24 28 32 36 38 41 43 19 22 24 26 27 28 31 0 0 0 7 10 15 19 0 0 0 13 0 65 70 72 74 77 78 79 40 45 48 50 53 54 55 Extract air...

Page 8: ...VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes without prior notification INTERNAL ELECTRICAL DIAGRAM 8...

Page 9: ...VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes without prior notification 9 EXTERNAL WIRING DIAGRAM...

Page 10: ...mple with the heat exchanger V supplied with the unit See the mounting examples in the technical specification in the section describing water circulating radiator connections Post heating regulation...

Page 11: ...is switched on at a temperature higher than the stopping temperature factory setting 6 C If preheating cannot keep exhaust air temperature warmer than the stopping temperature the supply air fan stop...

Page 12: ...VALLOX DIGIT SE VKL VALLOX We reserve the right to make changes without prior notification 12 CONTROL DIAGRAM DIGIT SE electric radiator...

Page 13: ...also choose automatic search for thehumidity content threshold on the control panel H One or more modes of control may be used simultaneously the mode demanding boosting is the dominant one Fan speed...

Page 14: ...Ljp TS3 TS4 EU 3 EU 7 PF SOUND ABSORBER DISTRIBUTION PANEL REMOTE MONITORING CENTER OF THE PROPERTY ALARM RUNNING MODE CONTROL MEASUREMENT REGULATION INTERNAL ELECTRICAL AND CONTROL CONNECTIONS OF TH...

Page 15: ...operation ofthe damper motor FG on the basis of measuring results given by theoutdoor sensor TE3 and the extract air temperature sensor TE4 The aim isto get as cool supply air to the ventilation zone...

Page 16: ...becau se of sound conduction Condensing water A water seal is included in the delivery Through the piping connected to this water seal the water condensing from ex tract air is led to a floor drain an...

Reviews: